Plan Review Details - Permit 20020926
Plan Review Stops For Permit 20020926
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-04-24 Cont ID  
Sent By pvalenti Date 2020-04-24 Time 08:23 Rev Time 0.00
Received By pvalenti Date 2020-04-24 Time 08:23 Sent To  
Notes
2020-04-24 08:26:12PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED:
 THE CONTRACTOR SUBMITTED AN ORIGINAL SIGNED AND SEALED
 GENERAC SPEC. FOR WIND LOAD ANCHORING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-17 Cont ID  
Sent By pvalenti Date 2020-04-17 Time 16:06 Rev Time 0.00
Received By pvalenti Date 2020-04-17 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 14:39 Sent To I
Notes
2020-04-02 14:47:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NEW PRE-FAB GENERATOR PAD ENGINEERING DOES NOT
 LIST THE MODEL NUMBER FOR THE 22 KW GENERAC MODEL
 G007043 WEIGHING 466 LB. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 16:34 Rev Time 0.00
Received By rmcphers Date 2020-03-19 Time 16:34 Sent To  
Notes
2020-03-19 16:34:34GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND
 DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE
 NUMBER 2 ON THE SLAB ENGINEERING DRAWING.
 2) PLEASE SHOW GENERATOR EXHAUST AT 10 FEET AWAY FROM
 AN OPENING INTO THE HOUSE PER FBC R303.5.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2020-03-06 Time 15:29 Sent To  
Notes
2020-03-06 15:40:06GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND
 DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE
 NUMBER 2 ON THE SLAB ENGINEERING DRAWING.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jleahy Date 2020-03-18 Time 14:37 Rev Time 0.00
Received By jleahy Date 2020-03-18 Time 14:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By fgiaquin Date 2020-03-04 Time 06:36 Rev Time 0.00
Received By fgiaquin Date 2020-03-04 Time 06:16 Sent To I
Notes
2020-03-04 06:30:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AIC RATING OF MB IN SERVICE RATED ATS IS SHOWN TO BE
 10,000 AIC.
  
 PROVIDE AVAILABLE SHORT CIRCUIT INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-03-02 Cont ID  
Sent By lcrespo Date 2020-03-02 Time 07:15 Rev Time 0.00
Received By lcrespo Date 2020-03-02 Time 07:11 Sent To  
Notes
2020-03-02 07:17:25GAS PERMIT UNDER 20020923 BY TKL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 16:35 Rev Time 0.00
Received By rmcphers Date 2020-03-13 Time 13:03 Sent To  
Notes
2020-03-19 16:35:58PLANS TAKEN TO PERMIT LIBRARY
2020-03-16 13:03:54RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2020-02-24 Time 17:46 Sent To  
Notes
2020-03-06 15:50:20PLANS TAKEN TO PERMIT LIBRARY
2020-03-04 15:42:223/4 ROUTED TO BLDG MISC 2
2020-02-27 16:50:432/27 ROUTED TO GENERATOR INBOX
2020-02-24 17:46:34TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-27 Cont ID  
Sent By rfalcone Date 2020-02-27 Time 16:01 Rev Time 0.00
Received By rfalcone Date 2020-02-27 Time 16:01 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved