2020-07-30 11:38:16 | FAILED |
| |
| ARCADE IDENTITY SIGN TYPE 1D |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. NOTE: ADDITIONAL |
| COMMENTS MAY BE ISSUED WHEN THE INFORMATION TO ADDRESS |
| THE COMMENTS BELOW IS PROVIDED. |
| |
| 1) UPDATED COMMENT: THE CURRENT ROSEMARY SQUARE TENANT |
| SIGN CRITERIA STOREFRONT TYPE 2 REQUIRES THAT THE |
| ARCADE IDENTITY SIGN IS CENTERED ON THE FACADE IN FRONT |
| OF THE TENANT'S ENTRY. THE PROPOSED SIGN IS NOT LOCATED |
| CENTERED ON THE CITY CELLAR FACADE AND NOT IN FRONT OF |
| THE CITY CELLAR ENTRY. NOTE: THE CITY IS PROCESSING AN |
| AMENDMENT TO THE SIGN CRITERIA THAT WOULD PERMIT |
| CITYPLACE RETAIL, LLC, TO GRANT A WAIVER I (WRITTEN |
| APPROVAL) TO PERMIT THE SIGN TO NOT BE CENTERED ON THE |
| ENTRY; HOWEVER, UNTIL SUCH TIME THAT THE CHANGE IS |
| APPROVED BY THE CITY COMMISSION (PUBLIC HEARING IN |
| SEPTEMBER) ZONING CANNOT REVIEW FOR COMPLIANCE WITH THE |
| NEW REQUIREMENTS. |
| |
| 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE THAT SIGNS ARE MOUNTED WITHIN THE |
| LEASE LINES. PROVIDE VERIFICATION THAT THIS LOCATION IS |
| WITHIN THE LEASE LINES. |
| |
| 3) UPDATED COMMENT: THE PROPOSED SIGN DESIGN DOES NOT |
| MATCH THE CURRENTLY PERMITTED ARCADE IDENTITY SIGN |
| OPTION C - TENANT NAME MOUNTED TO A SUSPENDED PANEL |
| THAT IS DESCRIBED IN THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA. THE CURRENT REGULATIONS DO NOT PERMIT THE |
| PAINTING OF LETTERS ON A SUSPENDED PANEL. NOTE: THE |
| CITY IS PROCESSING AN AMENDMENT TO THE SIGN CRITERIA |
| THAT WOULD PERMIT PAINTED LETTERS; HOWEVER, UNTIL SUCH |
| TIME THAT THE CHANGE IS APPROVED BY THE CITY COMMISSION |
| (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT REVIEW FOR |
| COMPLIANCE WITH THE NEW REQUIREMENTS. |
| |
| 4) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA |
| REQUIRE THAT COPY AREA BE AT LEAST 6 INCHES FROM ANY |
| EDGE OF THE PERCEIVED SIGN AREA. PROVIDE VERIFICATION |
| ON THE PLAN. NOTE: THE CITY IS PROCESSING AN AMENDMENT |
| TO THE SIGN CRITERIA THAT WOULD PERMIT THE COPY AREA TO |
| BE ONLY 3 INCHES FROM THE PERCEIVED SIGN AREA; HOWEVER, |
| UNTIL SUCH TIME THAT THE CHANGE IS APPROVED BY THE CITY |
| COMMISSION (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT |
| REVIEW FOR COMPLIANCE WITH THE NEW REQUIREMENTS. |
| |
| 5) REPEAT COMMENT: THE FULL DIMENSION OF THE SIGN IS |
| NOT PROVIDED ON THE PLANS. IN ACCORDANCE WITH THE |
| ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES THAT THE |
| SIGN AREA IS CALCULATED USING THE MAXIMUM EXTENT OF THE |
| SIGN. FOR THIS PARTICULAR SIGN IT IS THE DISTANCE FROM |
| THE LOWEST POINT OF THE BOTTOM FAUX RUSTIC THRU BOLT |
| MOUNTING HARDWARE TO THE EQUAL DISTANCE ON THE TOP AND |
| SIDE HARDWARE ATTACHMENTS. |
| |
| 6) REPEAT COMMENT: THE ROSEMARY SQUARE SIGN PLAN |
| MEASURES SIGNAGE ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT |
| OF SIGNAGE FOR EACH ONE LINEAR FOOT OF STORE FRONTAGE. |
| PLEASE PROVIDE THE LINEAR FEET OF STORE FRONTAGE. |
| |
| 7) REPEAT COMMENT: CITY CELLAR HAS EXISTING SIGNAGE ON |
