Plan Review Details - Permit 20021029
Plan Review Stops For Permit 20021029
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By jwitmer Date 2020-04-13 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2020-04-13 Time 06:32 Sent To  
Notes
2020-04-13 07:38:222017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20021029
 ADD: 420 CLAREMORE DR.
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. / APRIL 13/2020
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: SHEET S-0.0 UNDER THE HEADING
 FOUNDATIONS NOTE # 8 STATES TO FOLLOW THE GEOTECHNICAL
 REPORT RECOMMENDATIONS AND SITE PREPARATIONS IN ALL
 ASPECTS. SUBMIT GEOTECHNICAL REPORT BEFORE THE FOTTINGS
 ARE TO BE POURED.
  
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) BUILDING PROVISO: ROOFING PRODUCT APPROVAL TO BE A
 DEFERRED SUBMITTAL. TO BE REVIEWED BY THE DESIGNER OF
 RECORD BEFORE BEING SUBMITTED TOTHE BUILDING
 DEPARTMENT.
  
 JIM WITMER - BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By jwitmer Date 2020-03-03 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2020-03-02 Time 16:12 Sent To  
Notes
2020-03-03 09:45:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20021029
 ADD: 420 CLAREMORE DR.
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. / MARCH 03/2020
 ACTION: DENIED
  
 1) SHEET S-0.0 UNDER THE HEADING FOUNDATIONS NOTE # 8
 STATES TO FOLLOW THE GEOTECHNICAL
 REPORT RECOMMENDATIONS AND SITE PREPARATIONS IN ALL
 ASPECTS. THERE WAS NO GEO-TECHNICAL REPORT SUBMITTED
 FOR THE NEW FOUNDATIONS, HOW TO ACHIEVE 2500 PSF
 BEARING VALUE.
  
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) SHEET S-1.1 SHOWS IN THE ROOF FRAMING PLAN THE ROOF
 RAFTERS TO BE SPACED AT 16 INCHES ON CENTER WHERE AS ON
 THE SAME SHEET IN THE ROOF FRAMING NOTES, NOTE # 1 THE
 NOTE STATES THAT THE 2 X12 RAFTERS ARE TO BE SPACED AT
 24 INCHES ON CENTER. PLEASE CORRECT THE DISCREPANCY IN
 THE PLANS. THE SPAN TABLE, 2017 FBC-B TABLE 2308.7.2(2)
 WILL ALLOW THE 2X12 RAFTERS TO SPAN WITH CEILING THE
 ALLOWABLE SPAN AT 16 INCHES ON CENTER BUT NOT AT 24
 INCHES ON CENTER.
  
 3A) SHEET 10.1 ARCHITECTURAL PLAN HAS THE DOOR SCHEDULE
 AND HARDWARE SCHEDULE WHAT IS NOT SHOWN IS PANIC
 HARDWARE ON THE NEW EXIT DOORS, SLIDERS AND SWING
 DOORS. THE 2017 FBC-B SECTION 1010.1.10 IN AN ASSEMBLY
 OCCUPANCY WITH AN OCCUPANT LOAD OF 50 OR MORE. RAG TOPS
 IN THE PAST HAS HAD ASSEMBLY OCCUPANCY EVENTS IN THE
 PAST. ON THE INTERNET RAGTOPS IS ALSO ADVERTISED AS AN
 AUTOMOBILE MUSEUM ALSO CONSIDERED AN ASSEMBLY
 OCCUPANCY. THE PLANS STATE A BUSINESS OCCUPANCY. PLEASE
 CLARIFY THE USAGE FOR THIS TENANT SPACE, ON THE PLANS,
 IT WILL CLARIFY WHAT TYPE OF HARDWARE WOULD BE REQUIRED
 DEPENDING ON THE MOST RESTRICTIVE USAGE. NOA-
 18-0221.11.
  
