Plan Review Details - Permit 20020633
Plan Review Stops For Permit 20020633 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2020-03-16 |
Time |
|
Rev Time |
|
Received By |
rrossano |
Date |
2020-03-16 |
Time |
|
Sent To |
I |
|
Notes |
2020-03-23 11:04:30 | PASS WITH PROVISOS: PLEASE ADDRESS PLUMBING CONCERNS. | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | CONCERNS, THANKS. | | | | RICK ROSSANO, PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX: | | (561) 494-1116 MOBILE: (561) 246-9525 | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | | MANNY GONZALEZ, SENIOR ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 MOBILE: (561) 644-7301 EMAIL: | | [email protected] WWW.WPB.ORG/ENGINEERING | | | 2020-03-16 14:14:58 | PLEASE PROVIDE SURVEY SHOWING PROPOSED WORK RELATIVE TO | | RIGHT OF WAY. | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | CONCERNS, THANKS. | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-30 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-03-30 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-03-25 |
Time |
12:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-03-21 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-02-25 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-03-30 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-03-30 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-03-27 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-03-16 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-03-16 |
Time |
14:13 |
Sent To |
|
|
Notes |
2020-03-16 14:28:40 | 1) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR. THERE IS | | A NOTE ON THE PLAN THAT STATES THE INTERCEPTOR HAS BEEN | | DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH FL. ADMIN. | | CODE CHAPTER 64E-6 BUT THE SUBMITTED DETAIL DOES NOT | | SHOW COMPLIANCE. CLARIFY. | | 2) THE SUBMITTED APPLICATION STATES "GREASE TRAP | | REPAIR" BUT THE PLANS SHOW TWO NEW INTERCEPTORS BEING | | INSTALLED. CLARIFY AND UPDATE THE DESCRIPTION ON THE | | APPLICATION.WPB AMEND. TO FBC SEC. 107.2.1. | | 3) INDICATE ON THE PLAN THE SIZE AND NUMBER OF THE | | EXISTING GREASE TRAPS BEING REPLACED. WPB AMEND. TO FBC | | SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2020-03-18 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-03-18 |
Time |
04:05 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-03-18 |
Time |
04:05 |
Sent To |
|
|
Notes |
2020-03-18 04:06:11 | PLANS DRAWN BY CONTRACTOR. SIGNATURE NOT REQD. T.LARGE |
|
|
|