Plan Review Details - Permit 20020168
Plan Review Stops For Permit 20020168
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status N Date 2020-05-04 Cont ID  
Sent By jwitmer Date 2020-05-04 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2020-05-04 Time 08:34 Sent To  
Notes
2020-05-04 08:40:03PERMIT 18081402. SHELL PERMIT, NEW CONSTRUCTION. JW.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 08:24 Sent To  
Notes
2020-02-18 09:24:20ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-04 Cont ID  
Sent By jwitmer Date 2020-05-04 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2020-05-04 Time 08:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 08:24 Sent To  
Notes
2020-02-18 11:24:312017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020168
 ADD: 6500 S. DIXIE HWY.
 CONT: KCA CONSTRUCTION
 TEL: 561-361-1491
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 18TH/ 2020
 ACTION: DENIED
  
 1A) THE COVERSHEET LIST THE WORK TO BE ACCOMPLISHED IS
 A LEVEL 3 ALTERATION UNDER THE 2017 FLORIDA EXISTING
 BUILDING CODE. THE PHOTOGRAPH SHOWN ON THE COVERSHEET
 SHOWS A VACANT LOT. UNDER THE MASTER PERMIT 18081402.
 THE PLAN SHOWS A PHASED PROJECT, A NEW SHELL BUILDING
 THE NORTH TENANT SPACE IS C/O-ED, THE TENANT SPACE B
 AND C ARE STILL SHELL SPACES. WITH THE TENANT SPACES B
 & C NOT EVER OCCUPIED THESE SPACES ARE CONSIDER NEW
 WORK UNDER THE CURRENT 2017 FLORIDA BUILDING CODE.
 PLEASE REVIEW UNDER THE 2017 FBC-EXISTING BUILDING CODE
 SECTION 101.4.1 BUILDINGS NOT PREVIOUSLY OCCUPIED.
  
 1B) PLEASE NOTE THERE ARE TWO VACANT SHELL SPACES
 TENANT B AND TENANT C. TO WHICH VACANT TENANT SPACE IS
 THE WORK TO BE PERFORMED UNDER THIS PERMIT? 2017
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED.
  
 2) SHEET 1.0A THE FLOOR PLAN DOES SHOW A NEW X-RAY
 MACHINE BEING INSTALLED AT THIS LOCATION. THERE WAS NO
 INFORMATION SUBMITTED FOR THE X-RAY MACHINE, THE AMOUNT
 OF RADIATION THE MACHINE DELIVERED FROM THE SEALED
 SOURCE OR HOUSING EXCEEDS 0.005 REMS PER HOUR 2017
 FBC-B SECTION465.4.8 OR QUALIFIES AS HIGH RADIATION
 REQUIRING CONTROL OF ACCESS TO HIGH RADIATION AREAS PER
 FBC-B SECTIONS 465.2 AND 465.5 GENERAL REQUIREMENTS,
 465.2 X-RAY FILM PROCESSING FACILITIES AND 465.6 DOOR,
 INTERLOCK AND WARNING SYSTEMS. PLEASE NOTE IF THE HIGH
 RADIATION EQUIPMENT AND PROCESS IS TO BE INSTALLED THE
 DEPARTMENT OF HEALTH, RULE 64E-5 AND FLORIDA
 ADMINISTRATIVE CODE, AND CHAPTER 404 FLORIDA STATUTE
 NEEDS TO BE ADDRESSED AS WELL.
  
 3) SHEET 1.0A THE FLOOR PLAN SHOWS THE RESTROOM WITH
 EXISTING WALLS, THERE ARE NO DETAILS TO DETERMINE IF
 THE EXISTING RESTROOM AND COMPONENTS MEETS THE
 ACCESSIBILITY REQUIREMENTS FOUND IN THE 2017
 FBC-ACCESSIBILITY CODE.
 2017 FBC-EXISTING BUILDING CODE SECTION 806.1. A
 BUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING CODE
 ACCESSIBILITY.
  
