Plan Review Stops For Permit 20011157 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-16 |
Time |
11:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-02-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-02-13 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-02-13 |
Time |
14:39 |
Sent To |
|
|
Notes |
2020-02-13 16:46:50 | HEART AND SOUL PARK | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) PLEASE PROVIDE SIGNED AND SEALED GATEWAY WALL | | DETAILS FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH | | FBC 1609 | | 2) PLEASE PROVIDE SIGNED AND SEALED PLAYGROUND | | EQUIPMENT FOUNDATION AND ATTACHMENTS TO THE FOUNDATION | | FBC 1609 | | 3) PLEASE PROVIDE SIGNED AND SEALED DETAILS FOR THE | | SHADE SAIL - (FOUNDATION, POLE DESIGNATION, HEIGHT FROM | | GROUND, AND ALL ATTACHMENTS). FBC 1609 AND 3102 | | 4) PLEASE PROVIDE SIGNED AND SEALED FOUNDATION, POLE | | AND ATTACHMENT DETAILS FOR THE LIGHT POLES TO COMPLY | | WITH FBC 1609 | | 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE | | STRUCTURES LISTED ABOVE PER FBC 1603.1.4 | | 6) ALL PROVIDED SHOP DRAWINGS/DETAILS NEED TO BE | | REVIEWED AND MARKED APPROVED BY THE PARK DESIGNER OF | | RECORD. FBC WPB AMENDMENTS 107.3.4 | | 7) PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED COPY OF | | THE GEOTECHNICAL REPORT (AN ELECTRONICALLY SIGNED | | DOCUMENT WOULD BE BETTER FOR ELECTRONIC PERMITTING). | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-03-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-03-25 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-03-25 |
Time |
08:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-02-18 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-02-15 |
Time |
23:55 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-02-13 |
Time |
10:35 |
Sent To |
|
|
Notes |
2020-02-18 09:10:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE NOTE ON PLAN THAT SIGNS WILL REQUIRE | | SEPARATE PERMITS. FBC 105.1 FBC 107.2.1 | | | | 2. PROVIDE NOTE ON PLAN THAT IN-USE RECEPTACLES | | WEATHERPROOF COVERS WILL BE USED PER NEC 406.9B1 | | | | 3. PROVIDE NOTE ON PLAN THAT EXTERIOR LIGHTING WILL | | COMPLY WITH FBC CE 405.2.5 (10 HOUR BATTERY BACKUP) FOR | | ALL LIGHTING TIMER SWITCHES | | | | 4. NO WIRE OR CONDUIT SIZE SHOWN FOR FEEDER TO PANEL A. | | FBC 107.2.1 | | | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | 6.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE | | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | AVAILABLE PER NEC 110.24. | | | | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | 8. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF ALL | | MATERIALS AND EQUIPMENT (LIGHTING ETC) FBC 107.2.1 NEC | | 90.7, 110.2, 110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2020-05-20 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2020-05-20 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2020-05-20 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2020-03-16 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2020-03-16 |
Time |
|
Sent To |
I |
|
Notes |
2020-03-16 13:34:50 | UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL E20030021. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2020-02-04 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2020-02-04 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2020-02-04 |
Time |
|
Sent To |
|
|
Notes |
2020-02-04 11:53:18 | PLEASE SUBMIT PLANS DIRECTLY TO ENGINEERING SERVICES | | FOR FORMAL REVIEW. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2020-03-17 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2020-03-17 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2020-03-17 |
Time |
14:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2020-01-31 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2020-01-31 |
Time |
14:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-26 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-03-26 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-03-12 |
Time |
15:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-18 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-29 |
Time |
16:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-03-17 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2020-03-17 |
Time |
19:17 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2020-03-16 |
Time |
16:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-02-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-18 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-02-14 |
Time |
16:22 |
Sent To |
|
|
Notes |
2020-02-18 10:13:47 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES | | PER WPB UTILITIES. PLACE NOTE ON PLAN | | | | 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH | | EDITION 2017 PLEASE CORRECT NOTE #7 ON SHEET P101 UNDER | | GENERAL NOTES. | | | | 3. PROVIDE PIPING DETAIL WATER AND SANITARY FOR THE | | WATER FOUNTAIN SHOWING ALL SHUT VALVE P-TRAP AND VENT. | | PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 4. PROVIDE DETAIL FOR ELECTRICAL OUTLET PEDESTAL WITH | | HOSE BIB NOTE ON PLAN REFERENCE ELECTRICAL DRAWING I | | COULD NOT LOCATE ANY DETAILS. PER WPB AMEND TO FBC | | 107.3.5.1.3(13) | | | | 5. EACH HOSE BIB IS REQUIRED TO HAVE A VACUUM BREAKER | | AND SHUT OFF VALVE. PER FBC PL 608.15.4.2, 606.2(2) | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
Rev No |
2 |
Status |
P |
Date |
2020-03-17 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2020-03-17 |
Time |
19:17 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2020-03-16 |
Time |
16:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-02-14 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-02-14 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-02-14 |
Time |
16:47 |
Sent To |
|
|
Notes |
2020-02-14 16:53:16 | 1ST REVIEW: 20010844 | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. BACKFLOW REQUIRED SHOW LOCATION SEPARATE PERMIT | | REQUIRED. PER WPB UTILITIES CROSS CONNECTION MANUAL. | | NOTE ON PLAN SEPARATE PERMIT REQUIRED FOR BACKFLOW | | DEVICE. | | | | 2. RAIN SENSOR REQUIRED SHOW LOCATION. PER FS 373.62 | | | | 3. SHOW LOCATION OF CONTROLS. PER WPB AMEND TO FBC | | 107.2.1 | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-03-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-03-16 |
Time |
11:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-02-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-02-13 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-02-13 |
Time |
16:55 |
Sent To |
|
|
Notes |
2020-02-13 16:56:44 | ALL SIGNATURES OK AT THIS TIME - NEW DRAWINGS ADDED | | WILL NEED TO BE LOOKED AT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-03-26 |
|
|
Cont ID |
|
Sent By |
elevesqu |
Date |
2020-03-26 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
elevesqu |
Date |
2020-03-25 |
Time |
16:34 |
Sent To |
|
|
Notes |
2020-03-26 10:16:12 | LANDSCAPE TO BE REVIEWED THROUGH SEPARATE LANDSCAPE | | PERMIT - NOT APPROVED AS PART OF THIS PERMIT | | | | APPLICANT SHALL CONSIDER THE INCORPORATION OF A RAMP ON | | THE EAST SIDE OF ROSEMARY AVE AT THE 8TH STREET | | INTERSECTION AND CONSIDER THE REALIGNMENT OF THE RAMP | | ON THE EAST SIDE OF ROSEMARY AT 7TH STREET FOR ENHANCED | | CONNECTIVITY | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | [email protected] | | 561 822 1426 | 2020-03-25 16:34:28 | LANDSCAPE TO BE REVIEWED THROUGH SEPARATE PERMIT - | | PLEASE REMOVE LANDSCAPE PLANS FROM THIS SET | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-02-13 |
|
|
Cont ID |
|
Sent By |
elevesqu |
Date |
2020-02-13 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
elevesqu |
Date |
2020-02-13 |
Time |
15:41 |
Sent To |
|
|
Notes |
2020-02-13 15:41:45 | SITE PLAN APPROVAL NEEDED PRIOR TO ZONING PERMIT REVIEW | | | | PLEASE ENSURE THAT ALL PAGES MATCH THE ZONING APPROVAL | | SET ONCE APPROVED | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | [email protected] | | 561 822 1426 |
|
|