Plan Review Details - Permit 20021000
Plan Review Stops For Permit 20021000
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-05-07 Cont ID  
Sent By pvalenti Date 2020-05-07 Time 11:02 Rev Time 0.00
Received By pvalenti Date 2020-05-07 Time 11:02 Sent To  
Notes
2020-05-07 11:11:14PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED:
  
 THE ENGINEER HAS CLARIFIED AND AND UPDATED THE REQUIRED
 CORRECTIONS.
 THE SIGNED AND SEALED CORRECTIONS (PAGE A-1 AND
 CLARIFICATION LETTER) HAVE BEEN SUBMITTED ON PAPER TO
 THE DROP BOX.
 THEY HAVE NOW BEEN REVIEWED, APPROVED, AND ARE NOW IN
 PROCESS OF BEING SCANNED INTO PROJECT DOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-05 Cont ID  
Sent By rmcphers Date 2020-05-05 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 15:02 Sent To  
Notes
2020-05-05 15:10:00SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A-1 HAS A DETAIL FOR A LEDGER BOARD DETAIL
 SHOWING 3/8" TAPCONS INTO A STEEL TUBE BEAM - TAPCONS
 ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO A STEEL
 BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH
 AND DIAMETER OF THE ANCHOR TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By pvalenti Date 2020-04-24 Time 09:00 Rev Time 0.00
Received By pvalenti Date 2020-04-24 Time 08:31 Sent To  
Notes
2020-04-24 09:27:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 CORRECTIONS NEEDED ? FBC WPB AMENDMENTS 107
  
 1) FAILED: THE NEW DRAWING A?1 HAS A DETAIL FOR A
 LEDGER BOARD DETAIL
 SHOWING 3/8" TAPCONS AT 12" O.C. INTO A STEEL BEAM ?
 TAPCONS ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO
 A STEEL
 BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH
 AND DIAMETER OF THE ANCHOR TO BE USED.
  
 2) OK
  
 3) OK (PER PRODUCT APPROVA)
  
 4) FAILED: PLEASE SHOW THE DETAILS FE EXTERIOR WALL
 INFILL.
  
  
 5) OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-28 Cont ID  
Sent By rmcphers Date 2020-02-28 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2020-02-28 Time 14:22 Sent To  
Notes
2020-02-28 15:28:17SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A-1 HAS A DETAIL FOR A LEDGER BOARD DETAIL
 SHOWING 5/8" LAG BOLTS INTO A STEEL BEAM - LAG BOLTS
 ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO A STEEL
 BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH
 AND DIAMETER OF THE ANCHOR TO BE USED.
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED - FBC
 R301.2.1.1 - - - FBC 1603.1.4
 3) PLEASE SHOW THE EXTERIOR DOOR OPENING WIND DESIGN
 PRESSURE FBC R301.2.1
 4) PLEASE SHOW THE DETAILS FOR THE EXTERIOR WALL
 INFILL.
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOOR.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By jpearson Date 2020-04-29 Time 14:04 Rev Time 0.00
Received By jpearson Date 2020-04-29 Time 14:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By jpearson Date 2020-03-16 Time 14:59 Rev Time 0.00
Received By jpearson Date 2020-03-16 Time 14:44 Sent To  
Notes
2020-03-16 14:58:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SOME AREAS ARE MISSING THE REQUIRED SMOKE
 ALARM. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 2. PLAN DOES NOT SHOW THE DEDICATED CIRCUIT FOR
 BATHROOM RECEPTACLE OUTLET. A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE
 E3703.4
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-05 Cont ID  
Sent By rmcphers Date 2020-05-05 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2020-05-04 Time 15:05 Sent To  
Notes
2020-05-04 15:06:13ROUTED TO PETER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-29 Time   Rev Time 0.00
Received By jgomez Date 2020-04-22 Time 14:47 Sent To  
Notes
2020-04-23 14:59:47SENT TO R1 BIN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-24 Time 11:41 Sent To  
Notes
2020-02-25 11:41:41R03

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-27 Cont ID  
Sent By jgomez Date 2020-04-27 Time 13:53 Rev Time 0.00
Received By jgomez Date 2020-04-27 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By ccole Date 2020-03-17 Time 16:09 Rev Time 0.00
Received By ccole Date 2020-03-17 Time 16:09 Sent To I
Notes
2020-03-17 16:18:371ST REVIEW FBC-2017 PLUMBING
 PERMIT #20021000
 3/17/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: ADD THE RELOCATED BATHTUB TO THE SANITARY
 RISER- SECTIONS P3005.4 AND P3101.2.1 FBC RES
  
 2) E-1: PROVIDE A SANITARY RISER DRAWING FOR THE
 REMODELED KITCHEN- SINK AND DISHWASHER DRAINS AND
 VENTING- SECTIONS P3005.4 AND P3101.2.1 FBC RES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-07 Cont ID  
Sent By pvalenti Date 2020-05-07 Time 11:12 Rev Time 0.00
Received By pvalenti Date 2020-05-07 Time 11:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-29 Cont ID  
Sent By shill Date 2020-04-29 Time 11:28 Rev Time 0.00
Received By shill Date 2020-04-29 Time 11:28 Sent To  
Notes
2020-04-29 11:28:31ORIGNAL S&S PLANS PROVIDED
  