Plan Review Details - Permit 20020613
Plan Review Stops For Permit 20020613
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By ppetty Date 2020-05-08 Time 10:02 Rev Time 0.00
Received By ppetty Date 2020-05-08 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-04 Cont ID  
Sent By ppetty Date 2020-05-04 Time 09:24 Rev Time 0.00
Received By ppetty Date 2020-05-08 Time 09:58 Sent To  
Notes
2020-05-04 09:24:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-20 Cont ID  
Sent By ppetty Date 2020-02-20 Time 08:44 Rev Time 0.00
Received By ppetty Date 2020-02-20 Time 08:44 Sent To  
Notes
2020-02-20 08:45:32PLEASE SEE F/D NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-05-07 Cont ID  
Sent By pleduc Date 2020-05-07 Time   Rev Time 0.00
Received By pleduc Date 2020-05-07 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By pleduc Date 2020-04-28 Time   Rev Time 0.00
Received By pleduc Date 2020-04-28 Time 12:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-02-19 Cont ID  
Sent By pleduc Date 2020-02-19 Time   Rev Time 0.00
Received By pleduc Date 2020-02-19 Time 13:10 Sent To E
Notes
2020-02-19 13:30:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FA 2 - OFFICE 3 DOES NOT INDICATE ANY
 NOTIFICATION DEVICE PER NFPA 101 & 72
  
 PER NFPA 101, CH 9
  
 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH
 9.6.3.5.8,
 NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE
 AUDIBLE, AND
 VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM
 AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN
 NATIONAL
 STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND
 FACILITIES, OR
 OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY
 HAVING
 JURISDICTION SHALL BE PROVIDED.
  
 9.6.3.5.1 AREAS NOT SUBJECT TO OCCUPANCY BY PERSONS WHO
 ARE
 HEARING IMPAIRED SHALL NOT BE REQUIRED TO COMPLY WITH
 THE
 PROVISIONS FOR VISIBLE SIGNALS
  
 PLEASE REVIEW AND CORRECT AND/OR JUSTIFY WITH SPECIFIC
 CODE REFERENCES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-08 Cont ID  
Sent By ppetty Date 2020-05-08 Time 10:03 Rev Time 0.00
Received By ppetty Date 2020-05-06 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-04 Cont ID  
Sent By ppetty Date 2020-05-04 Time 09:25 Rev Time 0.00
Received By ppetty Date 2020-04-27 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-20 Cont ID  
Sent By ppetty Date 2020-02-20 Time 08:46 Rev Time 0.00
Received By ppetty Date 2020-02-14 Time 13:14 Sent To  
Notes
2020-02-18 13:15:00ROUTED TO FIRE INBOX