 3B) THE SAME HOLDS TRUE FOR THE NEW SWING DOOR BEING
 ADDED. WITHIN THE SUBMITTED TECHNICAL SHEET 1-14 THE
 PRESSURES VARY DEPENDING ON THE LOCKING MECHANISM,
 PLEASE IDENTIFY WHICH LOCKING DEVICES WILL BE USED IN
 THIS INSTALLATION. THANK YOU. NOA-17-0426.02.
  
 4A) IN THIS SUBMITTAL THERE WAS NO ROOFING PRODUCT
 APPROVAL SUBMITTED. SHEET A-3.2 NOTES THE FLORIDA
 APPROVAL FL- 11819-R3. ALL OF THE MODELS OF METAL ROOF
 ARE TO BE INSTALLED OVER OPEN FRAMING, NOT OVER A
 PLYWOOD DECK. PLEASE ALSO SUBMIT THE PRODUCT APPROVAL
 FOR THE UNDERLAYMENT TO REVIEW FOR CODE COMPLIANCE.
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 10:03 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By jpearson Date 2020-03-18 Time 10:47 Rev Time 0.00
Received By jpearson Date 2020-03-18 Time 10:47 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By pleduc Date 2020-04-10 Time   Rev Time 0.00
Received By pleduc Date 2020-04-10 Time 09:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-05 Cont ID  
Sent By pleduc Date 2020-03-05 Time   Rev Time 0.00
Received By pleduc Date 2020-03-05 Time 14:04 Sent To  
Notes
2020-03-05 14:24:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 1.1 - THERE IS AN INDICATION OF OCCUPANCY AS
 GROUP B - BUSINESS.
  
 WHAT IS THE PROPOSED USE OF THE BUILDING? IT APPEARS TO
 BE MERCANTILE PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS.
  
  
 2) SHEET 1.1 - THE ARE NO INDICATIONS OF ELECTICAL
 SHEETS NOR ELECTRICAL WORK
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET 3.0 - THERE IS NO INDICATIONS OF AN OCCUPANCY
 LOAD PER # 1 ABOVE.
  
 PER NFPA 101, CH 7
  
 7.3 CAPACITY OF MEANS OF EGRESS.
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY,
 BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE
 SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF.
 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS,
 WHERE MORE
 THAN ONE MEANS OF EGRESS IS REQUIRED, THE MEANS OF
 EGRESS SHALL BE
 OF SUCH WIDTH AND CAPACITY THAT THE LOSS OF ANY ONE
 MEANS OF
 EGRESS LEAVES AVAILABLE NOT LESS THAN 50 PERCENT OF THE
 REQUIRED
 CAPACITY.
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF
 PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED
 TO THAT USE
 BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED
 IN TABLE
 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B).
 WHERE BOTH
 GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME
 OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE
 GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO
 THE USE FOR
 WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY
 APPLYING THE NET
 AREA FIGURE TO THE NET AREA OF THE PORTION OF THE
 BUILDING DEVOTED TO
 THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 PROVIDE THE SIZE OF EGRESS WIDTH AND THE OCCUPANCY LOAD
 COUNT THROUGH THOSE EXITS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 4) SHEET 3.0 - THERE IS NO INDICATIONS OF THE
 SEPARATION OF THE REQUIRED EGRESSES.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PER # 1 ABOVE, PLEASE PROVIDE THE DIMENSION OF THE
 SEPARATION OF EGRESS
  
  
  
 5) SHEET 3.0 - THERE IS NO CLEAR EXIT SIGANGE WITH
 ILLUMINATION.
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 6) SHEET 3.0 - THERE IS NO INDICATION OF EGRESS
 LIGHTING
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR
 SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE
 ILLUMINATION TO THE
 MINIMUM CRITERIA VALUES HEREIN SPECIFIED.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 7) SHEET 3.0 - PER THE APPLICABLE OCCUPANCY CHAPTER
 EMERGENCY LIGHTING IS NOT INDICATED.
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN SECTION
 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH THE
 FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLOSURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE
 WITH 7.2.1.6.2
  
 PLEASE REVIEW AND PROVIDE.
  
  
 8) SHEET 3.2 & 10.1 - THE REAR DOOR IS NOT INDICATED ON
 THE DOOR SCHEDULE, INCLUDING NO HARDWARE.
  
 PLEASE REVIEW AND CORRECT.
  
 IF THIS IS ALSO A REQUIRED EXIT DOOR, (WHICH IT
 SHOULDBW) ALL EXIT HARDWARE SHALL BE INCLUDED.
  
  
  
 9) PLEASE SECURE AND BIND ALL APPLICABLE SHEETS INTO 2
 COMPLETE SETS NOT 6 SEPARATE SHEETS.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-04-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-09 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2020-04-08 Cont ID  
Sent By shill Date 2020-04-08 Time 16:56 Rev Time 0.00
Received By shill Date 2020-04-08 Time 14:07 Sent To  
Notes
2020-04-08 17:03:16SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLEASE SEE THE PROJECTDOX QUICKSTART GUIDE. THE
 SECOND PAGE GIVES A NAMING CONVENTION. PLEASE FOLLOW AS
 THE PAGES NEED TO BE IN ORDER FOR THE PLAN REVIEWERS TO
 REVIEW EFFICIENTLY.
  
 2. ONLY FIVE PAGES WERE UPLOADED BUT THE PAPER
 SUBMITTAL HAD 13 PAGES. PLEASE UPLOAD ALL PAGES
 REQUIRED FOR REVIEW.
  
 3. IN SUPPORTING DOCUMENTS, TWO NOAS WERE UPLOADED. NOA
 18-0801.12 NEEDS TO BE UPLOADED, UNLESS IT IS NO LONGER
 NEEDED.
  
 4. THE APPLICATION HAS BEEN SCANNED AND ADDED TO THE
 FILE.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-24 Time 11:44 Sent To  
Notes
2020-02-25 11:44:10B24

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 10:04 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 10:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By llouie Date 2020-04-13 Time   Rev Time 0.00
Received By llouie Date 2020-04-13 Time   Sent To  
Notes
2020-04-13 08:18:14* ZONING APPROVAL FOR BUILDING FACADE AND NEW COVERED
 ENTRY ONLY. (SEE STAMPED SHEETS FOR ZONING APPROVED
 PLANS)
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK'D BY AVANN AND VNOEL).
  
 * PER PLANS: "INTERIOR TENANT IMPROVEMENT FOR MARKET
 WILL BE PROVIDED UNDER A SEPARATE PERMIT"
  
 *SEPARATE PERMITS REQUIRED FOR LANDSCAPING AND PARKING
 AREA. BOTH PERMITS MUST BE ISSUED AND THE WORK
 COMPLETED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY (C.O.).
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By llouie Date 2020-03-04 Time   Rev Time  
Received By llouie Date 2020-03-04 Time   Sent To  
Notes
2020-03-04 14:32:11 
 ** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) EXTERIOR MODIFICATIONS DETECTED. PROVIDE A SITE
 PLAN SHOWING THE PROPOSED CHANGES TO THE PROPERTY.
 INCLUDE ALL NECESSARY DIMENSIONS, INCLUDING STRUCTURAL
 SETBACK DISTANCE TO THE PROPERTY LINE. ALL NEW
 STRUCTURES (I.E. CANOPY), ETC. MUST MEET THE MINIMUM
 REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT.
  
 2.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($260,915) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK?D BY AVANN AND VNOEL)
  
 * SCOPE: BUILDING FACADE RENOVATION AND NEW COVERED
 ENTRY.
  
 * PER PLANS: "INTERIOR TENANT IMPROVEMENT FOR MARKET
 WILL BE PROVIDED UNDER A SEPARATE PERMIT.
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 AREA
  