| THE FACADE OF THE BUILDING. THE ROSEMARY SQUARE TENANT |
| SIGN CRITERIA PERMIT ONLY ONE PRIMARY IDENTITY SIGN PER |
| STOREFRONT. IF CITYPLACE RETAIL GRANTS A WAIVER AND |
| PERMITS MORE THAN ONE SIGN AND THE EXISTING SIGNAGE IS |
| TO REMAIN THEN THE SQUARE FOOTAGE OF THE EXISTING |
| SIGNAGE (AND AN ELEVATION DRAWING SHOWING THE SIGNAGE) |
| IS TO BE PROVIDED AND SUBTRACTED FROM THE SIGNAGE |
| ALLOWANCE. IF THE EXISTING SIGNAGE IS TO BE REMOVED |
| THEN THAT NEEDS TO BE CLARIFIED WITH THE RESUBMITTAL. |
| |
| 8) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA PERMIT A MAXIMUM LETTER HEIGHT OF 18 INCHES |
| FOR AN ARCADE IDENTITY SIGN. PROVIDE THE HEIGHT OF THE |
| LETTERS ON THE PLANS. |
| |
| 9) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE THAT ARCADE IDENTITY SIGNS HAVE A |
| MINIMUM CLEARANCE OF NINE (9) FEET FROM FINISHED FLOOR. |
| THE DRAWINGS SHOW THAT THE SIGN DOES NOT MEET THIS |
| MINIMUM CLEARANCE (ONLY 8 FEET 9 INCHES). |
| |
| 10) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST |
| BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR |
| SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO |
| THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED |
| BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD |
| WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED. |
| ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE |
| ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. |
| |
| 11) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER |
| FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE |
| FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE. |
| THE BOLT HEADS, BOLT ENDS AND NUTS THAT EXTEND PAST THE |
| MOUNTING HARDWARE DO NOT MEET THIS STANDARD. IF THE |
| BOLT HEADS MUST EXTEND PAST THE MOUNTING HARDWARE, THEY |
| NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE |
| MOUNTING HARDWARE. |
| |
| 12) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE THAT ALL BOLTS, FASTENINGS AND CLIPS |
| CONSIST OF ENAMELING IRON WITH PORCELAIN ENAMEL FINISH; |
| STAINLESS STEEL, ANODIZED ALUMINUM, BRASS OR BRONZE; OR |
| CARBON-BEARING STEEL WITH PAINTED FINISH. PROVIDE |
| VERIFICATION ON THE PLANS. |
| |
| 13) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA DO |
| NOT PERMIT EXTERNALLY ILLUMINATED ARCADE IDENTITY |
| SIGNS. NOTE: THE CITY IS PROCESSING AN AMENDMENT TO THE |
| SIGN CRITERIA THAT WOULD PERMIT EXTERNAL LIGHTING (BY |
| WRITTEN APPROVAL FROM CITYPLACE RETAIL, LLC) FOR |
| PAINTED SUSPENDED PANEL SIGNS; HOWEVER, UNTIL SUCH TIME |
| THAT THE CHANGE IS APPROVED BY THE CITY COMMISSION |
| (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT REVIEW FOR |
| COMPLIANCE WITH THE NEW REQUIREMENTS. |
| |
| 14) THE ROSEMARY SQUARE TENANT SIGN CRITERIA ALLOW A |
| MAXIMUM HEIGHT FOR ARCADE IDENTITY SIGNS OF 12 FEET |
| FROM THE FINISHED FLOOR. WHILE THE DIMENSION HAS NOT |
| BEEN PROVIDED, STAFF HAS ADDED THE DIMENSIONS THAT ARE |
| PROVIDED AND THE SIGN EXCEEDS THE 12 FOOT HEIGHT |
| ALLOWANCE. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |