Plan Review Stops For Permit 20020949 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2020-03-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-04 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-04 |
Time |
16:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-02 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-02 |
Time |
13:03 |
Sent To |
|
|
Notes |
2020-03-02 13:04:44 | ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM | | THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-04-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-29 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-29 |
Time |
14:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-04-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-09 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-09 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-02 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-02 |
Time |
11:32 |
Sent To |
|
|
Notes |
2020-03-02 12:45:38 | ADDED OFFICE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) PLEASE SHOW DOOR LABELED (106) TO BE SELF CLOSING | | AND LATCH TO COMPLY WITH FBC 716.5.9 | | 2) CABINETS IN OFFICE (101) ARE SHOWN AT 2 DIFFERENT | | ELEVATIONS ON DRAWING (A1.1.4) - PLEASE CLEARIFY THE | | CABINET HEIGHT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2020-05-06 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-05-06 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-05-06 |
Time |
08:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-04-13 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-04-13 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-04-13 |
Time |
16:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-03-18 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-03-18 |
Time |
08:38 |
Sent To |
|
|
Notes |
2020-03-18 08:38:04 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | EQUIPMENT PER CODE. NEC 210.63 | | 2. PANEL SCHEDULES SHOW TWO PANEL HA AND TWO PANEL LA, | | EACH WITH DIFFERENT LOADS. PROVIDE CLARIFICATION AND/OR | | CORRECTION. WPB FBC 107.2.1; NEC 215.5, 408.4 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-04-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-04-22 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-04-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-04-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-04-08 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2020-03-06 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2020-03-06 |
Time |
|
Sent To |
|
|
Notes |
2020-03-06 17:29:09 | DIGITAL PLAN REVIEW PASS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-05-06 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-05-06 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-04-21 |
Time |
10:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-04-13 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-04-13 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-04-07 |
Time |
15:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-03-21 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-02-21 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2020-05-06 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-05-06 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-04-30 |
Time |
16:27 |
Sent To |
|
|
Notes |
2020-05-05 10:16:14 | MU-2020-014914 - $280.55 - PAID | 2020-04-30 16:27:34 | 4/30/20 SENT TO IMPACT FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-02 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-02 |
Time |
12:54 |
Sent To |
|
|
Notes |
2020-03-02 12:58:24 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-04-22 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-04-22 |
Time |
16:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-04-10 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-04-10 |
Time |
12:18 |
Sent To |
|
|
Notes |
2020-04-10 13:19:58 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #20020949 | | 4/10/20 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE AC CALCULATION SUMMARY SHOWS THE 8.5-TON CARRIER | | RTU IS OVER SIZED. THE CALCULATIONS INDICATE 74.1 MBH | | TOTAL COOLING AND 57 MBH SENSIBLE COOLING REQUIRED | | (APPROX. 6.5 TON), HOWEVER THE RTU-1 SCHEDULE ON THE | | PLAN INDICATES 103 MBH TOTAL AND 81 MBH COOLING- | | SECTION C403.2.1 FBC EC. | | | | 2) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN | | ADDRESSED ON THE PLAN. 4) M2.1 & M6.1: INDICATE HOW O/A | | IS BEING PROVIDED TO THE LARGE CONFERENCE ROOM AND | | PROVIDE CALCULATIONS- TABLE 403.3.1.1 FBC M. PLEASE | | NOTE THAT AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS | | REQUIRED FOR THE REQUIRED O/A INLET OR DUCT TO THE AIR | | HANDLER- SECTION C403.2.4.3 FBC EC. | | | | 3) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE | | RTU HAS NOT BEEN PROVIDED. PLEASE NOTE THE ENGINEERING | | MAY BE DEFERRED- SECTION 107.3.4.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-03-16 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-03-16 |
