Plan Review Details - Permit 20020852
Plan Review Stops For Permit 20020852
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2020-04-16 Cont ID  
Sent By rmcphers Date 2020-04-16 Time 15:23 Rev Time 0.00
Received By rmcphers Date 2020-04-16 Time 15:22 Sent To  
Notes
2020-04-16 15:25:17CHANGE OF OCCUPANCY IS UNDER PERMIT 20040115

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 08:17 Rev Time 0.00
Received By rmcphers Date 2020-03-20 Time 14:43 Sent To  
Notes
2020-03-20 14:47:01FIRE ALARMS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - A CHANGE OF USE OF THE SINGLE
 FAMILY HOUSE TO AN R3 OCCUPANCY CLASSIFICATION NEEDS TO
 COMPLY WITH FBC EXISTING BUILDING CHAPTER 10 (CHANGE OF
 OCCUPANCY)
 1) PLEASE SHOW THAT THE SINGLE FAMILY HOUSE HAS
 EXISTING SPRINKLERS THAT COMPLY WITH FBC 310.5.1 CARE
 FACILITIES WITHIN A DWELLING.
 CARE FACILITIES FOR FIVE OR FEWER PERSONS RECEIVING
 CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING ARE
 PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE,
 RESIDENTIAL PROVIDED AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.3 OR
 SECTION P2904 OF THE FLORIDA BUILDING CODE,
 RESIDENTIAL.
  
 FBC EXISTING BUILDING 1001.2 CERTIFICATE OF OCCUPANCY.
 A CHANGE OF OCCUPANCY OR A CHANGE OF OCCUPANCY WITHIN A
 SPACE WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM
 THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL NOT BE MADE TO ANY
 STRUCTURE WITHOUT THE APPROVAL OF THE CODE OFFICIAL.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE CHANGE OF
 OCCUPANCY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2020-03-10 Time 08:47 Sent To  
Notes
2020-03-11 13:12:28ADD FIRE ALARM -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) IS THIS A CHANGE OF OCCUPANCY CLASSIFICATION ?
 2) PLEASE SHOW ON THE DRAWING THE OCCUPANCY
 CLASSIFICATION AND BUILDING USE PER FBC CHAPTER 3.
 3) IF THIS IS A CHANGE OF OCCUPANCY PLEASE SHOW ALL
 REQUIREMENTS TO COMPLY WITH FBC EXISTING BUILDING
 CHAPTER 10

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By ppetty Date 2020-03-19 Time 10:29 Rev Time 0.00
Received By ppetty Date 2020-03-19 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-05 Cont ID  
Sent By fgiaquin Date 2020-03-05 Time 06:55 Rev Time 0.00
Received By fgiaquin Date 2020-03-05 Time 06:46 Sent To I
Notes
2020-03-05 06:55:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE TWO COPIES OF PLANS, ONLY ONE PLAN
 SUBMITTED. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED
 AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED
 BY THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT
 ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE
 THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC
 107.2.1, 107.3.5
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN, PROVIDE ACCURATE
 VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL.
 INFORMATIONAL NOTE. FIRE ALARM DESIGNS $5000 AND OVER
 MUST BE DESIGNED AND SIGNED/SEALED BY A DESIGN
 PROFESSIONAL. FBC 105.3.1.2 #4
  
 3. PASS FIRE REVIEW
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-13 Cont ID  
Sent By pleduc Date 2020-03-13 Time   Rev Time 0.00
Received By pleduc Date 2020-03-13 Time 11:54 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 11:41 Sent To E
Notes
2020-03-04 11:45:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM
 SYSTEM.
  
 PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION PER THE
 FLORIDA FIRE PREVENTION CODE.
  
  
  
 2) THE DOES NOT APPEAR TO BE SUFFICINET OCCUPANT
 NOTIFICATION IN ALL THE ROOMS.
  
 PER # 1 ABOVE , PLEASE REVIEW CODE COMPLIANT
 NOTIFICATION IN ALL APPLICABLE AREAS OR JUSTIFY WITH A
 SPECIFIC DETAILS IN A WRITTEN NARRATIVE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 11:47 Rev Time 0.00
Received By rmcphers Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-16 Cont ID  
Sent By rmcphers Date 2020-04-16 Time 15:26 Rev Time 0.00
Received By rmcphers Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 08:17 Rev Time 0.00
Received By rmcphers Date 2020-03-11 Time 13:17 Sent To  
Notes
2020-03-23 08:18:34PLANS TAKEN TO PERMIT LIBRARY
2020-03-19 11:35:303/191 GIVEN TO RMCPHERSON
2020-03-16 18:19:40ROUTED TO ELECTRICAL INBOX
2020-03-12 13:18:05RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2020-02-20 Time 13:22 Sent To  
Notes
2020-03-11 13:13:18PLANS TAKEN TO PERMIT LIBRARY
2020-03-05 07:32:07ROUTED TO MECHANICAL INBOX
2020-02-21 13:22:40ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-03-10 Cont ID  
Sent By medwards Date 2020-03-10 Time 09:46 Rev Time  
Received By medwards Date   Time   Sent To  
Notes
2020-03-10 09:47:10NO DUCT DETECTORS SHOWN IN THIS SYSTEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-02 Cont ID  
Sent By shill Date 2020-05-02 Time 11:04 Rev Time 0.00
Received By shill Date 2020-05-02 Time 11:04 Sent To  
Notes
2020-05-02 11:04:27PLANS PREPARED BY CONTRACTOR