Plan Review Stops For Permit 20010803 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2020-02-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-02-20 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-02-20 |
Time |
17:21 |
Sent To |
|
|
Notes |
2020-02-20 17:22:21 | LETTER FROM THE CONTRACTOR WAS SUBMITTED. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
18:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
18:57 |
Sent To |
|
|
Notes |
2020-01-31 19:04:32 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-02-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-02-20 |
Time |
17:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-02-20 |
Time |
17:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-02-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-02-03 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
18:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-02-24 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-02-24 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-02-24 |
Time |
08:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-01-28 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-01-28 |
Time |
14:41 |
Sent To |
|
|
Notes |
2020-01-28 14:38:05 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR | | ENGINEERS. THIS ENGINEER HAS PREVIOUSLY BEEN WARNED | | THAT FUTURE DOCUMENTS WOULD NOT BE ACCEPTED IF | | SELF-CERTIFIED. PROVIDE CORRECTION. WPB FBC 107.1; FS | | 471/481 | | 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | 3. PROVIDE DETAIL OF SEPARATION OF LOW VOLTAGE WIRES | | AND POWER WIRES IN J-BOX. WPB FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-02-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-02-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-02-20 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-01-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-01-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-01-22 |
Time |
15:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-02-25 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-02-25 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-02-25 |
Time |
14:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-02-03 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-21 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
18:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
18:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2020-02-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-02-20 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-02-20 |
Time |
11:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-01-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-01-27 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-01-27 |
Time |
16:11 |
Sent To |
|
|
Notes |
2020-01-27 16:34:25 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #20010803 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-1: IT APPEARS THAT FIRE DAMPERS ARE MISSING | | WHERE SUPPLY DUCTS ARE PENETRATING THE CONTROL ROOM | | WALLS- SECTION 607.5.2 FBC M. | | | | 2) M-1 & LS1.0: PROVIDE DETAILS FOR VENTING OF THE CT | | SCAN IF REQUIRED BY MANUFACTURER'S SPECIFICATIONS. SHOW | | THE TYPE AND SIZE OF VENT, VENT RUN AND TERMINATION | | LOCATION- SECTION 304.1 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
2 |
Status |
P |
Date |
2020-02-25 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-02-25 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-02-25 |
Time |
14:28 |
Sent To |
|
|
Notes |
2020-02-25 14:28:45 | MEDICAL GAS COMMENTS: APPROVED | | | | 20010803 2201 45TH ST | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
1 |
Status |
P |
Date |
2020-01-29 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-29 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-29 |
Time |
16:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-02-25 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-02-25 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-02-25 |
Time |
14:27 |
Sent To |
|
|
Notes |
2020-02-25 14:28:18 | PLUMBING COMMENTS: APPROVED | | | | 20010803 2201 45TH ST | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2020-01-29 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-29 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-29 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-02-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-02-20 |
Time |
18:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-02-20 |
Time |
18:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-01-28 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-01-28 |
Time |
14:32 |
Sent To |
|
|
Notes |
2020-01-28 14:32:06 | ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC, | | EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL | | PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD | | PARTY VERIFICATION. SELF-CERTIFICATION IS NOT | | ACCEPTABLE FOR ENGINEERS. THIS ENGINEER HAS PREVIOUSLY | | BEEN WARNED THAT FUTURE DOCUMENTS WOULD NOT BE ACCEPTED | | IF SELF-CERTIFIED. PROVIDE CORRECTION. WPB FBC 107.1; | | FS 471/481 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2020-01-28 |
Time |
16:50 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2020-01-28 |
Time |
16:45 |
Sent To |
|
|
Notes |
|
|