Plan Review Stops For Permit 20020852 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
N |
Date |
2020-04-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-16 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-16 |
Time |
15:22 |
Sent To |
|
|
Notes |
2020-04-16 15:25:17 | CHANGE OF OCCUPANCY IS UNDER PERMIT 20040115 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-23 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-20 |
Time |
14:43 |
Sent To |
|
|
Notes |
2020-03-20 14:47:01 | FIRE ALARMS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - A CHANGE OF USE OF THE SINGLE | | FAMILY HOUSE TO AN R3 OCCUPANCY CLASSIFICATION NEEDS TO | | COMPLY WITH FBC EXISTING BUILDING CHAPTER 10 (CHANGE OF | | OCCUPANCY) | | 1) PLEASE SHOW THAT THE SINGLE FAMILY HOUSE HAS | | EXISTING SPRINKLERS THAT COMPLY WITH FBC 310.5.1 CARE | | FACILITIES WITHIN A DWELLING. | | CARE FACILITIES FOR FIVE OR FEWER PERSONS RECEIVING | | CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING ARE | | PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE, | | RESIDENTIAL PROVIDED AN AUTOMATIC SPRINKLER SYSTEM IS | | INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.3 OR | | SECTION P2904 OF THE FLORIDA BUILDING CODE, | | RESIDENTIAL. | | | | FBC EXISTING BUILDING 1001.2 CERTIFICATE OF OCCUPANCY. | | A CHANGE OF OCCUPANCY OR A CHANGE OF OCCUPANCY WITHIN A | | SPACE WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM | | THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA | | BUILDING CODE, BUILDING SHALL NOT BE MADE TO ANY | | STRUCTURE WITHOUT THE APPROVAL OF THE CODE OFFICIAL. | | | | 2) A SEPARATE PERMIT IS REQUIRED FOR THE CHANGE OF | | OCCUPANCY. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-03-11 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-11 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-10 |
Time |
08:47 |
Sent To |
|
|
Notes |
2020-03-11 13:12:28 | ADD FIRE ALARM - | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) IS THIS A CHANGE OF OCCUPANCY CLASSIFICATION ? | | 2) PLEASE SHOW ON THE DRAWING THE OCCUPANCY | | CLASSIFICATION AND BUILDING USE PER FBC CHAPTER 3. | | 3) IF THIS IS A CHANGE OF OCCUPANCY PLEASE SHOW ALL | | REQUIREMENTS TO COMPLY WITH FBC EXISTING BUILDING | | CHAPTER 10 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2020-03-19 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2020-03-19 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-03-05 |
Time |
06:55 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-03-05 |
Time |
06:46 |
Sent To |
I |
|
Notes |
2020-03-05 06:55:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE TWO COPIES OF PLANS, ONLY ONE PLAN | | SUBMITTED. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED | | AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED | | BY THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT | | ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE | | THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC | | 107.2.1, 107.3.5 | | | | 2. VALUE LOW FOR AMOUNT OF WORK SHOWN, PROVIDE ACCURATE | | VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL. | | INFORMATIONAL NOTE. FIRE ALARM DESIGNS $5000 AND OVER | | MUST BE DESIGNED AND SIGNED/SEALED BY A DESIGN | | PROFESSIONAL. FBC 105.3.1.2 #4 | | | | 3. PASS FIRE REVIEW | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-03-13 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-03-13 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-03-13 |
Time |
11:54 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-03-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-03-04 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-03-04 |
Time |
11:41 |
Sent To |
E |
|
Notes |
2020-03-04 11:45:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM | | SYSTEM. | | | | PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION PER THE | | FLORIDA FIRE PREVENTION CODE. | | | | | | | | 2) THE DOES NOT APPEAR TO BE SUFFICINET OCCUPANT | | NOTIFICATION IN ALL THE ROOMS. | | | | PER # 1 ABOVE , PLEASE REVIEW CODE COMPLIANT | | NOTIFICATION IN ALL APPLICABLE AREAS OR JUSTIFY WITH A | | SPECIFIC DETAILS IN A WRITTEN NARRATIVE. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-04-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-24 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-04-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-16 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-23 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-11 |
Time |
13:17 |
Sent To |
|
|
Notes |
2020-03-23 08:18:34 | PLANS TAKEN TO PERMIT LIBRARY | 2020-03-19 11:35:30 | 3/191 GIVEN TO RMCPHERSON | 2020-03-16 18:19:40 | ROUTED TO ELECTRICAL INBOX | 2020-03-12 13:18:05 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-11 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-11 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-02-20 |
Time |
13:22 |
Sent To |
|
|
Notes |
2020-03-11 13:13:18 | PLANS TAKEN TO PERMIT LIBRARY | 2020-03-05 07:32:07 | ROUTED TO MECHANICAL INBOX | 2020-02-21 13:22:40 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2020-03-10 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-03-10 |
Time |
09:46 |
Rev Time |
|
Received By |
medwards |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2020-03-10 09:47:10 | NO DUCT DETECTORS SHOWN IN THIS SYSTEM. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2020-05-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-05-02 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-05-02 |
Time |
11:04 |
Sent To |
|
|
Notes |
2020-05-02 11:04:27 | PLANS PREPARED BY CONTRACTOR |
|
|