Plan Review Stops For Permit 20020777 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2020-03-06 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-06 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-06 |
Time |
10:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2020-03-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-05 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-05 |
Time |
17:09 |
Sent To |
|
|
Notes |
2020-03-05 17:11:05 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | ASBESTOS REVIEW DENIED: | | | | ASBESTOS REQUIREMENTS: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-02-21 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-21 |
Time |
05:58 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-21 |
Time |
05:58 |
Sent To |
|
|
Notes |
2020-02-21 05:59:11 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | ASBESTOS REQUIREMENTS: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-03-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-05 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-05 |
Time |
17:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-02-21 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-21 |
Time |
06:00 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-21 |
Time |
05:59 |
Sent To |
|
|
Notes |
2020-02-21 06:05:39 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.1/107.2.1: | | | | 1) PLEASE PROVIDE A PLAN SHOWING THE INTERIOR WALLS | | THAT WILL BE REMOVED AND INDICATE ALL BEARING, | | NON-BEARING, AND FIRE RATED WALLS. PLEASE PROVIDE | | DETAILS OF ANY TEMPORARY SHORING OF BEARING MEMBERS IF | | REQUIRED. | | | | 2) PLEASE PROVIDE THE CONTRACTOR'S LICENSE NUMBER THAT | | WILL BE CONTRACTED FOR THE DEMOLITION OF INTERIOR | | WALLS. | | | | NOTE: IF FIRE SPRINKLER WORK IS ANTICIPATED, PLEASE | | APPLY FOR A SEPERATE FIRE SPRINKLER PERMIT. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-03-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-03-11 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-03-11 |
Time |
10:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-02-24 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-02-24 |
Time |
12:46 |
Sent To |
|
|
Notes |
2020-02-24 12:51:00 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) SUBMIT PLANS FOR DEMO | | | | 2) ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | PERMIT APPLICATION TO [email protected] AND CC | | [email protected] AND [email protected] SO WE RECEIVE IT | | ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS | | WILL APPROVE THE PLAN REVIEW. | | THE ORIGINAL PERMIT APPLICATION MUST BE SUBMITTED WHEN | | THE PERMIT IS PICKED UP | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-03-11 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-03-11 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-03-11 |
Time |
11:47 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-02-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-02-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-02-26 |
Time |
09:17 |
Sent To |
|
|
Notes |
2020-02-26 09:21:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) A DETAILED LIFE SAFETY REVIEW COULD NOT BE CONDUCTED | | ON THE APPLICATION DUE TO NO PLANS BEING SUBMITTED. | | | | PER NFPA 1 | | | | 1.14 PLAN REVIEW. | | | | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, | | MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS | | AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND | | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN | | SECTION 1.14. | | | | 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE | | THAT THE FOLLOWING CONDITIONS ARE MET: | | (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE | | PROTECTION REQUIREMENTS. | | (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE | | WITH THE APPLICABLE CODES AND STANDARDS. | | (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF | | CONSTRUCTION DOCUMENTS ON SITE. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-11 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-03-11 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-03-11 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-26 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-02-26 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-02-19 |
Time |
13:28 |
Sent To |
|
|
Notes |
2020-02-20 13:28:59 | ROUTED TO PVALENTI |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-02-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2020-02-24 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2020-02-24 |
Time |
13:15 |
Sent To |
|
|
Notes |
2020-03-11 11:31:33 | CONTRACTOR TO ASSURE PLUMBING IS IN SAFE CONDITION AND | | EVALUATE NEED FOR INVOLVING A PLUMBER. SPACE WILL BE | | REMODELED IN THE FUTURE. | 2020-02-24 13:16:57 | NO PLUMBING WORK SHOWN. |
|
|