Plan Review Stops For Permit 20020926 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2020-04-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-04-24 |
Time |
08:23 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-04-24 |
Time |
08:23 |
Sent To |
|
|
Notes |
2020-04-24 08:26:12 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW APPROVED: | | THE CONTRACTOR SUBMITTED AN ORIGINAL SIGNED AND SEALED | | GENERAC SPEC. FOR WIND LOAD ANCHORING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2020-04-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-04-17 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-04-17 |
Time |
16:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2020-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-04-02 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-04-02 |
Time |
14:39 |
Sent To |
I |
|
Notes |
2020-04-02 14:47:27 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE NEW PRE-FAB GENERATOR PAD ENGINEERING DOES NOT | | LIST THE MODEL NUMBER FOR THE 22 KW GENERAC MODEL | | G007043 WEIGHING 466 LB. FBC 107.2.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-19 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-19 |
Time |
16:34 |
Sent To |
|
|
Notes |
2020-03-19 16:34:34 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1 | | 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND | | DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE | | NUMBER 2 ON THE SLAB ENGINEERING DRAWING. | | 2) PLEASE SHOW GENERATOR EXHAUST AT 10 FEET AWAY FROM | | AN OPENING INTO THE HOUSE PER FBC R303.5.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-03-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-06 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-06 |
Time |
15:29 |
Sent To |
|
|
Notes |
2020-03-06 15:40:06 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1 | | 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND | | DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE | | NUMBER 2 ON THE SLAB ENGINEERING DRAWING. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-03-18 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-03-18 |
Time |
14:37 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-04 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-03-04 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-03-04 |
Time |
06:16 |
Sent To |
I |
|
Notes |
2020-03-04 06:30:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. AIC RATING OF MB IN SERVICE RATED ATS IS SHOWN TO BE | | 10,000 AIC. | | | | PROVIDE AVAILABLE SHORT CIRCUIT INFORMATION FROM THE | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC | | RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS | | IS ADEQUATE. NEC 110.9, 110.10 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-03-02 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-03-02 |
Time |
07:11 |
Sent To |
|
|
Notes |
2020-03-02 07:17:25 | GAS PERMIT UNDER 20020923 BY TKL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-04-02 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-04-02 |
Time |
14:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-19 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-13 |
Time |
13:03 |
Sent To |
|
|
Notes |
2020-03-19 16:35:58 | PLANS TAKEN TO PERMIT LIBRARY | 2020-03-16 13:03:54 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-06 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-02-24 |
Time |
17:46 |
Sent To |
|
|
Notes |
2020-03-06 15:50:20 | PLANS TAKEN TO PERMIT LIBRARY | 2020-03-04 15:42:22 | 3/4 ROUTED TO BLDG MISC 2 | 2020-02-27 16:50:43 | 2/27 ROUTED TO GENERATOR INBOX | 2020-02-24 17:46:34 | TO ZONING | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-02-27 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-02-27 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-02-27 |
Time |
16:01 |
Sent To |
I |
|
Notes |
|
|