Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-27 Cont ID  
Sent By jgomez Date 2020-02-27 Time 14:38 Rev Time 0.00
Received By jgomez Date 2020-02-27 Time 13:58 Sent To  
Notes
2020-02-27 14:14:07RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. ENGINEER IS REFERENCING AND OLD FLORIDA
 PRODUCT APPROVAL FL16730-R22. ENGINEER IS SPECIFYING
 SYSTEM W-56 ON PAGE 14 OF 100. ACCORDING TO THE OLD
 FLORIDA PRODUCT APPROVAL, THIS IS A NON-INSULATED
 SYSTEM. FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED IS
 FL16730-R24 AND IS MARKED WITH ASSEMBLY W-54 WHICH IS
 AN INSULATED ASSEMBLY. REVISE AS REQUIRED TO MATCH.
 NOTE: ENGINEER NEEDS TO REFERENCE THE CURRENT FLORIDA
 PRODUCT APPROVAL FL 16730-R24 TO AVOID CONFLICTS
 DELAYS. RE-SUBMIT REVISED RAS 117 CALCULATIONS SHOWING
 THE CORRECT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS.
 (PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED).
  
 2- OK.
  
 3- OK.
  
 4- OK
  
 5- OK.
  
  
 PROVISO:
 8/12 ROOF TILE SLOPE REQUIRES EVERY TILE TO BE FASTENED
 IN ADDITION TO THE ADHESIVE. SEE PAGE 9 OF FRSA/TRI 5TH
 EDITION REVISED AND SEC. R905.3.2 FBC-RESIDENTIAL.
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-21 Cont ID  
Sent By jgomez Date 2020-02-21 Time 17:56 Rev Time 0.00
Received By jgomez Date 2020-02-21 Time 16:01 Sent To  
Notes
2020-02-21 16:12:02RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. ENGINEER IS REFERENCING AND OLD FLORIDA
 PRODUCT APPROVAL FL16730-R22. ENGINEER IS SPECIFYING
 SYSTEM W-56 ON PAGE 14 OF 100. ACCORDING TO THE OLD
 FLORIDA PRODUCT APPROVAL, THIS IS A NON-INSULATED
 SYSTEM. FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED IS
 FL16730-R24 AND IS MARKED WITH ASSEMBLY W-54 WHICH IS
 AN INSULATED ASSEMBLY. REVISE AS REQUIRED TO MATCH.
 NOTE: ENGINEER NEEDS TO REFERENCE THE CURRENT FLORIDA
 PRODUCT APPROVAL FL 16730-R24 TO AVOID CONFLICTS
 DELAYS. RE-SUBMIT REVISED RAS 117 CALCULATIONS SHOWING
 THE CORRECT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS.
 (PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED).
  
 2- OK.
  
 3- OK.
  
 4- OK
  
 5- OK.
  
  
 PROVISO:
 8/12 ROOF TILE SLOPE REQUIRES EVERY TILE TO BE FASTENED
 IN ADDITION TO THE ADHESIVE. SEE PAGE 9 OF FRSA/TRI 5TH
 EDITION REVISED AND SEC. R905.3.2 FBC-RESIDENTIAL.
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 18:32 Rev Time 0.00
Received By jgomez Date 2020-02-07 Time 18:13 Sent To  
Notes
2020-02-07 18:33:10RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- ROOF TILE AND ROOF TILE ADHESIVE PRODUCT APPROVALS
 SUBMITTED. CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED
 BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 3- ROOF TILE CHANNEL METAL PRODUCT APPROVAL SUBMITTED.
 PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
 AND CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 4- ROOF TILE PRODUCT APPROVAL SUBMITTED. PROVIDE
 COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT APPROVAL
 SUBMITTED IS MISSING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE. THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE
 CURRENT CODE VERSION AND THE PRODUCT APPROVAL STATUS.
 CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 5-- ROOF TILE UNDERLAYMENT SUBMITTED FOR ADHESIVE
 APPLICATIONS: CLEARLY MARK WHICH SPECIFIC UNDERLAYMENT
 TYPE AND UNDERLAYMENT SYSTEM IS GOING TO BE USED TO
 VERIFY COMPLIANCE WITH THE WIND LOADS SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE SEC. 5.6.4 OF FLORIDA
 PRODUCT APPROVAL SUBMITTED AND CLEARLY IDENTIFY
 UNDERLAYMENT SYSTEM TO BE USED. IF USING THE FRSA/TRI
 INSTALLATION MANUAL, THEN PROVIDE APPLICABLE TABLES AND
 CLEARLY MARK PROPOSED INSTALLATION AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-27 Cont ID  
Sent By jgomez Date 2020-02-27 Time 14:38 Rev Time 0.00
Received By jgomez Date 2020-02-27 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-21 Cont ID  
Sent By jgomez Date 2020-02-21 Time 17:56 Rev Time 0.00
Received By jgomez Date 2020-02-20 Time 13:47 Sent To I
Notes
2020-02-21 13:47:36RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 18:33 Rev Time 0.00
Received By jgomez Date 2020-02-06 Time 14:56 Sent To I
Notes
***NONE***