2020-01-27 09:00:16 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 20010973 |
| REVIEWED: JANUARY 27, 2020 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) PROVIDE ENGINEERING FOR ENHANCED NAILING AS STATED |
| IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS 5.9 |
| - PLEASE SELECT THE SYSTEM THAY WILL BE USED AND IF THE |
| PRESSURE DOESN'T EXCEED ALL 3 ZONES(1,2 AND 3), PROVIDE |
| ENGINEERING FOR ATTACHMENT. |
| NOTE: |
| THE PROPERTY 308 WILDERMERE IS EXPOSURE CATEGORY C |
| |
| 2) PLEASE STATE THE AMOUNT OF SQ. FOOTAGE OF FLAT ROOF |
| AND SLOPE ROOF SEPARATE. STATE THE ROOF PITCH OF |
| SHINGLE AREA AND SEE COMMENT BELOW IF ROOF PITCH IS |
| LESS THAN 4/12 FOR DOUBLE LAYER UNDERLAYMENT. |
| |
| 3) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM |
| TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND |
| LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. |
| - PLEASE ADD NOTE FOR DOUBLE UNDERLAYMENT IF PITCH OF |
| SHINGLE ROOF AREA IS LESS THAN 4/12. |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |