|
 |
 |
 |
 |
 |
Plan Review Details - Permit 20010485
Plan Review Stops For Permit 20010485 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2020-02-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-02-14 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-02-14 |
Time |
09:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-01-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-17 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-17 |
Time |
15:21 |
Sent To |
|
|
Notes |
2020-01-17 15:23:01 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | ASBESTOS COMMENTS: | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-01-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-01-17 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-01-17 |
Time |
15:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-02-13 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-02-13 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-02-13 |
Time |
07:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-01-30 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-01-30 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-01-30 |
Time |
14:47 |
Sent To |
FIRE |
|
Notes |
2020-01-30 14:47:06 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | (S) | | | | 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL. | | PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO | | [email protected] AND CC [email protected] AND | | [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL | | IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN | | REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE | | SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-01-31 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-01-31 |
Time |
14:47 |
Sent To |
P |
|
Notes |
2020-01-31 14:48:47 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS | | AND SHOP DRAWINGS. | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-02-06 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2020-02-06 |
Time |
06:51 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2020-01-14 |
Time |
13:37 |
Sent To |
|
|
Notes |
2020-01-15 13:38:09 | ROUTED TO SHILL |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2020-02-05 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-02-05 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-02-05 |
Time |
06:45 |
Sent To |
|
|
Notes |
2020-02-05 06:54:00 | 02/05/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | [email protected] | | 561-701-6437 | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |