Plan Review Details - Permit 20010663
Plan Review Stops For Permit 20010663
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-03 Cont ID  
Sent By pvalenti Date 2020-03-03 Time 15:24 Rev Time 0.00
Received By pvalenti Date 2020-03-03 Time 15:24 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By pvalenti Date 2020-02-26 Time 08:57 Rev Time 0.00
Received By pvalenti Date 2020-02-26 Time 08:05 Sent To  
Notes
2020-02-26 08:58:24***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-03 Cont ID  
Sent By jwitmer Date 2020-02-03 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2020-02-03 Time 07:32 Sent To  
Notes
2020-02-03 08:36:36PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-03 Cont ID  
Sent By pvalenti Date 2020-03-03 Time 15:24 Rev Time 0.00
Received By pvalenti Date 2020-03-03 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By pvalenti Date 2020-02-26 Time 08:41 Rev Time 0.00
Received By pvalenti Date 2020-02-26 Time 08:05 Sent To  
Notes
2020-02-26 08:56:02***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 603.1/FBC B 1207.2/FBC B 1207.3, IT APPEARS THAT
 USING THE SELECTED FLOORING UNDERLAYMENT (PRO FLEX RCU
 250) HAS ONLY BEEN APPROVED FOR 8" THICK SLABS NOT 6".
  
 PLEASE PROVIDE THE ASTM E- 84 FLAME SPREAD, ASTM E - 90
 SOUND TRANSMISSION LOSS, AND ASTM E - 492 IMPACT SOUND
 TRANSMISSION LOSS SPECIFICATIONS FOR 6" THICK SLABS OR
 PROVIDE AN ALTERNATE PRODUCT THAT HAS BEEN APPROVED FOR
 THE 6" SLABS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-03 Cont ID  
Sent By jwitmer Date 2020-02-03 Time 08:49 Rev Time 0.00
Received By jwitmer Date 2020-02-03 Time 07:32 Sent To  
Notes
2020-02-03 08:49:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010663
 ADD: 1551 N. FLAGLER DR. SUITE: 815
 CONT: MEKA USA
 TEL: 561-756-4810
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 03/2020
 ACTION: DENIED
  
 1) THE A-002 DEMOLITION NOTE 1 INDICATES THE PLANS WERE
 DESIGNED TO THE 2017 RESIDENTIAL CODE. THE FLORIDA
 RESIDENTIAL CODE IS FOR ONE & TWO FAMILY CONSTRUCTION
 FOR R-3 CONSTRUCTION. PLEASE NOTE CONDOMINIUM UNITS AND
 APARTMENTS ARE OCCUPANCY TYPE R-2 AND DESIGNED UNDER
 THE 2017 FBC-B SECTION 420 AND HIGHRISE UNDER
 SECTION403 NOT THE 1 & 2 FAMILY RESIDENTIAL CODE.
  
 2) SHEET A-002 NOTE 13 INDICATES THE REQUIREMENT FOR
 IMPACT INSULATION UNDERLAYMENT REQUIREMENT OF 50 IIC
 MIN. 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "THE CODE SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017) WHAT TYPE OF FLOOR FINISH IS GOING TO BE
 INSTALLED THROUGHOUT THE UNIT? IS THE FLOOR FINISH
 MATERIAL GOING TO BE THE SAME THROUGHOUT THE
 CONDOMINIUM OR DIFFERENT SUCH AS TILE IN THE BATHROOMS
 BUT WOOD LAMINATE IN ALL OTHER ROOMS. THE NWE NEED THE
 TEST REPORTS FOR EACH FLOORING TYPE WITH UNDERLATMENT.
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By jleahy Date 2020-03-12 Time 13:05 Rev Time 0.00
Received By jleahy Date 2020-03-12 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jleahy Date 2020-02-11 Time 07:03 Rev Time 0.00
Received By jleahy Date 2020-02-11 Time 06:58 Sent To  
Notes
2020-02-11 07:33:02FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PENINSULAR SPACE HAS AN OVERHANG THAT LOOKS TO BE
 MORE THAN 6" THE OUTLET MOUNTED BELOW WOULD NOT MEET
 THE REQUIREMENTS OF THE RECEPTACLE SPACING.
  
 E3901.4.5 RECEPTACLE OUTLET LOCATION.
 RECEPTACLE OUTLETS SHALL BE LOCATED NOT MORE THAN 20
 INCHES (508 MM) ABOVE THE COUNTERTOP. RECEPTACLE OUTLET
 ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE LISTED FOR
 THE APPLICATION. RECEPTACLE OUTLETS SHALL NOT BE
 INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR
 COUNTERTOPS. RECEPTACLE OUTLETS RENDERED NOT READILY
 ACCESSIBLE BY APPLIANCES FASTENED IN PLACE, APPLIANCE
 GARAGES, SINKS OR RANGETOPS AS ADDRESSED IN THE
 EXCEPTION TO SECTION E3901.4.1, OR APPLIANCES OCCUPYING
 DEDICATED SPACE SHALL NOT BE CONSIDERED AS THESE
 REQUIRED OUTLETS. [210.52(C)(5)]
  
 EXCEPTION: RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 MOUNTED NOT MORE THAN 12 INCHES (305 MM) BELOW THE
 COUNTERTOP IN CONSTRUCTION DESIGNED FOR THE PHYSICALLY
 IMPAIRED AND FOR ISLAND AND PENINSULAR COUNTERTOPS
 WHERE THE COUNTERTOP IS FLAT ACROSS ITS ENTIRE SURFACE
 AND THERE ARE NO MEANS TO MOUNT A RECEPTACLE WITHIN 20
 INCHES (508 MM) ABOVE THE COUNTERTOP, SUCH AS IN AN
 OVERHEAD CABINET. RECEPTACLES MOUNTED BELOW THE
 COUNTERTOP IN ACCORDANCE WITH THIS EXCEPTION SHALL NOT
 BE LOCATED WHERE THE COUNTERTOP EXTENDS MORE THAN 6
 INCHES (152 MM) BEYOND ITS SUPPORT BASE. [210.52(C)(5)
 EXCEPTION]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-02-26 Cont ID  
Sent By pleduc Date 2020-02-26 Time   Rev Time 0.00
Received By pleduc Date 2020-02-26 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-21 Cont ID  
Sent By pleduc Date 2020-01-21 Time   Rev Time 0.00
Received By pleduc Date 2020-01-21 Time 12:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-21 Time 10:29 Sent To  
Notes
2020-02-25 10:29:53B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-11 Cont ID  
Sent By jleahy Date 2020-02-11 Time 07:33 Rev Time 0.00
Received By jleahy Date 2020-01-16 Time 16:40 Sent To  
Notes
2020-01-16 16:40:58B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-03 Cont ID  
Sent By jwitmer Date 2020-02-03 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2020-02-03 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By ccole Date 2020-03-02 Time 08:44 Rev Time 0.00
Received By ccole Date 2020-03-02 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By ccole Date 2020-02-04 Time 12:38 Rev Time 0.00
Received By ccole Date 2020-02-04 Time 12:30 Sent To  
Notes
2020-02-04 12:43:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010663
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) RETURN AIR FROM THE BEDROOMS REQUIRED. PLEASE NOTE
 THAT ALL AIR INTO A MASTER SUITE INCLUDING THE BATH AND
 CLOSETS SHALL BE RETURNED- SEE SECTION 601.6 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-17 Cont ID  
Sent By jwitmer Date 2020-03-17 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2020-03-17 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By gjohnson Date 2020-01-30 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2020-01-30 Time 10:57 Sent To  
Notes
2020-01-30 11:54:421ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A-001 UNDER THE DEMOLITION NOTES #1. STATES THE
 WORK SHALL COMPLY TO THE RESIDENTIAL CODE BUT THIS IS A
 MULTIFAMILY THE RESIDENTIAL ONLY APPLIES TO 1=2 FAMILY
 THIS WORK SHALL COMPLY WIT H FBC 2017 6TH EDITION FBC
 PLUMBING ANS FBC MECHANICAL PLEASE CHANGE NOTE . PER
 WPB AMEND TO FBC 107.2.1
  
 2. THIS BUILDING WAS DESIGNED AND BUILT IN COMPLIANCE
 WITH THE FAIR HOUSING ACT AND SHALL REMAIN IN
 COMPLIANCE THE PLAN SHALL SHOW THE DESIGN SPEC OF THE
 BATHROOM A OR B SHOWING CLEAR FLOOR SPACE AND BACKING
 FOR GRAB BARS OR IF IT IS NOT TO BE IN COMPLIANCE
 PROVIDE A LETTER FROM THE ARCHITECT, CONTRACTOR AND THE
 OWNER STATING THAT THEY ARE AWARE THAT THE UNIT IS NOT
 IN COMPLIANCE WITH THE FAIR HOUSING ACT AND THE OWNER
 MAY BE RESPONSIBLE TO BRING THE UNIT BACK INTO
 COMPLIANCE AT THE OWNERS EXPENSE IF THE UNIT IS EVER
 SOLD. FAIR HOUNIG DESIGN MANUAL OR THE FAIR HOUING
 GUIDELINE CANBE FOUND IN THE BACK OF THE FLORIDA
 BUIDING CODE ACCESSIBILITY OR ON THE WEB AT FAIR
 HOUSING FIRST
  
 3. THE SHUT OFF VALVE FOR THE STACKABLE WASHING MACHINE
 SHALL BE ACCESSIBLE WITHOUT MOVING THE APPLIANCE. PER
 FBC PL 606.3
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]