2020-02-24 07:56:52 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20020470 |
| ADD: 1801 N. FLAGLER DR. / SUITE 302 |
| CONT: BENCHMARK PAINTING & CARPENTRY |
| TEL: 908-514-3123 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. FEB. 24TH/ 2020 |
| ACTION: BUILDING PROVISO |
| |
| 1) THE PLANS ARE NOT CLEAR IF THE BATHROOM FLOOR TILE |
| IS BEING REMOVED AND NEW MARBLE/ TILE IS BEING |
| INSTALLED. IF SO THEN SHOW COMPLIANCE WITH THE |
| FOLLOWING 3 REQUIREMENTS. BLDG TYPE: TYPE I/ TYPE II |
| FLOOR INSULATION (FBC-B 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS: |
| |
| 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| |
| 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |