Plan Review Details - Permit 20020777
Plan Review Stops For Permit 20020777
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-06 Cont ID  
Sent By pvalenti Date 2020-03-06 Time 10:27 Rev Time 0.00
Received By pvalenti Date 2020-03-06 Time 10:27 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-03-05 Cont ID  
Sent By pvalenti Date 2020-03-05 Time 17:09 Rev Time 0.00
Received By pvalenti Date 2020-03-05 Time 17:09 Sent To  
Notes
2020-03-05 17:11:05***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REVIEW DENIED:
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By pvalenti Date 2020-02-21 Time 05:58 Rev Time 0.00
Received By pvalenti Date 2020-02-21 Time 05:58 Sent To  
Notes
2020-02-21 05:59:11***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-05 Cont ID  
Sent By pvalenti Date 2020-03-05 Time 17:09 Rev Time 0.00
Received By pvalenti Date 2020-03-05 Time 17:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By pvalenti Date 2020-02-21 Time 06:00 Rev Time 0.00
Received By pvalenti Date 2020-02-21 Time 05:59 Sent To  
Notes
2020-02-21 06:05:39***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.1/107.2.1:
  
 1) PLEASE PROVIDE A PLAN SHOWING THE INTERIOR WALLS
 THAT WILL BE REMOVED AND INDICATE ALL BEARING,
 NON-BEARING, AND FIRE RATED WALLS. PLEASE PROVIDE
 DETAILS OF ANY TEMPORARY SHORING OF BEARING MEMBERS IF
 REQUIRED.
  
 2) PLEASE PROVIDE THE CONTRACTOR'S LICENSE NUMBER THAT
 WILL BE CONTRACTED FOR THE DEMOLITION OF INTERIOR
 WALLS.
  
 NOTE: IF FIRE SPRINKLER WORK IS ANTICIPATED, PLEASE
 APPLY FOR A SEPERATE FIRE SPRINKLER PERMIT.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By jleahy Date 2020-03-11 Time 10:51 Rev Time 0.00
Received By jleahy Date 2020-03-11 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By jleahy Date 2020-02-24 Time 12:46 Rev Time 0.00
Received By jleahy Date 2020-02-24 Time 12:46 Sent To  
Notes
2020-02-24 12:51:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SUBMIT PLANS FOR DEMO
  
 2) ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] AND [email protected] SO WE RECEIVE IT
 ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS
 WILL APPROVE THE PLAN REVIEW.
 THE ORIGINAL PERMIT APPLICATION MUST BE SUBMITTED WHEN
 THE PERMIT IS PICKED UP
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By pleduc Date 2020-03-11 Time 11:47 Rev Time 0.00
Received By pleduc Date 2020-03-11 Time 11:47 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-02-26 Cont ID  
Sent By pleduc Date 2020-02-26 Time   Rev Time 0.00
Received By pleduc Date 2020-02-26 Time 09:17 Sent To  
Notes
2020-02-26 09:21:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) A DETAILED LIFE SAFETY REVIEW COULD NOT BE CONDUCTED
 ON THE APPLICATION DUE TO NO PLANS BEING SUBMITTED.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND
 APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION DOCUMENTS ON SITE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-11 Cont ID  
Sent By lmarchan Date 2020-03-11 Time 15:37 Rev Time 0.00
Received By lmarchan Date 2020-03-11 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-26 Cont ID  
Sent By lmarchan Date 2020-02-26 Time 16:23 Rev Time 0.00
Received By lmarchan Date 2020-02-19 Time 13:28 Sent To  
Notes
2020-02-20 13:28:59ROUTED TO PVALENTI

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-02-24 Cont ID  
Sent By skennedy Date 2020-02-24 Time 13:15 Rev Time 0.00
Received By skennedy Date 2020-02-24 Time 13:15 Sent To  
Notes
2020-03-11 11:31:33CONTRACTOR TO ASSURE PLUMBING IS IN SAFE CONDITION AND
 EVALUATE NEED FOR INVOLVING A PLUMBER. SPACE WILL BE
 REMODELED IN THE FUTURE.
2020-02-24 13:16:57NO PLUMBING WORK SHOWN.