Plan Review Details - Permit 20020796
Plan Review Stops For Permit 20020796
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-04 Cont ID  
Sent By rmcphers Date 2020-03-04 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2020-03-04 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-25 Cont ID  
Sent By rmcphers Date 2020-02-25 Time 09:37 Rev Time 0.00
Received By rmcphers Date 2020-02-25 Time 09:37 Sent To  
Notes
2020-02-25 09:50:35DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN
 PRESSURES FROM AN ENGINEER OR ARCHITECT PER FBC
 1609.1.1 (ENGINEERING SUPPLIED NEEDS TO BE THE ORIGINAL
 SIGNED AND SEALED DOCUMENT).
 2) PLEASE PROVIDE A DRAWING/FLOOR PLAN SHOWING THE
 LOCATION OF THE UNIT IN THE BUILDING. (REQUIRED TO
 DETERMINE THE WIND ZONE 4 OR 5).