Plan Review Details - Permit 20020655
Plan Review Stops For Permit 20020655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-19 Cont ID  
Sent By rmcphers Date 2020-05-19 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2020-05-19 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By rmcphers Date 2020-03-10 Time 13:23 Rev Time 0.00
Received By rmcphers Date 2020-03-09 Time 13:44 Sent To  
Notes
2020-03-10 13:23:31SEE PERMIT NUMBER 20020653

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-07 Cont ID  
Sent By jleahy Date 2020-03-07 Time 12:55 Rev Time 0.00
Received By jleahy Date 2020-03-07 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 17:20 Rev Time 0.00
Received By medwards Date 2020-12-07 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-19 Cont ID  
Sent By ccarvaja Date 2020-06-19 Time 11:07 Rev Time 0.00
Received By ccarvaja Date 2020-06-10 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-19 Cont ID  
Sent By rmcphers Date 2020-05-19 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-21 Cont ID  
Sent By cthroop Date 2020-03-21 Time 07:47 Rev Time 0.00
Received By cthroop Date 2020-02-26 Time 14:38 Sent To  
Notes
2020-02-27 14:38:43PLANS UNDER 20020653

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-02-02 Cont ID  
Sent By lmarchan Date 2021-02-02 Time 15:19 Rev Time 0.00
Received By lmarchan Date 2021-01-08 Time 17:40 Sent To  
Notes
2021-01-08 17:41:0801/08/21 EMAILED IMPACT FEES OFFICE. QUESTIONNAIRE
 UPLOADED UNDER 20020653.CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By rmcphers Date 2020-03-10 Time 13:23 Rev Time 0.00
Received By rmcphers Date 2020-03-10 Time 13:23 Sent To  
Notes
2020-03-10 13:23:57SEE PERMIT NUMBER 20020653

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 17:19 Rev Time 0.00
Received By medwards Date 2020-12-14 Time 17:19 Sent To  
Notes
2020-12-14 17:19:49PLEASE SEE SHEET M1 OF PRIMARY PERMIT #18080996.
 CONDENSATE LINES DO NOT APPEAR TO RUN THROUGH THE
 PROPERTY LINES. ME

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-06-19 Cont ID  
Sent By medwards Date 2020-06-19 Time 07:44 Rev Time 0.00
Received By medwards Date 2020-06-19 Time 07:44 Sent To  
Notes
2020-06-19 07:46:18REVIEWER CANNOT DO THIS REVIEW, NO DRAWINGS WERE
 SUBMITTED WITH THIS CYCLE OF REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-08 Cont ID  
Sent By ccole Date 2020-05-08 Time 13:21 Rev Time 0.00
Received By ccole Date 2020-05-08 Time 13:19 Sent To  
Notes
2020-05-08 13:22:05 
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020655
 5/8/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M4.6: THE REVISED SHEET SHOWS UNDERSLAB
 REFRIGERANT PIPING RUNS CROSSING THE INDIVIDUAL
 PROPERTY LINES OF THE TOWNHOUSES. PLEASE SEE SECTION
 R302.2 FBC RES AND RELOCATE THE CONDENSERS BACK TO
 THEIR ORIGINAL LOCATIONS AT THE REAR OF EACH TOWNHOUSE.
  
 2) THE 421 18TH ST. ADDRESS ON THE AC CALCULATIONS DOES
 NOT MATCH THE ADDRESSES ON THE PERMIT APPLICATION AND
 THE ENERGY CALCS. PLEASE PROVIDE CALCULATIONS
 SPECIFICALLY FOR THE PROPOSED TOWNHOUSE- SECTION
 R403.7.1 FBC EC. REVISE THE SURVEY TO SHOW CORRECT
 TOWNHOUSE AND LOT LOCATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By ccole Date 2020-03-17 Time 12:57 Rev Time 0.00
Received By ccole Date 2020-03-17 Time 12:57 Sent To  
Notes
2020-03-17 12:57:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020655
 3/17/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE PLANS SHOW MULTIPLE MODEL TOWNHOUSES. PLEASE
 PROVIDE A MASTER LIST THAT LINKS TOWN HOUSE MODELS WITH
 ADDRESSES- SECTION 107.2.1 WPB. IT WOULD ALSO BE
 HELPFUL TO A SITE PLAN OF THE TOWNHOUSE DEVELOPMENT
 THAT IDENTIFIES EACH BUILDING LOCATION, THE STREETS AND
 THE ADDRESSES OF THE TOWNHOUSES- SEE ZONING REVIEW.
  
 2) IN ORDER TO REVIEW THE ENERGY AND AC CALCULATIONS,
 PLEASE PROVIDE DOOR AND WINDOW SCHEDULES ON THE PLAN-
 SECTIONS R402 & R403.7.1 FBC EC.
  
 3) SHEET M1, NAVARRE MODEL:
 A) IT APPEARS THAT FLEX DUCTS WILL BE INSTALLED IN THE
 GARAGE. PLEASE PLACE A NOTE TO VERIFY THE DUCTS WILL BE
 INSTALLED ABOVE THE REQUIRED DRYWALL CEILING- SECTION
 R302.5.2 FBC RES
 B) PROVIDE A RETURN FROM THE MASTER BEDROOM WALK-IN
 CLOSET- SECTION M1602.2(3) FBC RES.
 C) THE MAIN RETURN TO THE AC CLOSET IS SLIGHTLY
 UNDERSIZED- 50 SQ. INCHES PER 100 CFMS REQUIRED. A
 24X24 GRILL WILL BE ADEQUATE.
 D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES
 DRYER AND RANGE HOOD- SECTIONS M1502.4.5.2 AND M1503.1
 FBC RES. PLEASE NOTE THAT A LOUVERED DOOR OR GRILL TO
 PROVIDE MAKEUP AIR MAY BE REQUIRED FOR THE CLOTHES
 DRYER- SECTION 1307.1 FBC RES.
  
 4) SHEET M2, GRAYTON MODEL:
 A) PROVIDE A RETURN FROM THE MASTER BEDROOM WALK-IN
 CLOSET- SECTION M1602.2(3) FBC RES.
 B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES
 DRYER AND RANGE HOOD- SECTIONS M1502.4.5.2 AND M1503.1
 FBC RES. PLEASE NOTE THAT A LOUVERED DOOR OR GRILL TO
 PROVIDE MAKEUP AIR MAY BE REQUIRED FOR THE CLOTHES
 DRYER- SECTION 1307.1 FBC RES.
  
 5) THE ENERGYGAUGE PERFORMANCE COMPLIANCE FORM
 R405-2017 SHALL BE ELECTRONICALLY SIGNED AND SEALED BY
 THE ENGINEER WHO PREPARED THE DOCUMENT. PLEASE NOTE
 THAT A BLOWER DOOR TEST WILL BE REQUIRED AND THE TEST
 FORM (ATTACHED WITH THE REPORT) SHALL BE FILLED OUT AND
 SUBMITTED FOR FINAL CO.
  
 6) THE ELITE HVAC COOLING AND HEATING CALCULATIONS
 ATTACHED WITH THE ENERGY FORMS ARE NOT INDICATED TO BE
 "WORST CASE" AND THERE IS NO SECTION IN THE FBC EC THAT
 ALLOWS FOR A WORST CASE HEAT LOAD CALCULATION.
 CALCULATIONS SHALL BE SUBMITTED FOR EACH PERMITTED
 TOWNHOUSE. PLEASE NOTE THAT THE REVISED CALCULATIONS
 SHALL BEAR THE TOWNHOUSE MODEL NAME AND ADDRESS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-21 Cont ID  
Sent By cthroop Date 2020-03-21 Time 07:47 Rev Time 0.00
Received By cthroop Date 2020-03-20 Time 12:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-05-19 Cont ID  
Sent By rmcphers Date 2020-05-19 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2020-05-19 Time 16:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 17:20 Rev Time 0.00
Received By medwards Date 2020-12-14 Time 17:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-06-19 Cont ID  
Sent By medwards Date 2020-06-19 Time 07:46 Rev Time 0.00
Received By medwards Date 2020-06-19 Time 07:46 Sent To  
Notes
2020-06-19 07:47:42NO DRAWINGS WERE SUBMITTED WITH THIS CYCLE OF REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-19 Cont ID  
Sent By rmcphers Date 2020-05-19 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2020-05-19 Time 16:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By rmcphers Date 2020-03-10 Time 13:24 Rev Time 0.00
Received By rmcphers Date 2020-03-10 Time 13:24 Sent To  
Notes
2020-03-10 13:24:22SEE PERMIT NUMBER 20020653

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-11 Cont ID  
Sent By llouie Date 2020-05-11 Time   Rev Time 0.00
Received By llouie Date 2020-05-11 Time   Sent To  
Notes
2020-05-11 17:35:17ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) MINOR PD AMENDMENT REQUIRED FOR THE AS-BUILT PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.).

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By llouie Date 2020-03-10 Time   Rev Time  
Received By llouie Date 2020-03-10 Time   Sent To  
Notes
2020-03-10 16:17:42** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY OF LOT IS REQUIRED.
  
 2.) MISSING SITE PLAN. SITE PLAN MUST INCLUDE ALL
 RELEVANT DIMENSIONS (I.E. BUILDING SETBACKS, LOT
 DIMENSIONS, ETC.).
  
  
  
 NOTES:
  
 * SEPARATE LANDSCAPE PERMIT REQUIRED.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (MERRY PLACE - 34 TH UNITS)
  
 * 1910 MERRY PLACE; 18 FT. WIDE LOT; 18 FT. WIDE UNIT
 (INTERIOR)
  
 * REFERENCE: PB 1421 (MERRY PLACE RPD)
  