Plan Review Details - Permit 20020470
Plan Review Stops For Permit 20020470
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-30 Cont ID  
Sent By shill Date 2020-03-30 Time 09:51 Rev Time 0.00
Received By shill Date 2020-03-30 Time 09:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-03-21 Cont ID  
Sent By shill Date 2020-03-21 Time 11:32 Rev Time 0.00
Received By shill Date 2020-03-21 Time 11:32 Sent To  
Notes
2020-03-21 11:33:00A VERY LENGTHY LETTER WAS PROVIDED BUT IT NEEDS TO HAVE
 ONLY THE EXACT LANGUAGE BELOW. PLEASE EMAIL THE
 ACKNOWLEDGEMENT TO [email protected].
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By jwitmer Date 2020-02-24 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:21 Sent To  
Notes
2020-02-24 07:57:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-02-24 Cont ID  
Sent By jwitmer Date 2020-02-24 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:21 Sent To  
Notes
2020-02-24 07:56:522017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020470
 ADD: 1801 N. FLAGLER DR. / SUITE 302
 CONT: BENCHMARK PAINTING & CARPENTRY
 TEL: 908-514-3123
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24TH/ 2020
 ACTION: BUILDING PROVISO
  
 1) THE PLANS ARE NOT CLEAR IF THE BATHROOM FLOOR TILE
 IS BEING REMOVED AND NEW MARBLE/ TILE IS BEING
 INSTALLED. IF SO THEN SHOW COMPLIANCE WITH THE
 FOLLOWING 3 REQUIREMENTS. BLDG TYPE: TYPE I/ TYPE II
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX,SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jpearson Date 2020-03-18 Time 10:54 Rev Time 0.00
Received By jpearson Date 2020-03-18 Time 10:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 15:04 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 15:04 Sent To I
Notes
2020-03-01 15:04:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW THAT IS DESIGNED
 BY AND SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR DESIGNED BY AND SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-14 Cont ID  
Sent By pleduc Date 2020-02-14 Time   Rev Time 0.00
Received By pleduc Date 2020-02-14 Time 13:50 Sent To  
Notes
2020-02-14 13:52:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) IF REQUIRED, ANY AND ALL WORK ON THE FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY A CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-21 Cont ID  
Sent By shill Date 2020-03-21 Time 11:33 Rev Time 0.00
Received By shill Date 2020-03-17 Time 09:37 Sent To  
Notes
2020-03-18 09:37:45RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-12 Time 14:08 Sent To  
Notes
2020-02-13 14:08:35B03

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-02-25 Cont ID  
Sent By jesmith Date 2020-02-25 Time 16:09 Rev Time 0.00
Received By jesmith Date 2020-02-25 Time 16:09 Sent To  
Notes
2020-02-25 16:09:29PLUMBING COMMENTS: APPROVED WITH PROVISO
  
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE AS A
 DEFERRED SUBMITTAL, A DETAIL SHOWING HOW THE ORIGINAL
 TUB BOX VOID AND THE NEW PIPE PENETRATION WILL BE
 FIRESAFED. IF EXISTING PIPING IS PVC THEN A UL ASSEMBLY
 SHALL BE SUBMITTED. IF EXISTING AND NEW PENETRATION ARE
 METAL THEN SUBMIT ON AN APPROVED FIRE RATED CONCRETE.
 SUBMITTAL SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO INSPECTION. PROCEED AT YOUR OWN RISK.
  
 THE FOLLOWING IS NOTED:
 NO RELOCATION OF FIXTURES. RISER DIAGRAMS ARE NOT
 REQUIRED.
 THE TUB IN THE MASTER BATH IS BEING REPLACED WITH A
 SHOWER STALL. THE NEW CONTROL VALVE IS BEING RELOCATED
 TO THE OPPOSITE WALL.
  