Time |
15:34 |
Sent To |
|
|
Notes |
2020-03-16 16:33:59 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #20020949 | | 3/16/20 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | RTU AND THE MINI-SPLIT SYSTEMS- SECTION C403.2.1 FBC | | EC. | | | | 2) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE | | SUPPLY AIR SYSTEM OF THE RTU- SECTION 606.2.1. | | | | 3) M2.1 & M6.1: PROVIDE AUTOMATICALLY CONTROLLED | | SHUTOFF DAMPERS FOR THE RTU O/A INTAKE- SECTION | | C403.2.4.3 FBC EC. | | | | 4) M2.1 & M6.1: INDICATE HOW O/A IS BEING PROVIDED TO | | THE LARGE CONFERENCE ROOM AND PROVIDE CALCULATIONS- | | TABLE 403.3.1.1 FBC M. PLEASE NOTE THAT AN | | AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS REQUIRED FOR | | THE REQUIRED O/A INLET OR DUCT- SECTION C403.2.4.3 FBC | | EC. | | | | 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS | | OF THE RTU AND THE CU, AND PROVIDE INSTALLATION | | ENGINEERING- SECTION 301.15 FBC M | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2020-04-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-04-29 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-04-29 |
Time |
14:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-04-10 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-04-10 |
Time |
09:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
jbaker |
Date |
2020-03-20 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
jbaker |
Date |
2020-03-20 |
Time |
11:06 |
Sent To |
|
|
Notes |
2020-03-20 11:09:16 | 1. PROVIDE SIZE OF EXISTING GREASE INTERCEPTOR. 2017 | | FPC CHAPTER 10 | | 2. ROUTE MOP SINKS, FLOOR SINKS, AND SANDWICH CASES AND | | ANY OTHER GREASE GENERATING PIECE OF EQUIPMENT TO | | GREASE INTERCEPTOR. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2020-04-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-04-29 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-04-29 |
Time |
14:17 |
Sent To |
|
|
Notes |
2020-04-22 16:56:16 | ARCHITECTURAL PLANS OK. MEP PLANS ARE NOT | | ELECTRONICALLY SIGNED AND SEALED- FL. STATE 471.025 AND | | SECTION 61G1523.005 FAC. | | CCOLE- 4/29/20 |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-04-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-09 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-09 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-02 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-02 |
Time |
12:58 |
Sent To |
|
|
Notes |
2020-03-02 12:59:55 | ELECTRONIC SIGNED DRAWINGS O.K. AT THIS TIME - ALL NEW | | DRAWINGS WILL NEED TO BE CHECKED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-04-28 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2020-04-28 |
Time |
10:15 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2020-04-24 |
Time |
16:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-03-03 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2020-03-03 |
Time |
11:32 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2020-03-03 |
Time |
11:32 |
Sent To |
|
|
Notes |
2020-03-03 11:33:25 | FAILED | | | | PROVIDE RESPONSES IN WRITING. | | | | 1) ORDINANCE NO. 3987-06 REQUIRES THE FOLLOWING | | INFORMATION TO BE PROVIDED CONCURRENT WITH THE BUILDING | | PERMIT APPLICATION: | | | | A. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND | | ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT | | WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE | | APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE | | USES WITHIN BUILDINGS 1, 2 AND 3. THE SPECIFIC SQUARE | | FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE | | ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE | | TABLE, UNLESS THE PROPERTY OWNER PROVIDES A TRAFFIC | | EQUIVALENCY STATEMENT, PREPARED BY A LICENSED TRAFFIC | | ENGINEER, DEMONSTRATING THAT THE APPROVED TRAFFIC | | CONCURRENCY FOR THE PROJECT IS NOT EXCEEDED. | | | | B. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC | | ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING | | AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH | | ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER | | OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR | | EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. THE | | TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED | | WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF | | THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD. | | | | 2) THE DEMOLITION PLAN DOES NOT CALL OUT THE REMOVAL OF | | THE WESTERNMOST OF THE PAIR OF DOORS AT THE NEW LOBBY | | AREA, YET IT IS NOT SHOWN ON THE LIFE SAFETY OR FLOOR | | PLAN. ALL PLANS NEED TO SHOW THE FULL EXTENT OF THE | | ACTUAL WORK BEING DONE. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] | | |
|
|