Plan Review Details - Permit 20011221
Plan Review Stops For Permit 20011221
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By rmcdouga Date 2020-03-11 Time 17:05 Rev Time 0.00
Received By rmcdouga Date 2020-03-11 Time 17:05 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-06 Cont ID  
Sent By rmcdouga Date 2020-02-06 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2020-02-06 Time 15:27 Sent To I
Notes
2020-02-06 16:31:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. FBC
 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS SHALL
 BE DESIGNED TO RESIST THE LOADS SET FORTH IN CHAPTER 16
 OF THIS CODE EXCEPT THAT STRUCTURES OR PARTS THEREOF
 WHICH ARE INTENDED TO BE REMOVED OR REPOSITIONED DURING
 PERIODS OF HIGH WIND VELOCITY SHALL BE DESIGNED IN
 THEIR OPEN OR EXTENDED POSITION TO DESIGN PRESSURES
 BASED ON A BASIC WIND SPEED OF MINIMUM 115 MPH,
 3-SECOND WIND GUST WITH APPLICABLE SHAPE FACTORS TO
 RESIST NOT LESS THAN 10 PSF ROOF LIVE LOAD.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-11 Cont ID  
Sent By rmcdouga Date 2020-03-11 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2020-03-03 Time 13:42 Sent To  
Notes
2020-03-11 15:26:053/11 RESUB ROUTED TO RMCDOUGAL
2020-03-04 13:42:14RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-06 Cont ID  
Sent By rmcdouga Date 2020-02-06 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2020-01-30 Time 13:21 Sent To  
Notes
2020-02-04 18:16:44ROUTED TO MISC 2 INBOX
2020-01-31 13:22:05ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By rfalcone Date 2020-03-11 Time 10:52 Rev Time 0.00
Received By rfalcone Date 2020-03-11 Time 10:52 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-04 Cont ID  
Sent By rfalcone Date 2020-02-04 Time 14:31 Rev Time 0.00
Received By rfalcone Date 2020-02-04 Time 14:31 Sent To I
Notes
***NONE***