Plan Review Details - Permit 20020924
Plan Review Stops For Permit 20020924
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-06-02 Cont ID  
Sent By pvalenti Date 2020-06-02 Time 13:54 Rev Time 0.00
Received By pvalenti Date 2020-06-02 Time 13:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-04-02 Cont ID  
Sent By jbrooks Date 2020-04-02 Time 10:24 Rev Time 0.00
Received By jbrooks Date 2020-04-02 Time 10:24 Sent To  
Notes
2020-04-02 10:24:55JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. PLEASE PROVIDE SIGNED AND SEALED
 SITE-SPECIFIC WIND DESIGN PRESSURE FROM AN ARCHITECT OR
 ENGINEER PER NOTE NUMBER 2 ON THE SLAB ENGINEERING
 DRAWING. AS PER PREVIOUS REVIEWER?S NOTE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 09:25 Sent To  
Notes
2020-03-23 09:25:23GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND
 DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE
 NUMBER 2 ON THE SLAB ENGINEERING DRAWING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 11:24 Rev Time 0.00
Received By rmcphers Date 2020-03-19 Time 11:23 Sent To  
Notes
2020-03-19 12:32:17GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND
 DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE
 NUMBER 2 ON THE SLAB ENGINEERING DRAWING.
 2) PLEASE SHOW THE DISTANCE FROM THE GENERATOR TO
 OPENINGS INTO THE HOUSE.
 3) PLEASE PROVIDE A STATEMENT ON THE DRAWING THAT THE
 ELEVATION OF THE SLAB WILL MATCH THE FINISHED FLOOR
 ELEVATION OF THE EXISTING HOUSE LIVING SPACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-03-06 Time 15:08 Sent To  
Notes
2020-03-06 15:14:36GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC WIND
 DESIGN PRESSURE FROM AN ARCHITECT OR ENGINEER PER NOTE
 NUMBER 2 ON THE SLAB ENGINEERING DRAWING.
 2) PLEASE SHOW THE DISTANCE FROM THE GENERATOR TO
 OPENINGS INTO THE HOUSE.
 3) PLEASE PROVIDE A STATEMENT ON THE DRAWING THAT THE
 ELEVATION OF THE SLAB WILL MATCH THE FINISHED FLOOR
 ELEVATION OF THE EXISTING HOUSE LIVING SPACE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jleahy Date 2020-03-18 Time 11:58 Rev Time 0.00
Received By jleahy Date 2020-03-18 Time 11:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By fgiaquin Date 2020-03-04 Time 06:55 Rev Time 0.00
Received By fgiaquin Date 2020-03-04 Time 06:43 Sent To I
Notes
2020-03-04 06:55:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AIC RATING OF MB IN SERVICE RATED ATS IS SHOWN TO BE
 10,000 AIC.
  
 PROVIDE AVAILABLE SHORT CIRCUIT INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-02 Cont ID  
Sent By jbrooks Date 2020-04-02 Time 10:25 Rev Time 0.00
Received By jbrooks Date 2020-03-30 Time 13:15 Sent To  
Notes
2020-03-30 13:15:38RESUB ROUTED TO BLDG MISC 2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2020-03-20 Time 16:07 Sent To  
Notes
2020-03-23 09:26:15PLANS TAKEN TO PERMIT LIBRARY
2020-03-20 16:07:34RESUB ROUTED TO RMCPHERSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 12:32 Rev Time 0.00
Received By rmcphers Date 2020-03-13 Time 13:05 Sent To  
Notes
2020-03-19 12:33:13PLANS TAKEN TO PERMIT LIBRARY
2020-03-17 17:47:07ROUTED TO FGIAQUINTO INBOX
2020-03-16 13:05:17RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 15:25 Rev Time 0.00
Received By rmcphers Date 2020-02-24 Time 17:46 Sent To  
Notes
2020-03-06 15:26:11PLANS TAKEN TO PERMIT LIBRARY
2020-03-04 15:42:003/4 BLDG MISC 2
2020-02-27 16:51:122/27 ROUTED TO GENERATOR INBOX
2020-02-24 17:47:06TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-17 Cont ID  
Sent By rfalcone Date 2020-03-17 Time 15:37 Rev Time 0.00
Received By rfalcone Date 2020-03-17 Time 15:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By rfalcone Date 2020-02-27 Time 16:02 Rev Time 0.00
Received By rfalcone Date 2020-02-27 Time 16:02 Sent To I
Notes
2020-02-27 16:02:372/27/20 FAILED.
  
 PLEASE PROVIDE THE SETBACKS FROM THE PROPERTY LINES TO
 THE GENERATOR.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  