2020-02-13 06:01:11 | 1) YOU HAVE SUBMITTED A PE PIPE SIZING SHEET WITH TWO |
| DIFFERENT SIZING TABLES ON IT. WHICH ONE IS BEING USED |
| TO SIZE THE PE SYSTEM? ALSO, WHERE IS THIS SIZING TABLE |
| FROM? THE SYSTEM MUST BE SIZED BASED ON THE TABLES IN |
| THE 2017 FBC-FUEL GAS CODE OR USING THE SIZING TABLES |
| INCLUDED IN A LISTED PIPING SYSTEM'S MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. 2017 FBC-FUEL GAS CODE |
| SEC.402.3. |
| 2) THE SIZING TABLE SUBMITTED FOR THE SCH. 40 METALLIC |
| PIPE IS FROM THE UNIFORM PLUMBING CODE. THIS IS NOT A |
| REFERENCED STANDARD IN THE 2017 FBC-FUEL GAS CODE OR |
| PLUMBING CODE. THEREFORE THIS SIZING TABLE IS |
| UNACCEPTABLE. SUBMIT A SIZING TABLE FROM ONE OF THE |
| REQUIREMENTS IN THE 2017 FBC-FUEL GAS CODE SEC.402.3. |
| 3) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE |
| LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH |
| THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 4) THE BTU LOAD OF THE RANGE ON THE GAS DRAWING IS |
| SHOWN AS 28,100 BTU'S. ADDING UP THE BTU LOAD OF THE |
| BURNER'S ON THE MANUFACTURER'S SPECIFICATION SHEET |
| COMES TO 54,600 BTU'S. WHERE DDID THE 28,100 BTU LOAD |
| COME FROM? |
| 5) A SEPARATE PERMIT WILL BE REQUIRED FOR THE ELECTRIC |
| THAT NEEDS TO BE INSTALLED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |