Plan Review Details - Permit 20010490
Plan Review Stops For Permit 20010490 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:34 |
Sent To |
|
|
Notes |
2020-02-15 07:54:00 | PLAN REVIEW - BUILDING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. CITY OF WPB CHPT. 1 ? VALUE | | 109.3 BUILDING PERMIT VALUATIONS. | | VALUATION ? BASED ON THE INTERNATIONAL CODE COUNCIL | | (ICC) BUILDING VALUATION DATA YOUR STATED VALUE HAS | | BEEN CHANGED FROM $80,000 TO $185,770. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. | | | | 2. PROVIDE SURVEY AND SITE DRAINAGE PLAN | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED ON A BOUNDARY LINE SURVEY. | | | | 3. PROVIDE FINISHED FLOOR ELEVATION | | R403.1.7.3 FOUNDATION ELEVATION. | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | ALL LOCATIONS ON THE SITE. | | | | 4. ROOFING, MECHANICAL, ELECTRICAL & PLUMBING | | SUB-PERMITS REQUIRED - | | PERMITS 105.1 REQUIRED. | | | | 5. PROVIDE PRODUCT APPROVALS | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | SUBMITTALS. | | | | 6. PROVIDE ENERGY SUBMITTAL AND EPL DISPLAY CARD | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.+ | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 1) ENERGY GAUGE FORM R405 - SECTION R405.2 FBC EC. | | | | 2) PROVIDE MANUAL J WORKSHEETS - AC SYSTEM SIZING | | CALC?S - SECTION R403.7.1 FBC EC. | | | | 3) R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | (MANDATORY). | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:34 |
Sent To |
|
|
Notes |
2020-02-15 10:00:55 | PLAN REVIEW - ELECTRICAL | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ELECTRICAL SUB-PERMIT REQUIRED | | PERMITS - 105.1 REQUIRED. | | | | 2. TITLE BLOCK AND SIGNATURE OF DESIGNER | | THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A | | TITLE BLOCK AND SIGNATURE ON THE ELECTRICAL PLAN SHEET | | E-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. | | LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO | | PROVIDE AN ORIGINAL SEAL AND SIGNATURE PER FL. STATUE | | AND SECTIONS 61G15-16.003 AND 23.002 FAC. | | | | 3. AIC: | | PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM | | UTILITY. | | | | E3404.2INTERRUPTING RATING. | | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS | | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 | | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT | | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN | | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT | | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) | | | | PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC | | 110.3, 110.9; FBC RE E3606.4 | | | | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED | | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 | | | | 4. REMOVE REFERENCE ON PANEL SCHEDULE TO SMALL | | APPLIANCES FROM MASTER BATH CIRCUT #22 AND BATH #1 | | CIRCUT #24. | | A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE | | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-06 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:33 |
Sent To |
|
|
Notes |
2020-02-15 07:55:32 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:33 |
Sent To |
|
|
Notes |
2020-02-15 09:05:29 | PLAN REVIEW - MECHANICAL | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. MECHANICAL SUB-PERMIT REQUIRED | | 105.1 REQUIRED. | | | | 2. PROVIDE ENERGY GUAGE FORM 405 AND MANUAL J | | WORKSHEETS. | | 1) ENERGY GAUGE FORM R405 - SECTION R405.2 FBC EC. | | | | 2) PROVIDE MANUAL J WORKSHEETS - AC SYSTEM SIZING | | CALC?S - SECTION R403.7.1 FBC EC. | | | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | (MANDATORY). | | | | 3. MECHANICAL CONTRACTOR OR DESIGNER OF RECORD SHALL | | SIGN PLAN. | | TITLE BLOCK AND SIGNATURE OF DESIGNER | | THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A | | TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET | | M-1 | | SECTION 107.2.1 WPB. | | | | 4. PROVIDE TAMPER PROOF LOCKING GAS CAPS | | M1411.8 LOCKING ACCESS PORT CAPS. | | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL | | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR | | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED | | ACCESS. | | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE | | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING | | UNIT CABINET. | | | | 5. CONDENSING UNIT MOUNTING DETAIL | | M -1: PROVIDE ENGINEERING FOR INSTALLATION OF THE | | CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS | | M1305.1.4.1 AND M1401.4 FBC RES. | | | | 6. SHOW LOCATION OF BATHROOM EXHAUST FANS AND DISCHARGE | | ON PLAN | | NOTES 1 AND 4 ON MECH. PLAN DO NOT SPECIFY THEIR | | INTENDED USE | | M1501.1OUTDOOR DISCHARGE. | | THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM | | SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH | | SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN | | ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE. | | | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-02-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-02-07 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-02-07 |
Time |
07:16 |
Sent To |
|
|
Notes |
2020-02-07 07:26:39 | 02/07/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLUMBING RISER DIAGRAM REQUIRED WPB AMENDMENTS TO | | THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING | | | | 2. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | TO THE FBC SEC. 105.1. | | | | 3. PLANS DO NOT HAVE A SIGNATURE (OR SEAL, OR TITLE | | BLOCK, OR ALL THREE) ARE NOT IN ACCORDANCE WITH FLORIDA | | ADMINISTRATIVE CODE 61G15-23.001, FLORIDA STATUTE 471. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-02-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-15 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:34 |
Sent To |
|
|
Notes |
2020-02-15 08:33:01 | PLAN REVIEW - ROOFING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING SUB-PERMIT REQUIRED | | 105.1 REQUIRED. | | | | 2. PROVIDE PRODUCT APPROVALS | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-02-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-02-08 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-02-07 |
Time |
07:33 |
Sent To |
|
|
Notes |
2020-02-08 10:59:55 | PLAN REVIEW - SIGNATURE AND SEAL | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | DIGITAL SIGATURES AND SEALS PER FS 668.003. | | | | NAME AND SIGNATURE OF DESIGNER OF RECORD SEC 107.3.4.1 | | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5) AND F.S. 481.229. | | | | PURSUANT TO FBC 107.1, AND FS 481.229 (1) I, AS THIS | | DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE | | PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481. | | SEE BELOW: | | | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES& | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | TITLE BLOCK | | | | FBC-107.1 GENERAL ? FAC 61G1-16.004 ? A TITLE BLOCK | | MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN | | DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT | | ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK | | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION | | NUMBER OF THE PERSON SEALING THE DOCUMENT. | | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE | | REVISED. | | (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO | | BE A CORPORATION, LIMITED LIABILITY COMPANY, | | PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME, | | OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN | | HIS OR HER OWN NAME. | | | | DESIGN PROFESSIONAL ? EXCEPTIONS | | | | FS 481.229 ?EXCEPTIONS; EXEMPTIONS FROM LICENSURE. | | (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN | | ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS | | FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR | | ALTERATION OF: | | (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY | | FARMER, REGARDLESS OF THE COST OF THE BUILDING; | | (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING, | | TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY | | ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST; | | | | EXCEPTION TO THE ABOVE | | | | RESIDENTIAL | | DESIGNER (NON-PROFESSIONAL) SHALL DEMONSTRATE | | COMPLIANCE WITH FBC R301.1 (PRESCRIPTIVE DESIGN) AND | | FBC R301.1.3 (ENGINEERED DESIGN) | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-02-14 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2020-02-14 |
Time |
|
Rev Time |
|
Received By |
awooten |
Date |
2020-02-14 |
Time |
|
Sent To |
|
|
Notes |
2020-02-14 09:11:38 | **********************ZONING REVIEW | | FAILED****************** | | | | PROVIDE A SURVEY OF PROPERTY AND A SITE PLAN SHOWING | | ALL SETBACKS. ADDITIONAL COMMENTS MAY FOLLOW FURTHER | | REVIEW. | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | PERMIT. SHOWING THE FOLLOWING: | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | BEACH | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | | | DRIVEWAYS, POOLS, AND FENCES REQUIRE A SEPARATE PERMIT. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] |
|
|
|