Plan Review Stops For Permit 20020134 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2020-02-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-24 |
Time |
06:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-24 |
Time |
06:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-10 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-10 |
Time |
10:44 |
Sent To |
|
|
Notes |
2020-02-10 10:45:19 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | ASBESTOS COMMENTS: | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-02-26 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-26 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-26 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-02-10 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-10 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-10 |
Time |
10:45 |
Sent To |
|
|
Notes |
2020-02-10 11:02:42 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B/WPB AMENDMENTS 107.1, THE SUBMITTED PLANS NEED | | TO BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. | | | | 2) FBC B 107.2.1, PROVIDE ENGINEER APPROVED DETAILS ON | | TEMPORARY SUPPORT, AS IT APPEARS THAT STRUCTURAL | | BEARING COLUMNS AND WALLS ARE TO BE REMOVED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-02-24 |
Time |
08:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-02-24 |
Time |
08:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-02-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-02-21 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-02-21 |
Time |
09:43 |
Sent To |
P |
|
Notes |
2020-02-21 09:44:23 | NEED TO SUBMIT AN ELECTRICAL PERMIT JLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-03-02 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-03-02 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-03-02 |
Time |
15:02 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-02-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-02-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-02-12 |
Time |
13:52 |
Sent To |
E |
|
Notes |
2020-02-12 13:58:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS INSUFFICIENT INDORMATION PROVIDED TO | | DETERMINE THE ACTAUL SCOPE OF WORK AND EXACTLY WHAT IS | | BEING DONE. | | | | THE APPLICATION SHEET INDICATES "REMOVE INTERIOR WALL | | AND TILE FLOOR" | | | | THE SHEET EXG100 IS AN OPEN FLOOR PLAN WITH NUMEROUS | | DOTTED LINES AND FEW COMMENTS BUT NONE WITH REMOVE WALL | | NOR TILE FLOOR. | | | | THE SHEET A100 INDICATES COMPLEX INTERIOR DESIGN WITH | | NO CLEAR INDICATION OF ANY WALL REMOVAL NOT TILE WORK | | | | PLEASE REVIEW AND PROVIDE SEPECIFIC DETAILS OF THE | | SCOPE OF WORK AND EXACTLY WHERE THE WORK IS LOCATED AND | | EXACTLY WHAT IS PROPOSED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-03-05 |
Time |
05:04 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-02-25 |
Time |
13:30 |
Sent To |
|
|
Notes |
2020-02-26 13:30:17 | RESUB ROUTED TO PVALENTI |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-02-25 |
Time |
05:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-02-05 |
Time |
13:37 |
Sent To |
|
|
Notes |
2020-02-07 13:37:24 | GIVEN TO PVALENTI |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-03-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-03-05 |
Time |
05:04 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-03-05 |
Time |
04:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-02-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-02-25 |
Time |
05:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-02-25 |
Time |
05:13 |
Sent To |
|
|
Notes |
2020-02-25 05:23:26 | | | 1) THERE IS INSUFFICIENT INFORMATION PROVIDED TO | | DETERMINE THE ACTUAL SCOPE OF WORK AND EXACTLY WHAT IS | | BEING DONE.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHT. EXG100 SHOWS FOUR TOILET ROOMS. INDICATE ON THE | | PLANS IF THE FIXTURES ARE BEING REMOVED FROM THESE | | TOILET ROOMS AND HOW REQUIRED SANITARY FACILITIES ARE | | BEING PROVIDED. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SHT. A100 HAS BEEN SUBMITTED BUT IS A COMPLEX | | BUILDOUT. CLARIFY THE REASON OF THE SUBMITTAL OF THIS | | SHEET.WPB AMEND. TO FBC SEC. 107.2.1. | | 4) PLEASE REVIEW AND PROVIDE SEPECIFIC DETAILS OF THE | | SCOPE OF WORK AND EXACTLY WHERE THE WORK IS LOCATED AND | | EXACTLY WHAT IS PROPOSED. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|