Plan Review Details - Permit 20020745
Plan Review Stops For Permit 20020745
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-03-05 Cont ID  
Sent By cpuell Date 2020-03-05 Time 14:21 Rev Time 0.00
Received By cpuell Date 2020-03-05 Time 14:21 Sent To  
Notes
2020-03-05 14:22:33ADDRESS SHOULD BE 347 SUMMA ST, CHANGED ADDRESS IN
 COMMUNITY PLUS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-14 Cont ID  
Sent By rmcphers Date 2020-05-14 Time 15:36 Rev Time 0.00
Received By rmcphers Date 2020-05-14 Time 15:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By rmcphers Date 2020-04-13 Time 16:55 Rev Time 0.00
Received By rmcphers Date 2020-04-13 Time 11:18 Sent To  
Notes
2020-04-13 16:41:07NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SURVEY NEEDS TO BE ELECTRONICALLY SIGNED BY THE
 SURVEYOR. (DOES NOT SHOW IN "ADOBE" AS ELECTRONICALLY
 SIGNED.
 2) PLEASE SHOW THE FLOOD ZONE PER THE LATEST FIRM.
 3) ELECTRONIC SIGNATURE ON THE STRUCTURAL DRAWINGS
 NEEDS TO BE VERIFIED BY A CERTIFICATION AUTHORITY - SEE
 61G15-23.004(2).
 4) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
 5) PLEASE SHOW THE REQUIRED HANDRAILING AT THE STAIRS (
 HEIGHT, EXTENSIONS AND ONE ON EACH SIDE) TO COMPLY WITH
 FBC 1014.
 6) PLEASE SHOW TERMITE TREATMENT REQUIRED TO COMPLY
 WITH FBC 1816.
 7) PLEASE PROVIDE SIDING ATTACHMENT DETAILS OR PRODUCT
 APPROVALS.
 8) PLEASE PROVIDE SOLAR PANEL ATTACHMENT DETAILS OR
 PRODUCT APPROVALS.
 9) PLEASE SHOW THE REQUIRED NAILING FOR THE STRAPPING
 (SIZE OF NAIL OR SCREW AND AMOUNT).
 10) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE METAL
 ROOFING.
 11) ANY DEFERRALS PLEASE PUT IN WRITING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By dbattles Date 2020-03-13 Time 17:01 Rev Time 0.00
Received By dbattles Date 2020-03-11 Time 09:21 Sent To  
Notes
2020-03-13 17:01:40BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20020745
 REVIEWED: MARCH 13, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1004 FBC[B]SHEET G-101 (MAIN BUILDING)
 PLEASE BASE OCCUPANCY UPON THE INTENDED USE. 15 SQ. FT.
 PER OCCUPANT IS FOR TABLES AND CHAIRS. THE PLAN IS
 SHOWN WITH CHAIRS ONLY AND THERE ARE 85 CHAIRS
 REPRESENTED. CONCENTATED CHAIRS USES 7 SQ. FT. PER
 OCCUPANT. SINCE THIS SPACE WILL BE USED FOR A VARIETY
 OF ASSEMBLY AND YOU ARE DEVIATING FROM CODE WORST CASE,
 PLEASE CONTACT THE FIRE MARSHALL AND BUILDING OFFICIAL
 TO DISCUSS.
 [email protected] (FIRE MARSHALL) AND [email protected]
 (BUILDING OFFICIAL)
 SHOW CLEAR PATH OF EGRESS OR SHOW DIMENSION BETWEEN
 CHAIRS AND WALL SINCE IT APPEARS LESS THAN 36 INCHES.
  
 2) 1004 FBC[B]ADJUST THE TAG MAIN INTERIO ASSEMBLY. IT
 SHOWS B AND USES 15 FOR COME UP WITH 59 OCCUPANTS.
 PLEASE UPDATE TO A-3 AND USE OCCUPANT FACTOR BASED ON
 USE OF THE SPACE.
  
 3) 1004 FBC[B] SHEET G-10 (RESTROOM FACILITY)
 LOCKER ROOMS ARE USING BUSINESS OCCUPANCY AT 100 SQ.
 FT. PER, BUT THERE IS A 50 GROSS FOR LOCKER ROOMS
 STATED IN TABLE 1004.1.2
 ALSO, BUSINESS IS USED FOR MAIN RESTROOM AREA. THESE
 DON?T SUPPORT BUSINESS USES. PLEASE USE OCCUPANCY COUNT
 AT LEAST MINIMUM OF FIXTURES SINCE THEY COULD BE USED
 SIMULTANEOUSLY.
  