 DISPROPORTIONATE COST. PLEASE PROVIDE A LETTER EITHER
 FROM THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE UP TO
 ($9,000.00)IS GOING TO BE SPENT IN ACCESSIBLE UPGRADES
 TO THE PROJECT. IF ALL EXISTING CONDITIONS ARE
 COMPLETED (COMPLIED) BEFORE DISPROPORTIONATION COST IS
 MET A LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By jpearson Date 2020-05-12 Time 09:57 Rev Time 0.00
Received By jpearson Date 2020-05-12 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 13:26 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 13:26 Sent To I
Notes
2020-03-01 13:26:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ORIGINAL PLANS FOR PERMIT 18081402 SHOW A 200 AMP
 AUTOMATIC TRANSFER SWITCH CONNECTED TO THE GENERATOR AS
 PART OF THE RISER DIAGRAM. THIS DRAWING DOES NOT SHOW
 AN ATS. PROVIDE CLARIFICATION AND/OR CORRECTIONS. WPB
 FBC 107.2.1
 2. ORIGINAL PLANS FOR PERMIT 18081402 SHOW 1/0 SIZE
 FEEDERS IN THE GUTTER TO METER CAN, AND FROM METER CAN
 TO DISCONNECT. THE PROVIDED PLAN STATES THAT THE
 FEEDERS TO THE PANEL WILL BE REPLACED, BUT IS SILENT IN
 REGARDS TO THESE CONDUITS. PROVIDE CORRECTION. NEC
 310.15(B)(16); WPB FBC 107.2.1
 3. PLAN DOES NOT STATE WHICH TENANT SPACE THIS BUILD
 OUT WILL OCCUPY. PROVIDE CORRECTION. WPB FBC 107.2.1
 4. PROVIDE UPDATED AIC CALCULATIONS AND NOTES FOR
 STICKERS WITH CHANGE IN WIRE SIZE. NEC 110.9, 110.10,
 110.16, 110.24; WPB FBC 107.2.1
 5. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 310.15, 408.30
 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By pleduc Date 2020-05-01 Time   Rev Time 0.00
Received By pleduc Date 2020-05-01 Time 10:40 Sent To  
Notes
2020-05-01 10:54:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET 1.0A - THE FRONT DOORS INDICATED AS 1 IN THE
 DOOR SCHEDULE HAS A DEADBOLT LOCK.
  
 PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7,
 MEANS OF EGRESS:
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET 1.0A - THE REAR EXIT DOOR INDICATED AS 2 IN
 THE DOOR SCHEDULE HAS A DEAD BOLT.
  
 PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7,
 MEANS OF EGRESS:
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 10:15 Sent To  
Notes
2020-02-12 10:22:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET 1.0A - THE FRONT DOORS INDICATED AS 1 IN THE
 DOOR SCHEDULE HAS A DEADBOLT LOCK.
  
 PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7,
 MEANS OF EGRESS:
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET 1.0A - THE REAR EXIT DOOR INDICATED AS 2 IN
 THE DOOR SCHEDULE HAS A DEAD BOLT.
  
 PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7,
 MEANS OF EGRESS:
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-12 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-30 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-05 Time 16:17 Sent To  
Notes
2020-02-06 16:17:41B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-04 Cont ID  
Sent By medwards Date 2020-05-04 Time 09:33 Rev Time 0.00
Received By medwards Date 2020-05-04 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By ccole Date 2020-02-18 Time 16:10 Rev Time 0.00
Received By ccole Date 2020-02-18 Time 14:29 Sent To  
Notes
2020-02-18 16:15:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20020168
 2/18/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.0M: THE CORRIDOR SHALL NOT BE USED TO CONVEY
 RETURN AIR TO THE AIR HANDLER- SECTION 601.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-04 Cont ID  
Sent By medwards Date 2020-05-04 Time 09:37 Rev Time 0.00
Received By medwards Date 2020-05-04 Time 09:33 Sent To  
Notes
***NONE***