Plan Review Details - Permit 20020083
Plan Review Stops For Permit 20020083
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-02-11 Cont ID  
Sent By jgomez Date 2020-02-11 Time 10:17 Rev Time 0.00
Received By jgomez Date 2020-02-11 Time 10:17 Sent To  
Notes
2020-02-11 10:18:20BUILT ON 2006.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 11:21 Rev Time 0.00
Received By jgomez Date 2020-04-01 Time 10:16 Sent To  
Notes
2020-04-01 11:21:50BUILDING REVIEW APPROVED WITH PROVISO:
 1)SEPARATE SPRINKLER PERMIT WILL BE REQUIRED FOR ANY
 MODIFICATIONS.
 2)FLOORING SOUND INSULATION MATERIAL FOR NEW TILE:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-10 Cont ID  
Sent By jgomez Date 2020-03-10 Time 13:10 Rev Time 0.00
Received By jgomez Date 2020-03-10 Time 11:37 Sent To  
Notes
2020-03-10 12:53:33SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 1- OK
 2- OK
 3- SEPARATE SPRINKLER PERMIT WILL BE REQUIRED FOR ANY
 MODIFICATIONS.
  
 ORIGINAL COMMENT.
 4-FLOORING SOUND INSULATION MATERIAL FOR NEW TILE:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 5- OK
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jgomez Date 2020-02-11 Time 13:50 Rev Time 0.00
Received By jgomez Date 2020-02-11 Time 08:43 Sent To  
Notes
2020-02-11 13:50:55BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ADDRESS OF PROJECT SHOWN ON ALL PLANS IS INCORRECT.
 THE CORRECT ADDRESS IS 610 CLEMATIS ST. NOT 601. REVISE
 AS REQUIRED. NOTE: COVER SHEET HAS 4 PLACES LISTING THE
 INCORRECT ADDRESS. PLEASE MAKE SURE ALL THE INFORMATION
 IS CORRECTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ONLY ONE SET OF PLANS WAS SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. THE OTHER COPY WAS NOT SIGNED AND
 SEALED. BOTH COPIES NEED TO BE SIGNED AND SEALED
 (ORIGINAL SEAL AND SIGNATURE) SEC. 107.1 CITY
 AMENDMENTS. CHAPTER 481 FLORIDA STATUTES.
  
 3- INFORMATION ABOUT SPRINKLER HEADS IS NOT CLEAR. SEC.
 107.2.1 CITY AMENDMENTS. KEY NOTE #8 ON THE DEMOLITION
 PLAN ON SHEET A2.1 CALLS FOR REMOVAL AND CAPPING OF
 EXISTING SIDEWALL SPRINKLER HEAD AND SUPPLY LINE. ON
 THE OTHER HAND, KEY NOTE #11ON THE NEW FLOOR PLAN ON
 SHEET A2.2 CALLS TO VERIFY IF EXISTING SPRINKLER HEAD
 WILL COVER THE NEW EXPOSED AREA. CLEARLY SPECIFY
 PROPOSED ALTERATION TO THE SPRINKLER SYSTEM. NOTE:
 SEPARATE PERMIT WILL BE REQUIRED.
  
 4-FLOORING SOUND INSULATION MATERIAL FOR NEW TILE:
  
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF
 SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-31 Cont ID  
Sent By ppetty Date 2020-03-31 Time 10:48 Rev Time 0.00
Received By ppetty Date 2020-03-31 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By jpearson Date 2020-03-10 Time 07:21 Rev Time 0.00
Received By jpearson Date 2020-03-10 Time 07:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By jpearson Date 2020-02-07 Time 13:49 Rev Time 0.00
Received By jpearson Date 2020-02-07 Time 13:45 Sent To  
Notes
2020-02-07 13:49:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. THIS RESPONSIBLE PERSON SHOULD BE EITHER A
 DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 10:45 Sent To  
Notes
2020-03-04 10:51:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-07 Cont ID  
Sent By pleduc Date 2020-02-07 Time   Rev Time 0.00
Received By pleduc Date 2020-02-07 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 11:40 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 13:06 Sent To I
Notes
2020-03-30 13:07:01B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-26 Time 13:38 Sent To  
Notes
2020-03-12 11:47:47MECHANICAL REVIEW REQUIRED PER HAROLD MOSER; ADDED STOP
2020-02-27 13:38:33B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-12 Cont ID  
Sent By lcrespo Date 2020-02-12 Time 15:34 Rev Time 0.00
Received By lcrespo Date 2020-02-04 Time 13:32 Sent To  
Notes
2020-02-05 13:32:22B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 09:11 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 08:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-16 Cont ID  
Sent By ccole Date 2020-03-16 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-03-16 Time 10:55 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-31 Cont ID  
Sent By ccole Date 2020-03-31 Time 09:13 Rev Time 0.00
Received By ccole Date 2020-03-31 Time 09:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jesmith Date 2020-03-12 Time 11:45 Rev Time 0.00
Received By jesmith Date 2020-03-12 Time 11:30 Sent To  
Notes
2020-03-12 11:45:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING STACK
 THAT WASHER DRYER IS TO BE CONNECTED TO. PROVIDE A
 SANITARY RISER DIAGRAM SHOWING HOW KEYNOTE #7 ON PLAN
 PAGE A2.2 WILL BE ACCOMPLISHED. IF THIS IS A SINGLE
 PIPE STACK (WASTE STACK VENT AS DESCRIBED IN FBC PL
 913), IT SHALL NOT BE OFFSET. PLEASE REFER TO THE
 PROVISIONS OF FBC PL 905, 909 AND 913 FOR GUIDANCE.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20020083 610 CLEMATIS ST
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By lcrespo Date 2020-02-12 Time 15:21 Rev Time 0.00
Received By lcrespo Date 2020-02-12 Time 15:21 Sent To  
Notes
2020-02-12 15:32:5602/12/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE SECOND PLAN THE SIGNATURE AND SEAL ARE
 MISSING (OR SEAL, OR TITLE BLOCK, OR ALL THREE) WHICH
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  