2020-02-18 10:45:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M101: THE PREVIOUSLY UNCONDITIONED STORAGE |
| BUILDING SHALL BE IN FULL COMPLIANCE WITH THE FLORIDA |
| ENERGY CONSERVATION CODE- 2017 SIXTH EDITION. PLEASE |
| SUBMIT A COMPLIANCE REPORT- SECTION C101.5 FBC EC. |
| |
| 2) M101: PLEASE CLARIFY WHY THE BUILDING IS BEING |
| CONDITIONED. PROVIDE A BRIEF NARRATIVE DESCRIBING THE |
| USE OF THE STORAGE SPACES. PLEASE NOTE THAT CHANGES OF |
| OCCUPANCY SHALL COMPLY THE FLORDIA EXISTING BUILDING |
| CODE- 2017 SIXTH EDITION (SECTION 101.2 FBC EX) AND MAY |
| REQUIRE A FL. LICENSED DESIGN PROFESSIONAL TO PROVIDE |
| PLANS AND SPECIFICATIONS. |
| |
| 3) M101: IT APPEARS THAT THE STORAGE SPACES HAVE GARAGE |
| BAY DOORS WHICH INDICATES VEHICLES MAY BE STORED IN THE |
| SPACES. REFER TO TABLE 403.3.1.1 AND SECTION 404: |
| EXHAUST VENTILATION SYSTEMS REQUIRED. |
| |
| 4) M101: THE SUBMITTED AC HEAT LOAD CALCULATIONS DO NOT |
| INDICATE BAY DOORS ON THE INPUT DATA SHEET- SECTION |
| C403.2.1 FBC EC. |
| |
| 5) M101: THE CORRIDOR SHALL NOT BE USED TO RETURN AIR |
| TO THE AIR HANDLER. PROVIDE DUCTED RETURNS- SECTION |
| 601.2 FBC M. |
| |
| 6) PROVIDE AN ELECTRICAL PLAN AND ELECTRICAL SUB-PERMIT |
| APPLICATION- SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |