Plan Review Stops For Permit 20010479 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-20 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-20 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-16 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-16 |
Time |
17:25 |
Sent To |
|
|
Notes |
2020-03-16 17:53:39 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, AS THE NOTES IN THE ELECTRIC REVIEW | | COMMENTS STATE, THE PERSON RESPONSIBLE FOR THE DESIGN | | IS REQUIRED TO SIGN ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS, AND ACCOMPANYING DATA. | | PLEASE HAVE DESIGNER OF RECORD COMPLETE SIGNING AND | | SEALING ALL PAGES SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-02-06 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-02-06 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-02-06 |
Time |
17:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-03-20 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-03-20 |
Time |
15:43 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-03-16 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-03-16 |
Time |
08:38 |
Sent To |
B |
|
Notes |
2020-03-16 08:38:36 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY | | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE | | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-01-28 |
Time |
18:01 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-01-28 |
Time |
18:01 |
Sent To |
|
|
Notes |
2020-01-28 18:00:58 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY | | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE | | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-20 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-20 |
Time |
14:49 |
Sent To |
|
|
Notes |
2020-03-20 14:49:48 | RESUB ROUTED TO JPEARSON |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-16 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-10 |
Time |
13:28 |
Sent To |
|
|
Notes |
2020-03-13 16:21:41 | 3/13 ROUTED TO JPEARSON | 2020-03-11 13:29:11 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2020-01-17 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-01-14 |
Time |
13:54 |
Sent To |
|
|
Notes |
2020-01-17 14:12:43 | TO ELEC. | 2020-01-15 13:54:37 | REVISION ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-03-13 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2020-03-13 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2020-03-13 |
Time |
|
Sent To |
|
|
Notes |
2020-03-13 15:31:48 | SOUTH ELEVATION "LOADING" SIGN ONLY. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-01-16 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2020-01-16 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2020-01-16 |
Time |
|
Sent To |
|
|
Notes |
2020-01-16 10:40:45 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE SOUTH BUILDING ELEVATION DOES NOT MATCH THE | | APPROVED BUILDING ELEVATIONS/FLOOR PLANS. PLEASE | | ADDRESS WITH THE PROPER PLACEMENT OF THE PROPOSED | | SIGNAGE ON THE SOUTH BUILDING FACADE. | | | | 2.) HAS THE SIGNAGE APPROVED ON THE NORTH, EAST AND/OR | | WEST ELEVATIONS CHANGED? IF SO, ADDITIONAL INFORMATION | | WILL BE REQUIRED AS A SUPPLEMENT TO THE APPLICATION. | | | | 3.) A MINOR PD AMENDMENT TO THE EXTRA SPACE STORAGE | | PROJECT WILL BE REQUIRED IF CHANGES ARE PROPOSED TO THE | | APPROVED BUILDING ELEVATIONS/FLOOR PLANS, INCLUDING THE | | PLACEMENT OF ANY BUILDING SIGNAGE. | | | | | | NOTES: | | | | * PROPOSED SIGNAGE CLASSIFICATION: PARKING AREA | | INSTRUCTIONAL AND RELATED SIGNS (REFERENCE: ZLDR | | S.94-407) | | | | * REFERENCE: 19060909, 19081106 AND 19081112 | | | | * PALMS GATEWAY CPD | | |
|
|