 4) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 - PLEASE PROVIDE DOCUMENTATION FOR COMPLIANCE WITH THE
 ENERGY CODE FOR EACH BUILDING.
  
 5) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL AND TRANSOM, OR INDICATE THAT THIS
 WILL BE A DEFERRED SUBMITTAL.
  
 6) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD
 RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED
 SUBMITTAL.
  
 7) 1507.4.2 FBC[B] DECK SLOPE. MINIMUM SLOPES FOR METAL
 ROOF PANELS SHALL COMPLY WITH THE FOLLOWING:
 A. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITHOUT APPLIED LAP SEALANT SHALL BE THREE
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT
 SLOPE).
 B. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITH APPLIED LAP SEALANT SHALL BE ONE-HALF
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE).
 LAP SEALANTS SHALL BE APPLIED IN ACCORDANCE WITH THE
 APPROVED MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 B. THE MINIMUM SLOPE FOR STANDING-SEAM METAL ROOF PANEL
 SYSTEMS SHALL BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).
 -PLEASE PROVIDE PRODUCT APPROVALS FOE METAL ROOFING
 THAT MEET 1507.4.2, OR INDICATE THAT THIS WILL BE A
 DEFERRED SUBMITTAL.
  
 8) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 9) 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 10) 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE
 FOR BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 NOTES:
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-15 Cont ID  
Sent By jpearson Date 2020-05-15 Time 14:44 Rev Time 0.00
Received By jpearson Date 2020-05-15 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By jpearson Date 2020-04-10 Time 15:31 Rev Time 0.00
Received By jpearson Date 2020-04-10 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By jleahy Date 2020-03-17 Time 12:55 Rev Time 0.00
Received By jleahy Date 2020-03-11 Time 10:34 Sent To  
Notes
2020-03-17 12:59:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SUBMIT AN AIC CALCULATION FOR THE SERVICE
 110.24
  
 2) OUTLET(S) FOR WATER FOUNTAIN TO BE ACCESSIBLE IF
 THEY ARE OF THE GCFI TYPE. 422.52, 422.5
  
 3) NEED A LOAD CALCULATION PER 220, 215.5
  
 4) LOW VOLTAGE, SITE LIGHTING, FIRE ALARM, AND SOLAR
 SYSTEMS ALL REQUIRE SEPARATE PERMITS.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2020-05-13 Cont ID  
Sent By Mgonzale Date 2020-05-13 Time   Rev Time 1.00
Received By mgonzale Date 2020-05-13 Time   Sent To I
Notes
2020-05-13 12:22:57REVIEWED UNDER ENGINEERING PROJECT.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2020-04-20 Cont ID  
Sent By rrossano Date 2020-04-20 Time   Rev Time 0.00
Received By rrossano Date 2020-04-20 Time   Sent To I
Notes
2020-04-20 14:19:24FORMAL ENGINEERING SUBMITTAL CURRENTLY UNDER REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By rrossano Date 2020-03-16 Time   Rev Time  
Received By rrossano Date 2020-03-16 Time   Sent To  
Notes
2020-03-16 14:33:50PLEASE SUBMIT FOR SITE PLAN AND FORMAL ENGINEERING
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-05-11 Cont ID  
Sent By pleduc Date 2020-05-11 Time   Rev Time 0.00
Received By pleduc Date 2020-05-08 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By pleduc Date 2020-04-10 Time   Rev Time 0.00
Received By pleduc Date 2020-04-10 Time 09:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-06 Cont ID  
Sent By pleduc Date 2020-03-06 Time   Rev Time 0.00
Received By pleduc Date 2020-03-06 Time 11:44 Sent To  
Notes
2020-03-06 11:57:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET G 101 - THE OCCUPANCY LOAD CALCULATION FOR THE
 CONFERENECE ROOM IS INDICATED AS B 100/3. THIS
 CONFERENCE ROOM IS AN ASSEMBLY SPACE PER THE FL FIRE
 PREVENTION CODE.
  
 THE OCCUPANCY LOAD SHOULD BE 20, WITH AN A REPLACE THE
 B DESIGNATION.
  
 PLEASE REVIEW AND REVISE AT THE APPLICABLE TIME PRIOR
 TO CO
  
  
  
 2) SHEET G 101 - THE OCCUPANCY LOAD CALCULATION FOR THE
 LARGE OPEN CONFERENECE SPACE IS INDICATED A B WHERE IT
 SHOULD BE A.
  
 PLEASE REVIEW AND REVISE AT THE APPLICABLE TIME PRIOR
 TO CO
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-04 Cont ID  
Sent By lmarchan Date 2020-06-04 Time 09:43 Rev Time 0.00
Received By lmarchan Date 2020-05-27 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-22 Cont ID  
Sent By shill Date 2020-05-15 Time 15:37 Rev Time 0.00
Received By shill Date 2020-05-07 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-22 Cont ID  
Sent By shill Date 2020-04-22 Time 15:04 Rev Time 0.00
Received By shill Date 2020-04-09 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-17 Cont ID  
Sent By jleahy Date 2020-03-17 Time 12:59 Rev Time 0.00
Received By jleahy Date 2020-02-26 Time 11:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-05-27 Cont ID  
Sent By lmarchan Date 2020-05-27 Time 11:31 Rev Time 0.00
Received By lmarchan Date 2020-05-15 Time 08:20 Sent To  
Notes
2020-05-27 11:31:38NO FEES DUE PER IMPACT FEE OFFICE. LEM
2020-05-15 08:20:485/15/20 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By dbattles Date 2020-03-11 Time 13:15 Rev Time 0.00
Received By dbattles Date 2020-03-11 Time 13:15 Sent To  
Notes
2020-03-11 13:16:02109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-06-02 Cont ID  
Sent By pvalenti Date 2020-06-01 Time 16:34 Rev Time 0.00
Received By pvalenti Date 2020-06-01 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-05-15 Cont ID  
Sent By hmoser Date 2020-05-15 Time 13:57 Rev Time 0.00
Received By hmoser Date 2020-05-15 Time 13:57 Sent To  
Notes
2020-05-15 14:40:44PLAN DENIED
 REFER TO SECTION C403.2.1 FLORIDA ENERGY CODE 2017
 CALCULATION OF HEATING AND COOLING LOADS REQUIRED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-05-08 Cont ID  
Sent By ccole Date 2020-05-08 Time 14:55 Rev Time 0.00
Received By ccole Date 2020-05-08 Time 08:02 Sent To  
Notes
2020-05-08 14:56:013RD REVIEW FBC-2017 MECHANICAL
 PERMIT #20020745
 5/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I WAS NOT ABLE TO LOCATE THE PREVIOUSLY SUBMITTED AC
 CALCULATIONS. PLEASE RE-SUBMIT THE CALCULATIONS OR
 PROVIDE NEW CALCULATIONS FOR THE SYSTEMS- SECTION
 C403.2.1 FBC EC.
  
 PLEASE UPDATE AND UPLOAD CORRECTED PLAN SHEETS TO
 ADDRESS THE COMMENTS FROM THE 1ST REVIEW LISTED BELOW.
  
 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE
 ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC
 EC. THE UNITS WILL HAVE TO BE RELOCATED.
 SHEET M101: THE ARCHITECT'S RESPONSE THAT THE SPACE
 ABOVE THE CEILING IS NOT AN ATTIC BY DEFINITION IS
 ACCEPTED, HOWEVER THE ENGINEER OF RECORD HAS NOT
 REMOVED OR CORRECTED KEY NOTES #8, 9, 11, & 12 WHICH
 IDENTIFY THE SPACE AS AN ATTIC.
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A
 SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
 THE VENTILATION CALCULATIONS ON SHEET M-101 CAN NOT BE
 CHECKED FOR COMPLIANCE WITH TABLE 403.3.1.1 FBC M
 BECAUSE THEY DO NOT INDICATE THE REQUIRED CFMS PER
 PERSON AND CFMS PER SQ. FT. OF THE ROOMS OR SPACES.
 PLEASE PROVIDE A COMPLETE CALCULATION TABLE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-10 Cont ID  
Sent By ccole Date 2020-04-10 Time 16:47 Rev Time 0.00
Received By ccole Date 2020-04-10 Time 14:02 Sent To  
Notes
2020-04-10 16:48:302ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020745
 4/10/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST
 EITHER PARTIALLY OR ENTIRELY.
  
 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE
 ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC
 EC. THE UNITS WILL HAVE TO BE RELOCATED.
 SHEET M101: THE ARCHITECT'S RESPONSE THAT THE SPACE
 ABOVE THE CEILING IS NOT AN ATTIC BY DEFINITION IS
 ACCEPTED, HOWEVER THE ENGINEER OF RECORD HAS NOT
 REMOVED OR CORRECTED KEY NOTES #8, 9, 11, & 12 WHICH
 IDENTIFY THE SPACE AS AN ATTIC.
  
 3) M-101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEM OF AHU-2 PER SECTION 606.2.1 FBC M. PLEASE NOTE
 THAT AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S
 PERFORMANCE DATA INDICATES THE AIR HANDLER IS NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
 PLEASE SEE PAGE 6 OF THE SUBMITTED PRODUCT DATA FOR THE
 CARRIER FAN COIL UNITS. THERE IS A NOTE BELOW THE
 PERFORMANCE DATA CHART INDICATING AIR FLOW CAN BE
 ADJUSTED +15% OR -10%. THEREFORE AHU-2 (060 IN THE
 TABLE) IS CAPABLE OF PRODUCING 2012 CFMS WHICH REQUIRES
 INSTALLATION OF A DS DETECTOR.
  
 4) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS- SECTION C403.2.2 FBC EC.
 THE AC CALCULATIONS INDICATE THE COOLING COIL AT 3.5
 TONS FOR THE GREAT ROOM HP/AHU-2 SYSTEM, HOWEVER THE
 SYSTEM SELECTED IS A 5-TON AS SHOWN ON SHEET M-601. THE
 UNIT APPEARS TO BE OVERSIZED- SECTION C403.2.1 FBC EC.
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A
 SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
 THE VENTILATION CALCULATIONS ON SHEET M-101 CAN NOT BE
 CHECKED FOR COMPLIANCE WITH TABLE 403.3.1.1 FBC M
 BECAUSE THEY DO NOT INDICATE THE REQUIRED CFMS PER
 PERSON AND CFMS PER SQ. FT. OF THE ROOMS OR SPACES.
 PLEASE PROVIDE A COMPLETE CALCULATION TABLE.
  
 8) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSERS- SECTION
 301.15 FBC M.
 MOUNTING PAD DETAILS HAVE BEEN PROVIDED BUT NO DETAILS
 FOR ANCHORING THE HEAT PUMPS TO THE SLABS. PLEASE NOTE
 THAT THE ENGINEERING MAY BE DEFERRED BY REQUEST-
 SECTION 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By ccole Date 2020-03-11 Time 15:04 Rev Time 0.00
Received By ccole Date 2020-03-11 Time 12:56 Sent To  
Notes
2020-03-11 15:35:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020745
 3/11/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE
 ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC
 EC. THE UNITS WILL HAVE TO BE RELOCATED.
  
 2 )M-101: PLEASE NOTE THAT AUTOMATIC SHUTOFF DAMPERS,
 EITHER MOTORIZED OR GRAVITY, WILL BE REQUIRED FOR THE
 O/A INTAKES TO THE RELOCATED AIR HANDLERS- SECTION
 C403.2.4.3 FBC EC.
  
 3) M-101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEM OF AHU-2 PER SECTION 606.2.1 FBC M. PLEASE NOTE
 THAT AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S
 PERFORMANCE DATA INDICATES THE AIR HANDLER IS NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 4) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS- SECTION C403.2.1 FBC EC.
  
 5) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW
 TENNIS CENTER- SEE SECTIONS C101.5 AND C401.2 FBC EC
 FOR COMPLIANCE AND SUBMITTAL INFORMATION.
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A
 SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2.1
 FBC M.
  
 8) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSERS- SECTION
 301.15 FBC M.
  
 9) A-152 & A-203: A) A MINIMUM 30 INCHES DEEP AND 30
 INCHES WIDE LEVEL PLATFORM WITH 42" HIGH GUARD RAILS
 SHALL BE PROVIDED FOR SERVICE AND REPLACEMENT OF THE
 ROOFTOP EXHAUST FANS- SECTION 306.5.1 FBC M. B) A
 RECEPTACLE OUTLET SAHLL BE POVIDED AT OR NEAR THE FANS
 IN ACCORDANCE WITH NFPA 70- SECTION 306.5.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-05-14 Cont ID  
Sent By rmcdouga Date 2020-05-14 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-05-14 Time 15:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-14 Cont ID  
Sent By tklarge Date 2020-04-14 Time 11:05 Rev Time 0.00
Received By tklarge Date 2020-04-14 Time 05:45 Sent To  
Notes
2020-04-14 10:57:421) SHT. A-411 & SHT. A-102 - DETAIL #1 - SHOW THE CLEAR
 FLOOR SPACE FOR THE HANDICAP ACCESSIBLE WATER CLOSETS
 ON THE ENLARGED FLOOR PLANS. COMPLY WITH 2017
 FBC-ACCESS. SEC. 604.3. SHOW THE LENGTH AND WIDTH
 DIMENSIONS OF THE CLEAR FLOOR SPACE ON THE PLANS.THE
 ONLY CLEAR FLOOR SPACE SHOWN IS FOR THE LAVATORY. 2ND
 REQUEST.
 2) SHT. A-102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116
 - A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET
 STALLS PER 2017 FBC-ACCESS.SEC. 604.8.1.6. 2ND REQUEST.
 3) SHT. A-102 - MEN'S & WOMEN'S RESTROOMS #115 & #116 -
 THE DOORSIN THE HANDICAP ACCESSIBLE TOILET STALLS SHALL
 BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL
 OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT
 LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.2017 FBC-
 ACCESS. SEC.604.8.1.2. 2ND REQUEST.
 4) THE WATER COOLER LOCATED ON THE EAST WALL OF THE
 RESTROOM FACILITY SHALL BE A HI-LO UNIT OR 2 SEPARATE
 UNITS COMPLYING WITH THE FBC-ACCESS. SEC. 211.1 &
 FBC-PLUMBING SEC.410.3. THIS WAS OVERLOOKED ON THE
 PREVIOUS REVIEW.
 5) SHT. A-401 - VERTICAL GRAB BARS ARE SHOWN IN THE
 ACCESSIBILITY DETAILS. SEC. 609.4 OF THE FBC-ACCESS.
 STATES THAT GRAB BARS SHALL BE INSTALLED IN THE
 HORIZONTAL POSITION.THERE IS NO EXCEPTION IN THE
 ACCESSIBILITY CODE ALLOWING GRAB BARS TO BE INSTALLED
 IN A VERTICAL POSITION EVEN THOUGH THEY ARE NOT
 "REQUIRED" GRAB BARS.
 6) SHT. P-601 - WATER HEATER SCHEDULE - IN THE "NOTES"
 COLUMN REFERENCE IS MADE TO NUMBERED NOTES BUT THERE
 ARE NO NUMBERED NOTES SHOWN. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By tklarge Date 2020-03-13 Time 14:05 Rev Time 0.00
Received By tklarge Date 2020-03-13 Time 12:06 Sent To  
Notes
2020-03-13 12:29:471) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) FOR THE
 ACCESSIBLE TOILET STALLS AND TOILET ROOMS ON THE
 ENLARGED FLOOR PLANS. , WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE CLEAR FLOOR SPACE FOR THE HANDICAP
 ACCESSIBLE WATER CLOSETS ON THE ENLARGED FLOOR PLANS.
 COMPLY WITH 2017 FBC-ACCESS. SEC. 604.3. SHOW THE
 LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE ON
 THE PLANS.
 3) SHT.A102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 -
 A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET STALL
 PER 2017 FBC-ACCESS. SEC.604.8.1.6. SHOW THIS ON ALL
 APPLICABLE PLANS.
 4) SHT. A101 - THE TOILET ROOMS IN THE TENNIS CENTER
 ARE LABELED AS UNISEX.THE TOILET ROOMS SHALL BE LABELED
 AS GENDER SPECIFIC PER 2017 FBC-PLUMBING SEC.403.2.
 5) SHT. A401 - ALL GRAB BARS SHALL BE MEASURED FROM THE
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER
 2017 FBC-ACCESS. SEC.609.4.
 6) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF ALL THE
 SHOWERS. WPB AMEND. TO FBC . SEC.107.2.1.
 7) SUBMIT AN ENLARGED FLOOR FLOOR PLAN FOR THE MEN'S
 TOILET ROOM IN THE RESTROOM FACILITY.WPB AMEND. TO FBC
 SEC. 107.2.1.
 8) A BACKFLOW PREVENTION DEVCE IS REQUIRED ON THE WATER
 SERVICE FOR THE TENNIS CENTER AND THE RESTROOM FACILITY
 PER THE CITY OF WEST PALM BEACH CROSS CONNECTION
 CONTROL MANUAL.. A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW DEVICES.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND SHOP
 DRAWINGS FOR THE RAINWATER COLLECTION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) NONPOTABLE WATER SYSTEMS SHALL BE IDENTIFIED IN
 ACCORDANCE WITH 2017 FBC-PLUMBING SECS.608.8 -
 608.8.2.3.
 11) SHT. P104 - DETAIL # 1- RESTROOM FACILITY - THE 3/4
 INCH CW LINES HAS A NOTE THAT READS" SEE 1/P101 FOR
 CONTINUATION". SHT. P101 IS FOR THE TENNIS CENTER AND
 THE LINE IS NOT SHOWN. CLARIFY.
 12) SHT. P104 - DETAIL #1 - THE WATER RISER SHOWS A 2
 INCH NPW BY FIXTURES P3, P7 & IM LINE TO NOWHERE.
 CLARIFY.
 13) SHT.P104 - THERE IS AN NPW LINE BY THE 1 1/2 NPW
 LINE TO P1A THAT HAS NO SIZE AND GOES NOWHERE. CLARIFY.
 14) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE FILTRATION SKID. WPB AMEND.
 TO FBC SEC. 107.2.1.
 15) BACK TO BACK WATER CLOSET CONNECTIONS SHALL COMPLY
 WITH 2017 FBC-PLUMBING SEC. 706.3 (EXCEPTION). SHOW
 COMPLIANCE ON PLANS.
 16) SHT. P105 - DETAIL #1 SHOWS SANITARY TEES USED IN
 THE HORIZONTAL POSITION WHICH IS NOT PERMITTED PER 2017
 FBC-PLUMBING TABLE 706.3. ALSO, THE PIPING TO FIXTURE
 P3 IS S- TRAPPED.
 17) SHT. P501 - THE T & P LINE FOR THE WATER HEATER
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER. 2017 FBC-PLUMBING SEC.504.6.
 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 WATTS ES-LSMMV-M1. DEVICES USED FOR TEMPERING WATER
 SHALL CONFORM TO ASSE 1070 PER 2017 FBC-PLUMBING SEC.
 607.1.2.
 19) AS OF APRIL 16, 2015 THE MINIMUM ENERGY FACTOR FOR
 THE 10 GALLON STORAGE WATER HEATER IS .95 PER 10 CFR
 430.32. THE ENERGY FACTOR FOR THE 66 GALLON STORAGE
 WATER HEATER SHALL BE 1.98. SHOW THESE CHANGES ON THE
 ENERGY CALCULATIONS.
 20) THE GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL BE
 INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS. 2017
 FBC-ACCESS. SEC.608.3.2.
 21)THE CONTROLS IN THE ACCESSIBLE SHOWERS SHALL BE
 LOCATED 27 INCHES MAXIMUM FROM THE SEAT WALL. SHOW THIS
 ON THE FLOOR PLANS. 2017 FBC-ACCESS. SEC. 608.5.2.
 22) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET STALLS
 SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE
 WALL OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT
 LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.. 2017
 FBC_ ACCESS. SEC.604.8.1.2.
 23) SHT. P104 - DETAIL #1 - THE 3/4 INCH NPW LINE IS
 ALSO NOTED AS "CW". CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2020-05-14 Cont ID  
Sent By rmcphers Date 2020-05-14 Time 15:36 Rev Time 0.00
Received By rmcphers Date 2020-05-14 Time 15:36 Sent To  
Notes
2020-05-14 15:38:55DEFERRED SUBMITTAL

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By rmcphers Date 2020-04-13 Time 16:54 Rev Time 0.00
Received By rmcphers Date 2020-04-13 Time 16:54 Sent To  
Notes
2020-04-13 16:54:56SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By dbattles Date 2020-03-13 Time 17:01 Rev Time 0.00
Received By dbattles Date 2020-03-11 Time 13:16 Sent To  
Notes
2020-03-13 17:02:30SEE BUILDING COMMENT #7

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-16 Cont ID  
Sent By shill Date 2020-05-16 Time 13:09 Rev Time 0.00
Received By shill Date 2020-05-16 Time 13:09 Sent To  
Notes
2020-05-16 13:09:37NOTIFIED ENGINEER THAT FUTURE SUBMITTALS WILL BE
 REQUIRED TO HAVE 3RD PARTY SIGNATURE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-14 Cont ID  
Sent By rmcdouga Date 2020-05-14 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2020-05-14 Time 16:50 Sent To  
Notes
2020-05-14 16:52:47ALL MECHANICAL, ELECTRICAL, AND PLUMBING SHEETS HAVE
 BEEN SELF-CERTIFIED BY THE ENGINEER OF RECORD. PER THE
 WPB AMENDMENTS TO THE FBC, FLORIDA ADMINISTRATIVE CODE
 RULE 61G15-23, EACH SHEET OF PLAN IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION.
 SELF-CERTIFICATION IS NOT ACCEPTABLE FOR ENGINEERS.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
 PREVIOUS COMMENTS NOT CORRECTED:
 ALL A SHEETS OK.
 ALL SHEETS DIGITALLY SIGNED BY ENGINEER NEED TO FOLLOW
 RULES ESTABLISHED BY THE BOARD OF ENGINEERS (SEE
 BELOW).
  
 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS
 DIGITALLY SIGN WITH A DIGITAL SIGNATURE ISSUED TO YOU
 BY A 3RD PARTY CERTIFICATION AUTHORITY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-10 Cont ID  
Sent By jpearson Date 2020-04-10 Time 14:57 Rev Time 0.00
Received By jpearson Date 2020-04-10 Time 14:57 Sent To  
Notes
2020-04-10 14:54:50ALL MECHANICAL, ELECTRICAL, AND PLUMBING SHEETS HAVE
 BEEN SELF-CERTIFIED BY THE ENGINEER OF RECORD. PER THE
 WPB AMENDMENTS TO THE FBC, FLORIDA ADMINISTRATIVE CODE
 RULE 61G15-23, EACH SHEET OF PLAN IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION.
 SELF-CERTIFICATION IS NOT ACCEPTABLE FOR ENGINEERS.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
 PREVIOUS COMMENTS NOT CORRECTED:
 ALL A SHEETS OK.
 ALL SHEETS DIGITALLY SIGNED BY ENGINEER NEED TO FOLLOW
 RULES ESTABLISHED BY THE BOARD OF ENGINEERS (SEE
 BELOW).
  
 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS
 DIGITALLY SIGN WITH A DIGITAL SIGNATURE ISSUED TO YOU
 BY A 3RD PARTY CERTIFICATION AUTHORITY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By dbattles Date 2020-03-11 Time 13:12 Rev Time 0.00
Received By dbattles Date 2020-03-11 Time 13:12 Sent To  
Notes
2020-03-11 13:15:23OK A-SHEETS
 ALL SHEETS DIGITALLY SIGNED BY ENGINEER NEED TO FOLLOW
 RULES ESTABLISHED BY THE BOARD OF ENGINEERS (SEE
 BELOW).
  
 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS
 DIGITALLY SIGN WITH A DIGITAL SIGNATURE ISSUED TO YOU
 BY A 3RD PARTY CERTIFICATION AUTHORITY.
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By awooten Date 2020-05-18 Time   Rev Time 0.00
Received By   Date 2020-05-18 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By rfalcone Date 2020-04-15 Time 09:35 Rev Time 0.00
Received By rfalcone Date 2020-04-15 Time 09:35 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-06 Cont ID  
Sent By hdanfort Date 2020-03-06 Time 14:14 Rev Time 0.00
Received By hmtribou Date 2020-03-06 Time 14:14 Sent To  
Notes
***NONE***