Plan Review Details - Permit 20020953
Plan Review Stops For Permit 20020953
Review Stop ENG-APP ENGINEERING APP. REVIEW
Rev No 2 Status F Date 2020-08-06 Cont ID  
Sent By gpatrie Date 2020-08-06 Time 09:14 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2020-08-06 09:13:53PROJECT #1801CVFF.219 / FL JPTRFL01-000097-NATIONS BANK
  
 1) PG 16 / HAND HOLE LOCATION IS INCORRECT.
  
 CONTACT: GORDON PATRIE AT [email protected]

Review Stop ENG-APP ENGINEERING APP. REVIEW
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By gpatrie Date 2020-03-04 Time 13:07 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2020-03-04 13:10:321) DRAWINGS NOT OVER AERIALS.
  
 2) CITY STANDART DETAILS NOT SHOWN,

Review Stop Z ZONING
Rev No 3 Status F Date 2020-08-19 Cont ID  
Sent By eschneid Date 2020-08-19 Time 09:33 Rev Time 1.00
Received By eschneid Date 2020-08-19 Time 09:33 Sent To  
Notes
2020-08-19 09:38:39FAILED
  
 PERMIT 20020953 - UNDERGROUND FIBER PBL & FORUM MCI
 PROJECT #1801CVFF.219 - 2ND RESUB
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 THE FOLLOWING ITEMS NEED TO BE ADDRESSED OR THE PERMIT
 WILL NOT BE APPROVED.
  
 1) ENGINEERING PLAN -
  
 A. THE ENGINEERING PLAN DOES NOT MATCH THE SURVEY IN
 SHOWING THE LOCATION OF THE RIGHT-OF-WAY LINE. HOWEVER,
 THE LOCATION OF THE FIBER INSTALL AND THE HANDHOLE ARE
 SHOWN ON THE ENGINEERING PLAN IN THE PARKWAY BETWEEN
 THE SIDEWALK AND THE EDGE OF PAVEMENT, WHICH THE SURVEY
 VERIFIES IS WITHIN THE RIGHT-OF-WAY. CORRECT THE
 RIGHT-OF-WAY LINE LOCATION ON THE RESUBMITTED
 ENGINEERING PLAN.
  
 B. THE BORE SHOWN AT 10 FEET BELOW GRADE IS AT A
 SUFFICIENT DEPTH TO AVOID PALM TREE DAMAGE.
  
 PLEASE NOTE:
  
 THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811
 TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL
 DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST
 BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE
 WORK.
  
 THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A
 CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE
 WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES
 THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS,
 OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-09 Cont ID  
Sent By eschneid Date 2020-04-09 Time 10:33 Rev Time 0.50
Received By eschneid Date 2020-04-09 Time 10:33 Sent To  
Notes
2020-04-09 10:34:39PERMIT 20020953 - UNDERGROUND FIBER PBL & FORUM MCI
 PROJECT #1801CVFF.219
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) SURVEY - THE SURVEY DOES NOT SHOW SUFFICIENT
 INFORMATION FOR STAFF TO VERIFY WHAT IS SHOWN ON THE
 ENGINEERING PLANS.
  
 A. REPEAT COMMENT: THE SURVEY MUST CLEARLY SHOW THE
 RIGHT-OF-WAY LINE AND THE SIDEWALK.
  
 B. UPDATED COMMENT: ALL UNDERGROUND UTILITIES NEED TO
 BE PROVIDED ON THE SURVEY. THE DIMENSIONS TO THE
 PROPOSED HANDHOLE NEED TO BE PROVIDED. ---- THE
 ENGINEERING PLANS SHOW MORE UNDERGROUND UTILITIES THAN
 ARE SHOWN ON THE SURVEY. IF THE BORE IS PROPOSED WITHIN
 FIVE (5) FEET OF AN EXISTING UTILITY, YOU NEED TO
 PROVIDE A LETTER FROM THAT UTILITY THAT THE PROPOSED
 BORE DOES NOT INTERFERE WITH THE PROVISIONS OF THEIR
 SERVICES.
  
 C. REPEAT COMMENT: THE LOCATIONS OF THE PALM TREES AND
 THEIR ROOT ZONE NEED TO BE SHOWN. THE FIBER BORE NEEDS
 TO BE CLEARLY SHOWN AVOIDING DAMAGE TO THE PALM ROOT
 ZONES.
  
 D. THE ENGINEERING PLANS MUST SHOW THE SAME CONDITIONS
 AS THE SURVEY, SO THAT STAFF CAN VERIFY THAT NONE OF
 THE PROPOSED WORK IS BEING INSTALLED ON PRIVATE
 PROPERTY.
  
 3) UPDATED COMMENT: EVIDENCE OF INSURANCE COVERAGE
  
 A. SINCE THE COMMUNICATIONS FACILITIES PLACEMENT PERMIT
 APPLICATION LISTS MCIMETRO ACCESS TRANSMISSION SERVICES
 CORP AS THE REGISTRANT, THIS IS WHOSE CERTIFICATE OF
 LIABILITY INSURANCE NEEDS TO BE PROVIDED.
  
 B. THE CERTIFICATE OF LIABILITY INSURANCE NEEDS TO BE
 REVISED TO NAME THE CITY OF WEST PALM BEACH, ITS
 COMMISSIONERS, OFFICERS, EMPLOYEES AND AGENTS AS
 ADDITIONAL INSURED.
  
 C. THE CERTIFICATE HOLDER IS THE ENGINEERING SERVICES
 DEPARTMENT.
  
 4) POLE STYLE - PLEASE NOTE THAT THE FUTURE POLES ARE
 REQUIRED TO MEET THE CITY CONCEALMENT STANDARDS
 OUTLINED IN SECTION 78-411 OF THE CITY CODE.
  
 NOTE: STAFF WILL NOT APPROVE THE INSTALLATION OF A SIX
 (6) FOOT TALL MARKER POLE ADJACENT TO THE HANDHOLE. IF
 THE HANDHOLE NEEDS TO BE MARKED, THEN PROVIDE THE
 INFORMATION ON THE HANDHOLE COVER.
  
 5) REPEAT COMMENT: ELECTRONIC FORMAT OF SUBMITTAL - A
 COPY OF ALL OF THE SUBMITTAL MATERIAL MUST BE SUBMITTED
 IN ELECTRONIC FORMAT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By eschneid Date 2020-03-03 Time 15:47 Rev Time 0.50
Received By eschneid Date 2020-03-03 Time 15:47 Sent To  
Notes
2020-03-03 16:23:13PERMIT 20020953 - UNDERGROUND FIBER PBL & FORUM MCI
 PROJECT #1801CVFF.219
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) SURVEY - THE SURVEY DOES NOT SHOW SUFFICIENT
 INFORMATION FOR STAFF TO VERIFY WHAT IS SHOWN ON THE
 ENGINEERING PLANS.
  
 A. THE SURVEY MUST CLEARLY SHOW THE RIGHT-OF-WAY LINE
 AND THE SIDEWALK.
  
 B. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE
 SURVEY. THE DIMENSIONS TO THE PROPOSED HANDHOLE NEED TO
 BE PROVIDED.
  
 C. THE LOCATIONS OF THE PALM TREES AND THEIR ROOT ZONE
 NEED TO BE SHOWN. THE FIBER BORE NEEDS TO BE CLEARLY
 SHOWN AVOIDING DAMAGE TO THE PALM ROOT ZONES.
  
 D. THE ENGINEERING PLANS MUST SHOW THE SAME CONDITIONS
 AS THE SURVEY, SO THAT STAFF CAN VERIFY THAT NONE OF
 THE PROPOSED WORK IS BEING INSTALLED ON PRIVATE
 PROPERTY.
  
 3) TIMETABLE - YOU ARE REQUIRED TO PROVIDE THE
 ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE PROJECT OR
 EACH PHASE THEREOF.
  
 4) EVIDENCE OF INSURANCE COVERAGE - PROVIDE EVIDENCE OF
 THE INSURANCE COVERAGE REQUIRED UNDER SECTION 78-406 OF
 THE CITY CODE.
  
 5) POLE STYLE - PLEASE NOTE THAT THE FUTURE POLES ARE
 REQUIRED TO MEET THE CITY CONCEALMENT STANDARDS
 OUTLINED IN SECTION 78-411 OF THE CITY CODE.
  
 6) ELECTRONIC FORMAT OF SUBMITTAL - A COPY OF ALL OF
 THE SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  