Plan Review Details - Permit 20020086
Plan Review Stops For Permit 20020086
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-28 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-26 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-05 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-28 Cont ID  
Sent By ccole Date 2020-02-28 Time 14:08 Rev Time 0.00
Received By ccole Date 2020-02-28 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-13 Cont ID  
Sent By ccole Date 2020-02-13 Time 11:32 Rev Time 0.00
Received By ccole Date 2020-02-13 Time 10:20 Sent To  
Notes
2020-02-13 12:19:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020086
 2/13/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 OF THE DUCT PLAN WHICH SHOWS THE FAMILY ROOM
 AND WHAT APPEARS TO BE GUEST ROOMS NEEDS TO BE A
 CLEARER COPY FOR REVIEW. MUCH OF THE PRINT IS
 ILLEGIBLE- SECTION 107.2.1 WPB.
  
 2) PLACE NOTES ON THE PLANS TO INDICATE IF THE AIR
 HANDLER IN THE GARAGE IS NEW, EXISTING, OR RELOCATED-
 107.2.1 WPB.
  
 3) THE PLAN APPEARS TO SHOW FLEX DUCTS RUNNING THROUGH
 THE GARAGE FROM THE AIR HANDLER WHICH IS NOT PERMITTED
 PER SECTION- R302.5.2 FBC RES DUCT PENETRATION.
 DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR
 CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL
 BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE (0.48 MM) SHEET
 STEEL, 1 INCH (25.4 MM) MINIMUM RIGID NONMETALLIC CLASS
 0 OR CLASS 1 DUCT BOARD, OR OTHER APPROVED MATERIAL AND
 SHALL NOT HAVE OPENINGS INTO THE GARAGE.
  
 4) SHEET 1: IT APPEARS NO AIR IS BEING RETURNED FROM
 THE 16X13' BEDROOM- SECTION M1602.3 FBC RES.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE AC SYSTEM ON
 THE PLAN. INCLUDE MAKE AND MODEL, COOLING AND HEATING
 CAPACITY, SUPPLY CFM CAPCITY, AND EFFICIENCY RATING-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-02-13 Cont ID  
Sent By ccole Date 2020-02-13 Time 12:19 Rev Time 0.00
Received By ccole Date 2020-02-13 Time 12:19 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved