Plan Review Details - Permit 20020422
Plan Review Stops For Permit 20020422
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 14:36 Rev Time 0.00
Received By jgomez Date 2020-04-01 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-03-16 Cont ID  
Sent By jgomez Date 2020-03-16 Time 15:50 Rev Time 0.00
Received By jgomez Date 2020-03-16 Time 15:20 Sent To  
Notes
2020-03-16 16:10:32ROOF RECOVER FOURTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 RESPONSE:
 NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE CONTENT
 TEST TAS 126. THESE TESTS NEED TO BE DONE BY AN
 APPROVED TESTING AGENCY AND ALL TEST REPORTS, INCLUDING
 CALCULATIONS SHALL BE SIGNED BY A REGISTERED DESIGN
 PROFESSIONAL. SEE SCOPE ON TESTING APPLICATION
 STANDARDS 105 AND 126 RESPECTIVELY. TESTING SUBMITTED
 IS NOT DONE BY AN APPROVED TESTING AGENCY AND IS NOT
 SIGNED BY REGISTERED DESIGN PROFESSIONAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-02 Cont ID  
Sent By jgomez Date 2020-03-02 Time 15:12 Rev Time 0.00
Received By jgomez Date 2020-03-02 Time 14:35 Sent To  
Notes
2020-03-02 14:36:52ROOF RECOVER THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By jgomez Date 2020-02-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2020-02-26 Time 15:16 Sent To  
Notes
2020-02-26 15:19:26ROOF RECOVER SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95
 FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET
 THE DESIGN PRESSURE FOR ALL ROOF ZONES. SEC. 1609.1
 FBC-BUILDING.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF
 PRODUCT APPROVAL SUBMITTED.
  
 RESPONSE:
 RAS 117 CALCULATIONS SUBMITTED NEED TO BE REVISED.
 ENGINEER STATED THAT CONCRETE FASTENERS NEED TO HAVE
 MIN. 1 INCH EMBEDMENT. ACCORDING TO NOTE #2 ON PAGE 2
 OF 67 OF FLORIDA PRODUCT APPROVAL FL16443-R17
 SUBMITTED, THE MINIMUM EMBEDMENT REQUIRED IS 1.25
 INCHES. ENGINEER TO REVISE SPECIFICATIONS OR PROVIDE
 COMPLETE ENGINEERING SHOWING THAT THE 1 INCHE EMBEDMENT
 IS ADEQUATE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 10:52 Rev Time 0.00
Received By jgomez Date 2020-02-11 Time 17:52 Sent To  
Notes
2020-02-12 10:53:22ROOF RECOVER BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95
 FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET
 THE DESIGN PRESSURE FOR ALL ROOFF ZONES. SEC. 1609.1
 FBC-BUILDING.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF
 PRODUCT APPROVAL SUBMITTED.
  
 2- NEED FIELD UPLIFT TESTING TAS 124 (2 COPIES) AS
 REQUIRED BY NOTE #12 ON PAGE 3 OF 67 OF FL16443-R17
 FOR BONDED INSULATION OR MEMBRANE OVER EXISTING
 SUBSTRATES IN A RECOVER INSTALLATION.
 FAC 61G20-3.001SEC. 1609.1 FBC-BUILDING.
  
 3- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 4-THERE ARE SEVERAL BUILDINGS AND ROOF AREAS IN THIS
 PROPERTY. PROVIDE SKETCH (2 COPIES) SHOWING THE ROOF
 AREA WHERE WORK IS GOING TO TAKE PLACE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 14:36 Rev Time 0.00
Received By jgomez Date 2020-04-01 Time 12:57 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-16 Cont ID  
Sent By jgomez Date 2020-03-16 Time 16:10 Rev Time 0.00
Received By jgomez Date 2020-03-13 Time 13:02 Sent To I
Notes
2020-03-16 13:02:15RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-02 Cont ID  
Sent By jgomez Date 2020-03-02 Time 15:14 Rev Time 0.00
Received By jgomez Date 2020-02-28 Time 13:32 Sent To I
Notes
2020-03-02 13:32:16RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-26 Cont ID  
Sent By jgomez Date 2020-02-26 Time 16:03 Rev Time 0.00
Received By jgomez Date 2020-02-25 Time 13:23 Sent To  
Notes
2020-02-26 13:23:58RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 10:54 Rev Time 0.00
Received By jgomez Date 2020-02-11 Time 12:29 Sent To  
Notes
***NONE***