Plan Review Details - Permit 20010869
Plan Review Stops For Permit 20010869
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-04-06 Cont ID  
Sent By cpuell Date 2020-04-06 Time 11:10 Rev Time 0.00
Received By cpuell Date 2020-04-06 Time 11:10 Sent To  
Notes
2020-04-06 11:11:04USED 74414224060230010 UNTIL PBC GIVES US A PCN,
 PROPOERTY IS LOCATED IN THE CITY.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By cpuell Date 2020-03-31 Time 15:32 Rev Time 0.00
Received By cpuell Date 2020-03-31 Time   Sent To  
Notes
2020-03-31 15:38:5200414236000005010 IS A PCN FOR PALM BEACH COUNTY, IF
 ANNEXED PLEASE GET WITH ENGINEERING AND SEAN MACDONALD,
 ADDRESSING TECHNICIAN AT PALM BEACH COUNTY -
 561-233-5316 OR E-MAIL AT [email protected]
  
2020-03-30 14:38:16LOOKS TO ME LIKE THIS IS LOATED AT:PCN:
 00414236000005010
 OWNER: WEST PALM BEACH CITY OF
 LOCATION: 10071 60TH ST N
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-30 Cont ID  
Sent By jbrooks Date 2020-01-30 Time 14:40 Rev Time 0.00
Received By jbrooks Date 2020-01-30 Time 14:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By jpearson Date 2020-03-11 Time 12:09 Rev Time 0.00
Received By jpearson Date 2020-03-11 Time 12:09 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-26 Cont ID  
Sent By jbrooks Date 2020-01-30 Time 14:41 Rev Time 0.00
Received By jpearson Date 2020-01-26 Time 13:43 Sent To  
Notes
2020-01-26 13:25:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE DETAIL SHOWING ALL ELECTRIAL CONNECTIONS
 INSTALLED ABOVE THE ELECTRICAL DATUM PLANE. NEC 555.9,
 555.5
 3. PROVIDE GROUND FAULT PROTECTION. NEC 555.3
 4. RISER DIAGRAM SHOWS A #6 EQUIPMENT GROUNDING
 CONDUCTOR INSTALLED IN THE FPL FEED TO THE METER CAN.
 THIS CONDUIT SHOULD NOT INCLUDE AN EGC. PROVIDE
 CORRECTION. NEC 250.6, 250.24
 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By spalmer Date 2020-03-16 Time 17:44 Rev Time 0.00
Received By spalmer Date 2020-03-06 Time 14:40 Sent To  
Notes
2020-03-13 17:22:05TO RM DESK
  
2020-03-09 14:40:42RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By jbrooks Date 2020-01-30 Time 14:41 Rev Time 0.00
Received By jbrooks Date 2020-01-22 Time 16:18 Sent To E
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2020-03-16 Cont ID  
Sent By rmcdouga Date 2020-03-16 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2020-03-16 Time 08:43 Sent To I
Notes
2020-03-16 09:42:22APPROVED WITH PROVISO
  
 THIS PROJECT IS LOCATED IN AN AE FLOOD ZONE WITH A BFE
 OF 18.2 FEET NAVD 88. THE CITY OF WEST PALM BEACH HAS A
 REQUIRED 2 FOOT FREEBOARD IN ADDITION TO THE FIRM'S
 18.2 FT. FOR A TOTAL REQUIRED ELEVATION OF 20.2 FEET
 NAVD 88. THE PLANS SHOW THAT THE GRAVEL AREA WHERE THE
 EQUIPMENT IS LOCATED HAS AN ELEVATION OF 22.1 FT NGVD
 29. SUBMIT A FINAL SURVEY OF THE PROJECT WITH THE
 ELEVATION SHOWN IN NAVD 88, SHOWING THAT THE EQUIPMENT
 IS AT OR ABOVE THE REQUIRED BFE OF 20.2 FEET NAVD 88 AT
 FINAL INSPECTION.