Plan Review Details - Permit 20020071
Plan Review Stops For Permit 20020071
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By pvalenti Date 2020-05-08 Time 11:09 Rev Time 0.00
Received By pvalenti Date 2020-05-08 Time 10:50 Sent To  
Notes
2020-05-08 11:11:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE GATES WILL NEED TO MEET THE EGRESS REQUIREMENTS OF
 THE FLORIDA BUILDING CODE SECTION 1010.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-04 Cont ID  
Sent By pvalenti Date 2020-05-04 Time 14:57 Rev Time 0.00
Received By pvalenti Date 2020-05-04 Time 14:07 Sent To  
Notes
2020-05-04 14:34:40PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. FBC B 1010.2, GATES IN THE MEANS OF EGRESS ARE TO
 MEET THE SAME REQUIREMENTS AS DOORS. NO INFORMATION WAS
 PROVIDED REGARDING LOCKS AND SPECIFICATIONS OF LATCHES
 AND DROP RODS FOR EGRESS, AS IT APPEARS THAT THE DOG
 YARD IS PART OF THE EGRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 11:01 Rev Time 0.00
Received By shill Date 2020-03-22 Time 11:01 Sent To  
Notes
2020-03-22 11:06:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1010.2, GATES IN THE MEANS OF EGRESS ARE TO
 MEET THE SAME REQUIREMENTS AS DOORS. NO INFORMATION WAS
 PROVIDED REGARDING LOCKS, PURPOSE OF THIS ENCLOSED
 AREA, REVISE PLAN ACCORDINGLY. IF THIS AREA IS FOR
 STORAGE, HOW WILL THE EGRESS PATH BE KEPT CLEAR?
  
 2. GATE LOCATION NOT CLEAR, ONE APPEARS TO BE DRAWN BUT
 PLAN STATES THERE ARE TWO GATES.
  
 3. PLEASE PAY THE $10 BALANCE DUE ONLINE SO YOUR PERMIT
 CAN BE EMAILED TO YOU WHEN ISSUED.
  
 4. IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By pleduc Date 2020-05-05 Time   Rev Time 0.00
Received By pleduc Date 2020-05-05 Time 14:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By pleduc Date 2020-03-11 Time   Rev Time 0.00
Received By pleduc Date 2020-03-11 Time 14:31 Sent To B
Notes
2020-03-11 14:37:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE FENCED AREA APPEARS TO BE CLOSE OFF A PATH OF
 EGRESS TO A PUBLIC WAY FROM THE EXISTING WAREHOUSE.
  
 THE DOOR/GATE NEED TO BE IDENTIFIED AS AN EXIT AND
 PROVIDED WITH HARDWARE THAT DOES NOT REQUIRE SPECIAL
 KNOWLDGE OR EFFORT.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.5 DOOR LEAF OPERATING FORCES.
 7.2.1.4.5.1 THE FORCES REQUIRED TO FULLY OPEN ANY DOOR
 LEAF
 MANUALLY IN A MEANS OF EGRESS SHALL NOT EXCEED 15 LBF
 (67 N) TO
 RELEASE THE LATCH, 30 LBF (133 N) TO SET THE LEAF IN
 MOTION, AND 15
 LBF (67 N) TO OPEN THE LEAF TO THE MINIMUM REQUIRED
 WIDTH, UNLESS
 OTHERWISE SPECIFIED AS FOLLOWS:
 (1) THE OPENING FORCES FOR INTERIOR SIDE-HINGED OR
 PIVOTEDSWINGING
 DOOR LEAVES WITHOUT CLOSERS SHALL NOT EXCEED 5 LBF
 (22 N).
 (2) THE OPENING FORCES FOR EXISTING DOOR LEAVES IN
 EXISTING
 BUILDINGS SHALL NOT EXCEED 50 LBF (222 N) APPLIED TO
 THE LATCH
 STILE.
 (3) THE OPENING FORCES FOR HORIZONTAL-SLIDING DOOR
 LEAVES IN
 DETENTION AND CORRECTIONAL OCCUPANCIES SHALL BE AS
 PROVIDED
 IN CHAPTERS 22 AND 23.
 (4) THE OPENING FORCES FOR POWER-OPERATED DOOR LEAVES
 SHALL BE
 AS PROVIDED IN 7.2.1.9.
 7.2.1.4.5.2 THE FORCES SPECIFIED IN 7.2.1.4.5 SHALL BE
 APPLIED TO THE
 LATCH STILE.
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE REVIEW AND CORRECT/PROVIDE
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By aborngra Date 2020-05-06 Time 11:10 Rev Time 0.00
Received By aborngra Date 2020-05-06 Time 11:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By aborngra Date 2020-02-12 Time 09:58 Rev Time 0.00
Received By aborngra Date 2020-02-12 Time 09:58 Sent To Z
Notes
2020-02-12 09:58:15THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 VINYL AS A MATERIAL FOR FENCING IS A PROHIBITED
 MATERIAL AND REQUIRES HISTORIC PRESERVATION BOARD
 APPROVAL. STAFF WILL RECOMMEND A DENIAL FOR VINYL
 FENCING. STAFF RECOMMENDS CHANGING THE MATERIAL TO
 ALUMINUM OR WOOD.
  
 THE APPLICANT AND/OR PROPERTY IS WELCOME TO GO IN FRONT
 OF THE HISTORIC PRESERVATION BOARD. PLEASE SUBMIT ALL
 MATERIALS UNDER "SITE WALL & FENCES" ALONG WITH A
 $40.00 APPLICATION FEE. THE APPLICATION WILL BE
 DEFERRED TO THE HISTORIC PRESERVATION BOARD. THE NEXT
 APPLICATION DEADLINE IS FEBRUARY 19, 2020 FOR THE MARCH
 24, 2020 HISTORIC PRESERVATION BOARD MEETING.
  
 THE CERTIFICATE OF APPROPRIATENESS APPLICATION IS
 AVAILABLE UNDER GOVERNMENT > DEVELOPMENT SERVICES >
 FORMS OR BY USING THIS URL: HTTPS://WWW.WPB.ORG/GOVERNM
 ENT/DEVELOPMENT-SERVICES/FORMS
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-08 Cont ID  
Sent By pvalenti Date 2020-05-08 Time 11:11 Rev Time 0.00
Received By pvalenti Date 2020-05-08 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-06 Cont ID  
Sent By lmarchan Date 2020-05-06 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2020-05-04 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 11:06 Rev Time 0.00
Received By shill Date 2020-02-04 Time 13:08 Sent To  
Notes
2020-03-10 06:18:56ROUTED TO FIRE INBOX
2020-03-06 09:11:35ADDED FIRE STOP
 ROUTED FROM ZONING TO PERMIT LIBRARIAN 3/6/20 EL
2020-02-05 13:08:47ROUTED TO HISTORIC INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-04 Cont ID  
Sent By pvalenti Date 2020-05-04 Time 15:02 Rev Time 0.00
Received By pvalenti Date 2020-05-04 Time 15:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By elevesqu Date 2020-05-06 Time 16:36 Rev Time 0.00
Received By elevesqu Date 2020-05-06 Time 16:36 Sent To  
Notes
2020-05-06 16:37:28PROVISO: PARKING SPACE ADJACENT TO FENCE GATE SHALL
 BE STRIPED THROUGH AS NO PARKING AREA
  
 WOOD MATERIAL, NOT VINYL PER HISTORIC COMMENTS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By elevesqu Date 2020-03-06 Time 09:11 Rev Time 0.00
Received By elevesqu Date 2020-03-06 Time 09:10 Sent To  
Notes
2020-03-06 09:10:56GATE APPEARS TO OPEN INTO EXISTING PARKING SPACE - AS
 THE PROPOSED FENCE BLOCKS ONE OF THE MAIN ENTRANCES TO
 BUILDING, GATE WILL NEED TO BE ACCESS AT ALL TIMES
 NEED TO BLOCK OFF PARKING SPACE (DIAGONALLY STRIPE
 THROUGH) OR MOVE GAT ACCESS TO ALLEY WAY
  
 ADDING FIRE REVIEW STOP AS FENCE WILL BLOCK TWO
 BUILDING ENTRANCES
  
 IF THE PARKING SPACE DIRECTLY ADJACENT TO THE FENCE IS
 TO REMAIN, MUST BE ONE FOOT AWAY FROM FENCE PER PARKING
 REGULATIONS (TO ALLOW FOR DOOR OPENING)
  
 WILL CURB STOP BE REMOVED INTERNAL TO FENCE? PLEASE
 INDICATE
  
 PLEASE SHOW LOCATION OF BAR OPENING - NEED TO SEE IN
 COMPARISON TO FENCE LOCATION
  
 WILL ASPHALT BE REMOVED AND OTHER MATERIAL INSTALLED?
  
 SEE HISTORIC COMMENTS FOR FENCE MATERIAL
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426