Plan Review Details - Permit 20010423
Plan Review Stops For Permit 20010423
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-11-12 Cont ID  
Sent By cpuell Date 2020-11-12 Time 16:41 Rev Time 0.00
Received By cpuell Date 2020-11-12 Time 16:41 Sent To  
Notes
2020-11-12 16:41:34CITY CELLAR IS SUITE 218

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-02-05 Cont ID  
Sent By cthroop Date 2021-02-05 Time 16:50 Rev Time 0.00
Received By cthroop Date 2021-02-04 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 15:42 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 14:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By cthroop Date 2020-07-23 Time 09:37 Rev Time 0.00
Received By cthroop Date 2020-07-23 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-02-14 Cont ID  
Sent By cthroop Date 2020-02-14 Time 10:32 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 18:15 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-05-27 Cont ID  
Sent By jleahy Date 2021-05-27 Time 12:31 Rev Time 0.00
Received By jleahy Date 2021-05-27 Time 12:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-03-09 Cont ID  
Sent By jleahy Date 2021-03-09 Time 11:20 Rev Time 0.00
Received By jleahy Date 2021-03-09 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 09:27 Rev Time 0.00
Received By jleahy Date 2020-12-04 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By fgiaquin Date 2020-07-17 Time 23:07 Rev Time 0.00
Received By fgiaquin Date 2020-07-17 Time 21:55 Sent To  
Notes
2020-07-17 23:07:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER LAST PLAN REVIEW COMMENTS. ELECTRICAL WORK SHOWN
 ON PLAN (LIGHTS TO LIGHT SIGN) IS OUT OF SCOPE OF WORK
 FOR ES LICENSE. NEED EC OR ER REGISTERED TO PALM BEACH
 COUNTY TO PULL SEPARATE ELECTRICAL PERMIT FOR LIGHTING.
 PLEASE REFERENCE ELECTRICAL PERMIT NUMBER FROM EC OR ER
 WHEN RESUBMITTING AND PROVIDE A REPONSE LETTER IN THE
 SUPPORTING DOCUMENTS SECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By jleahy Date 2020-01-31 Time 11:28 Rev Time 0.00
Received By jleahy Date 2020-01-31 Time 11:28 Sent To  
Notes
2020-01-31 11:31:42FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC TO THIS SIGN.
  
 ELECTRICAL WORK FOR THIS SIGN IS OUT OF THE SCOPE OF
 THIS CONTRACTORS LICENSE.
  
 SEPARATE PERMIT REQUIRED FROM AN EC OR ER LICENSED
 CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-08-17 Cont ID  
Sent By lmarchan Date 2021-08-17 Time 15:59 Rev Time 0.00
Received By lmarchan Date 2021-07-08 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-06-03 Cont ID  
Sent By lmarchan Date 2021-06-03 Time 15:01 Rev Time 0.00
Received By lmarchan Date 2021-05-17 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-03-31 Cont ID  
Sent By equinone Date 2021-03-31 Time 08:53 Rev Time 0.00
Received By equinone Date 2021-03-03 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-02-08 Cont ID  
Sent By shill Date 2021-02-08 Time 16:28 Rev Time 0.00
Received By shill Date 2021-01-22 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 09:27 Rev Time 0.00
Received By jleahy Date 2020-11-12 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By ccarvaja Date 2020-07-30 Time 17:54 Rev Time 0.00
Received By ccarvaja Date 2020-07-01 Time 16:01 Sent To  
Notes
2020-07-09 16:02:05CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-14 Cont ID  
Sent By cthroop Date 2020-02-14 Time 10:32 Rev Time 0.00
Received By cthroop Date 2020-01-13 Time 13:13 Sent To  
Notes
2020-01-30 07:09:18ROUTED TO ELECTRICAL BOX
2020-01-14 13:13:34ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 18:18 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 18:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-03-31 Cont ID  
Sent By equinone Date 2021-03-31 Time 08:56 Rev Time 0.00
Received By equinone Date 2021-03-31 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-04 Cont ID  
Sent By cthroop Date 2021-02-04 Time 16:32 Rev Time 0.00
Received By cthroop Date 2021-02-04 Time 16:28 Sent To  
Notes
2021-02-04 16:33:06SEE SIGNATURE REVIEW #1. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 15:07 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 15:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-09 Cont ID  
Sent By jgomez Date 2020-07-09 Time 15:44 Rev Time 0.00
Received By jgomez Date 2020-07-09 Time 15:44 Sent To  
Notes
2020-07-09 15:44:52CONVERTED TO DIGITAL.
 DRAWINGS/CALCULATIONS WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE IN CITY'S FILE. JG
  

Review Stop Z ZONING
Rev No 7 Status P Date 2021-08-17 Cont ID  
Sent By eschneid Date 2021-08-17 Time 14:58 Rev Time 0.25
Received By eschneid Date 2021-08-16 Time 15:41 Sent To  
Notes
2021-08-17 14:58:51ARCADE IDENTITY SIGN TYPE 1D
  
 PERMITTED: 97.5 SF
 EXISTING AWING SIGNS (3): 6.03 SF
 APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF
 PROPOSED SIGN: 23 SF
  
 TOTAL SIGN AREA: 45.83 SF
  

Review Stop Z ZONING
Rev No 6 Status F Date 2021-06-03 Cont ID  
Sent By eschneid Date 2021-06-03 Time 14:43 Rev Time 0.25
Received By eschneid Date 2021-05-27 Time 13:42 Sent To  
Notes
2021-06-03 14:41:59FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 ARCADE IDENTITY SIGN TYPE 1D
  
 PERMITTED: 97.5 SF
 EXISTING AWING SIGNS (3): 6.03 SF
 APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF
 PROPOSED SIGN: 23 SF
  
 TOTAL SIGN AREA: 45.83 SF
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE ALL
 LIGHTING CONDUIT, WIRING, BALLAST BOXES, TRANSFORMERS,
 AND OTHER EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL
 BE CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE HAND
 DRAWING FROM THE ELECTRICAL CONTRA VERIFIES THAT THERE
 WILL BE A BELL BOX WITH DISCONNECT SWITCH AND
 ELECTRICAL LEAD WITHIN FLEXIBLE CONDUIT TO AN EXISTING
 LIGHTING J BOX. THE ELECTRICIAN ADDED THE NOTE THAT THE
 COVER WILL BE DONE BY OTHERS. UNTIL A PLAN IS SUBMITTED
 SHOWING AND DETAILING EXACTLY HOW THE COVER TO CONCEAL
 THE ELECTRICAL CONNECTIONS TO THIS ILLUMINATED SIGN,
 ZONING WILL NOT APPROVE THIS PERMIT AS ALL OF THE
 REQUIREMENTS OF THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA HAVE NOT BEEN MET.
  
 2) ALTERNATIVELY YOU MAY REMOVE ALL REFERENCE TO
 ILLUMINATION AND ELECTRIC, TO INCLUDE THE "SATIN BLACK
 DIRECTIONAL BULLET SIGN LIGHTS" AND THE MOUNTING ARMS,
 FROM THE PLANS INCLUDED WITH THE SIGN PERMIT. THESE
 WILL THEN ALL NEED TO BE SHOWN IN DETAIL ON THE PLANS
 WITH THE ELECTRIC PERMIT, THAT INCLUDES CONCEALMENT. IF
 THE ELECTRIC PERMIT DOES NOT PASS, YOU WILL NOT BE
 PERMITTED TO INSTALL THE BULLET SIGN LIGHT.
  
 NOTE: THE SIGN WITH NO ELECTRIC DOES MEET THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA.
  
 I HAVE SEPARATELY CONTACTED THE ROSEMARY SQUARE
 MANAGEMENT REGARDING THE STATUS OF THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected].
  

Review Stop Z ZONING
Rev No 5 Status F Date 2021-03-30 Cont ID  
Sent By eschneid Date 2021-03-30 Time 13:11 Rev Time 0.50
Received By eschneid Date 2021-03-30 Time 11:33 Sent To  
Notes
2021-03-30 13:12:58FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 ARCADE IDENTITY SIGN TYPE 1D
  
 PERMITTED: 97.5 SF
 EXISTING AWING SIGNS (3): 6.03 SF
 APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF
 PROPOSED SIGN: 23 SF
  
 TOTAL SIGN AREA: 45.83 SF
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST
 BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR
 SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO
 THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED
 BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD
 WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED.
 ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE
 ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE
 SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN
 ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE
 CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO
 DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN
 REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT
 REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE
 THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE
 TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE
 PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE
 "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND
 PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT
 THE CONCEALMENT REQUIREMENTS ARE MET. THE PERMIT NUMBER
 CITED (20061298) IN THE RESPONSE DOES NOT SHOW ANY
 ELECTRICAL CONNECTION TO THE PROPOSED LOCATION OF THIS
 SIGN. YOU ARE REQUIRED TO SHOW HOW THE ELECTRICAL TO
 THE LIGHTING FOR THIS SIGN COMPLIES WITH THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA. ***** THE RESPONSE STATES
 THAT THE SIGN PERMIT WILL NOT BE DOING ELECTRICAL WORK
 AND THAT NO ELECTRICAL PERMIT WAS PULLED; HOWEVER, YOU
 DID SUBMIT AN ELECTRICAL SUB PERMIT FOR THIS
 INSTALLATION (PERMIT NUMBER 20010423). SINCE YOU HAVE
 SUBMITTED AN ELECTRICAL SUB PERMIT FOR YOUR SIGN THAT
 PROPOSES ELECTRIC, IN ACCORDANCE WITH THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA YOU NEED TO PROVIDE
 DRAWINGS SHOWING THAT THE ELECTRIC MEETS THE REQUIRED
 STANDARDS (AS REPEATED ON EACH PERMIT REVIEW). YOUR
 OTHER OPTION IS TO REMOVE ALL REFERENCE TO ILLUMINATION
 AND ELECTRIC, TO INCLUDE THE "SATIN BLACK DIRECTIONAL
 BULLET SIGN LIGHTS" AND THE MOUNTING ARMS, FROM THE
 SIGN PERMIT. THESE WILL THEN ALL NEED TO BE SHOWN IN
 DETAIL ON THE ELECTRIC PERMIT. IF THE ELECTRIC PERMIT
 DOES NOT PASS, YOU WILL NOT BE PERMITTED TO INSTALL THE
 BULLET SIGN LIGHT.
  
 NOTE: THE SIGN WITH NO ELECTRIC DOES MEET THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected].
  

Review Stop Z ZONING
Rev No 4 Status F Date 2021-02-08 Cont ID  
Sent By eschneid Date 2021-02-08 Time 15:40 Rev Time 0.50
Received By eschneid Date 2021-02-08 Time 08:54 Sent To  
Notes
2021-02-08 15:40:03FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 ARCADE IDENTITY SIGN TYPE 1D
  
 PERMITTED: 97.5 SF
 EXISTING AWING SIGNS (3): 6.03 SF
 APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF
 PROPOSED SIGN: 23 SF
  
 TOTAL SIGN AREA: 45.83 SF
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST
 BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR
 SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO
 THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED
 BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD
 WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED.
 ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE
 ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE
 SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN
 ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE
 CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO
 DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN
 REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT
 REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE
 THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE
 TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE
 PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE
 "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND
 PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT
 THE CONCEALMENT REQUIREMENTS ARE MET. ***** THE PERMIT
 NUMBER CITED (20061298) IN THE RESPONSE NOT SHOW ANY
 ELECTRICAL CONNECTION TO THE PROPOSED LOCATION OF THIS
 SIGN. YOU ARE REQUIRED TO SHOW HOW THE ELECTRICAL TO
 THE LIGHTING FOR THIS SIGN COMPLIES WITH THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA ALLOW A MAXIMUM HEIGHT FOR ARCADE IDENTITY
 SIGNS OF 12 FEET FROM THE FINISHED FLOOR. THE SIGN
 EXCEEDS THE 12 FOOT HEIGHT ALLOWANCE. 9 FEET + 4 FEET 8
 INCHES = 13 FEET 8 INCHES. THE RESPONSE MENTIONS THAT A
 WAIVER HAS BEEN SUBMITTED TO ALLOW WHAT IS AN
 ALTERNATIVE VERTICAL PLACEMENT OF A PERMITTED SIGN
 (WAIVER I); HOWEVER, THE PERMIT RESUBMITTAL DOES NOT
 INCLUDE THIS WAIVER I.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected].
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-12-02 Cont ID  
Sent By eschneid Date 2020-12-02 Time 14:53 Rev Time 0.75
Received By eschneid Date 2020-12-02 Time 11:03 Sent To  
Notes
2020-12-02 14:56:13FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 ARCADE IDENTITY SIGN TYPE 1D
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT C.1
 PAINTED SIGN PANELS AND C.2 SIGNAGE ON THE FRONT AND
 BACK OF A SUSPENDED PANEL ON A CASE BY CASE BASIS.
 APPROVAL OF CASE BY CASE SIGN OPTIONS MAY BE APPROVED
 BY CITYPLACE RETAIL AS A WAIVER I. PLEASE PROVIDE AN
 UPDATED WAIVER I APPROVAL LETTER (OR ADDITIONAL LETTER)
 THAT APPROVES THE TWO REQUESTED WAIVERS I.
  
 2) THE ROSEMARY SQUARE SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE BASED ON THE
 LEASE LINE DRAWING PROVIDED WITH THE RESUBMITTAL. THE
 TOTAL AMOUNT OF SIGNAGE PERMITTED ON THIS FACADE IS
 97.5 SQUARE FEET. CITY CELLAR HAS EXISTING SIGNAGE ON
 THE FACADE OF THE BUILDING AND THE AWNING VALANCES
 WHICH COUNT TOWARD THE MAXIMUM PERMITTED SIGN SQUARE
 FOOTAGE. PLEASE CLARIFY IF THE SIGNAGE WILL REMAIN
 AFTER THE INSTALLATION OF THE PROPOSED ARCADE IDENTITY
 SIGN.
  
 A. THE CITY CELLAR FAADE SIGN IS 49.5 SQUARE FEET
 (BASED ON APPROVED PERMIT). IF THE FASCIA SIGN WILL
 REMAIN, THEN ITS SQUARE FOOTAGE WILL BE DEDUCTED FROM
 THE PERMITTED SIGNAGE AMOUNT.
  
 B. STAFF WAS UNABLE TO LOCATE THE SQUARE FOOTAGE OF THE
 SIGNAGE ON THE THREE AWNINGS. IF THE AWNING SIGNS ARE
 TO REMAIN, THEN YOU MUST PROVIDE THE TOTAL SQUARE
 FOOTAGE OF THESE THREE AWNING SIGNS AND IT WILL BE
 DEDUCTED FROM THE PERMITTED SIGNAGE AMOUNT.
  
 C. BARRIO SANGRIA HAS A PERMITTED 16.8 SQUARE FOOT SIGN
 WHICH HAS NOT YET BEEN INSTALLED. SINCE THE SIGN FALLS
 WITHIN THE STORE FRONTAGE, IT IS COUNTED TOWARD THE
 TOTAL PERMITTED SIGNAGE
  
 D. THE TABLE BELOW PROVIDES THE SIGNAGE PERMITTED AND
 THE AMOUNT OF SIGNAGE THAT STAFF CAN ACCOUNT FOR. IF NO
 SIGNAGE IS TO BE REMOVED, THEN IF THE AWNING SIGNAGE
 EXCEEDS 8.2 SQUARE FEET, THE PROPOSED ARCADE IDENTITY
 SIGN WILL NEED TO BE REDUCED IN SIZE.
  
 PERMITTED: 97.5 SF
 EXISTING CITY CELLAR FASCIA SIGN: 49.5 SF
 EXISTING AWING SIGNS: ??? SF
 APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF
 PROPOSED SIGN: 23 SF
  
 TOTAL SIGN AREA: UNKNOWN; EXCLUDING AWNING SQUARE
 FOOTAGE 89.3 SF
  
 3) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST
 BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR
 SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO
 THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED
 BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD
 WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED.
 ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE
 ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE
 SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN
 ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE
 CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO
 DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN
 REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT
 REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE
 THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE
 TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE
 PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE
 "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND
 PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT
 THE CONCEALMENT REQUIREMENTS ARE MET.
  
 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER
 FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE
 FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE.
 THE BOLT HEADS, BOLT ENDS AND NUTS THAT EXTEND PAST THE
 MOUNTING HARDWARE DO NOT MEET THIS STANDARD. IF THE
 BOLT HEADS MUST EXTEND PAST THE MOUNTING HARDWARE, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING HARDWARE.
  
 5) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA ALLOW A MAXIMUM HEIGHT FOR ARCADE IDENTITY
 SIGNS OF 12 FEET FROM THE FINISHED FLOOR. THE SIGN
 EXCEEDS THE 12 FOOT HEIGHT ALLOWANCE. 9 FEET + 4 FEET 8
 INCHES = 13 FEET 8 INCHES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-30 Cont ID  
Sent By eschneid Date 2020-07-30 Time 11:38 Rev Time 0.75
Received By eschneid Date 2020-07-30 Time 09:55 Sent To  
Notes
2020-07-30 11:38:16FAILED
  
 ARCADE IDENTITY SIGN TYPE 1D
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS. NOTE: ADDITIONAL
 COMMENTS MAY BE ISSUED WHEN THE INFORMATION TO ADDRESS
 THE COMMENTS BELOW IS PROVIDED.
  
 1) UPDATED COMMENT: THE CURRENT ROSEMARY SQUARE TENANT
 SIGN CRITERIA STOREFRONT TYPE 2 REQUIRES THAT THE
 ARCADE IDENTITY SIGN IS CENTERED ON THE FACADE IN FRONT
 OF THE TENANT'S ENTRY. THE PROPOSED SIGN IS NOT LOCATED
 CENTERED ON THE CITY CELLAR FACADE AND NOT IN FRONT OF
 THE CITY CELLAR ENTRY. NOTE: THE CITY IS PROCESSING AN
 AMENDMENT TO THE SIGN CRITERIA THAT WOULD PERMIT
 CITYPLACE RETAIL, LLC, TO GRANT A WAIVER I (WRITTEN
 APPROVAL) TO PERMIT THE SIGN TO NOT BE CENTERED ON THE
 ENTRY; HOWEVER, UNTIL SUCH TIME THAT THE CHANGE IS
 APPROVED BY THE CITY COMMISSION (PUBLIC HEARING IN
 SEPTEMBER) ZONING CANNOT REVIEW FOR COMPLIANCE WITH THE
 NEW REQUIREMENTS.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT SIGNS ARE MOUNTED WITHIN THE
 LEASE LINES. PROVIDE VERIFICATION THAT THIS LOCATION IS
 WITHIN THE LEASE LINES.
  
 3) UPDATED COMMENT: THE PROPOSED SIGN DESIGN DOES NOT
 MATCH THE CURRENTLY PERMITTED ARCADE IDENTITY SIGN
 OPTION C - TENANT NAME MOUNTED TO A SUSPENDED PANEL
 THAT IS DESCRIBED IN THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA. THE CURRENT REGULATIONS DO NOT PERMIT THE
 PAINTING OF LETTERS ON A SUSPENDED PANEL. NOTE: THE
 CITY IS PROCESSING AN AMENDMENT TO THE SIGN CRITERIA
 THAT WOULD PERMIT PAINTED LETTERS; HOWEVER, UNTIL SUCH
 TIME THAT THE CHANGE IS APPROVED BY THE CITY COMMISSION
 (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT REVIEW FOR
 COMPLIANCE WITH THE NEW REQUIREMENTS.
  
 4) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA
 REQUIRE THAT COPY AREA BE AT LEAST 6 INCHES FROM ANY
 EDGE OF THE PERCEIVED SIGN AREA. PROVIDE VERIFICATION
 ON THE PLAN. NOTE: THE CITY IS PROCESSING AN AMENDMENT
 TO THE SIGN CRITERIA THAT WOULD PERMIT THE COPY AREA TO
 BE ONLY 3 INCHES FROM THE PERCEIVED SIGN AREA; HOWEVER,
 UNTIL SUCH TIME THAT THE CHANGE IS APPROVED BY THE CITY
 COMMISSION (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT
 REVIEW FOR COMPLIANCE WITH THE NEW REQUIREMENTS.
  
 5) REPEAT COMMENT: THE FULL DIMENSION OF THE SIGN IS
 NOT PROVIDED ON THE PLANS. IN ACCORDANCE WITH THE
 ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES THAT THE
 SIGN AREA IS CALCULATED USING THE MAXIMUM EXTENT OF THE
 SIGN. FOR THIS PARTICULAR SIGN IT IS THE DISTANCE FROM
 THE LOWEST POINT OF THE BOTTOM FAUX RUSTIC THRU BOLT
 MOUNTING HARDWARE TO THE EQUAL DISTANCE ON THE TOP AND
 SIDE HARDWARE ATTACHMENTS.
  
 6) REPEAT COMMENT: THE ROSEMARY SQUARE SIGN PLAN
 MEASURES SIGNAGE ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT
 OF SIGNAGE FOR EACH ONE LINEAR FOOT OF STORE FRONTAGE.
 PLEASE PROVIDE THE LINEAR FEET OF STORE FRONTAGE.
  
 7) REPEAT COMMENT: CITY CELLAR HAS EXISTING SIGNAGE ON
 THE FACADE OF THE BUILDING. THE ROSEMARY SQUARE TENANT
 SIGN CRITERIA PERMIT ONLY ONE PRIMARY IDENTITY SIGN PER
 STOREFRONT. IF CITYPLACE RETAIL GRANTS A WAIVER AND
 PERMITS MORE THAN ONE SIGN AND THE EXISTING SIGNAGE IS
 TO REMAIN THEN THE SQUARE FOOTAGE OF THE EXISTING
 SIGNAGE (AND AN ELEVATION DRAWING SHOWING THE SIGNAGE)
 IS TO BE PROVIDED AND SUBTRACTED FROM THE SIGNAGE
 ALLOWANCE. IF THE EXISTING SIGNAGE IS TO BE REMOVED
 THEN THAT NEEDS TO BE CLARIFIED WITH THE RESUBMITTAL.
  
 8) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT A MAXIMUM LETTER HEIGHT OF 18 INCHES
 FOR AN ARCADE IDENTITY SIGN. PROVIDE THE HEIGHT OF THE
 LETTERS ON THE PLANS.
  
 9) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT ARCADE IDENTITY SIGNS HAVE A
 MINIMUM CLEARANCE OF NINE (9) FEET FROM FINISHED FLOOR.
 THE DRAWINGS SHOW THAT THE SIGN DOES NOT MEET THIS
 MINIMUM CLEARANCE (ONLY 8 FEET 9 INCHES).
  
 10) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST
 BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR
 SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO
 THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED
 BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD
 WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED.
 ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE
 ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX.
  
 11) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER
 FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE
 FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE.
 THE BOLT HEADS, BOLT ENDS AND NUTS THAT EXTEND PAST THE
 MOUNTING HARDWARE DO NOT MEET THIS STANDARD. IF THE
 BOLT HEADS MUST EXTEND PAST THE MOUNTING HARDWARE, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING HARDWARE.
  
 12) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT ALL BOLTS, FASTENINGS AND CLIPS
 CONSIST OF ENAMELING IRON WITH PORCELAIN ENAMEL FINISH;
 STAINLESS STEEL, ANODIZED ALUMINUM, BRASS OR BRONZE; OR
 CARBON-BEARING STEEL WITH PAINTED FINISH. PROVIDE
 VERIFICATION ON THE PLANS.
  
 13) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA DO
 NOT PERMIT EXTERNALLY ILLUMINATED ARCADE IDENTITY
 SIGNS. NOTE: THE CITY IS PROCESSING AN AMENDMENT TO THE
 SIGN CRITERIA THAT WOULD PERMIT EXTERNAL LIGHTING (BY
 WRITTEN APPROVAL FROM CITYPLACE RETAIL, LLC) FOR
 PAINTED SUSPENDED PANEL SIGNS; HOWEVER, UNTIL SUCH TIME
 THAT THE CHANGE IS APPROVED BY THE CITY COMMISSION
 (PUBLIC HEARING IN SEPTEMBER) ZONING CANNOT REVIEW FOR
 COMPLIANCE WITH THE NEW REQUIREMENTS.
  
 14) THE ROSEMARY SQUARE TENANT SIGN CRITERIA ALLOW A
 MAXIMUM HEIGHT FOR ARCADE IDENTITY SIGNS OF 12 FEET
 FROM THE FINISHED FLOOR. WHILE THE DIMENSION HAS NOT
 BEEN PROVIDED, STAFF HAS ADDED THE DIMENSIONS THAT ARE
 PROVIDED AND THE SIGN EXCEEDS THE 12 FOOT HEIGHT
 ALLOWANCE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By eschneid Date 2020-01-29 Time 16:04 Rev Time 0.75
Received By eschneid Date 2020-01-29 Time 09:50 Sent To PC
Notes
2020-01-29 16:13:50FAILED
 1/30/20 COMMENT UPDATE
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA STOREFRONT
 TYPE 2 REQUIRES THAT THE ARCADE IDENTITY SIGN IS
 CENTERED ON THE FACADE IN FRONT OF THE TENANT'S ENTRY.
 THE PROPOSED SIGN IS NOT LOCATED CENTERED ON THE CITY
 CENTER FACADE AND NOT IN FRONT OF THE CITY CELLAR
 ENTRY.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT SIGNS ARE MOUNTED WITHIN THE LEASE LINES. PROVIDE
 VERIFICATION THAT THIS LOCATION IS WITHIN THE LEASE
 LINES.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA DO NOT
 PERMIT THE PAINTING OF LETTERS TO A SUSPENDED PANEL,
 BUT RATHER REQUIRE THE TENANT NAME BE MOUNTED TO THE
 SUSPENDED PANEL. THE LETTERS ARE TO BE FABRICATED OUT
 OF ALUMINUM WITH A MINIMUM METAL THICKNESS OF 0.06
 INCHES WITH A PAINTED FINISH (IF CHANNEL LETTERS USED
 THE CHANNEL DEPTH MAY BE NO MORE THEN THREE INCHES).
 THE PAINTED WALL SIGN OPTION IS ONLY PERMITTED ON SOLID
 AREAS OF A FACADE SUCH AS STUCCO, WOOD OR BRICK PANELS
 (THIS WOULD BE A FASCIA IDENTITY SIGN NOT AN ARCADE
 IDENTITY SIGN AS PROPOSED).
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT UP
 TO THREE COLORS ON A SIGN. PROVIDE ON THE PLANS
 VERIFICATION OF THE COLORS USED ON THE SIGN. THE SIGN
 PANEL (WHITE) AND THE TUBE FRAME SUPPORTS (BLACK) AND
 ROLLED DECORATIVE RING (BLACK) ARE TWO COLORS. PROVIDE
 THE COLOR FOR THE ROLLED ALUMINUM MOUNTING PLATE AND
 THE FINAL LETTER MATERIAL (THE NOT PERMITTED PAINTED
 OPTION APPEARS TO HAVE MULTIPLE COLORS TO ACHIEVE THE
 SHADING EFFECT WHICH MAY NO LONGER BE NECESSARY WITH
 FABRICATED LETTERS).
  
 5) THE FULL DIMENSION OF THE SIGN IS NOT PROVIDED ON
 THE PLANS. IN ACCORDANCE WITH THE ROSEMARY SQUARE
 TENANT SIGN CRITERIA REQUIRES THAT THE SIGN AREA IS
 CALCULATED USING THE MAXIMUM EXTENT OF THE SIGN. FOR
 THIS PARTICULAR SIGN IT IS THE DISTANCE FROM THE LOWEST
 POINT OF THE BOTTOM FAUX RUSTIC THRU BOLT MOUNTING
 HARDWARE TO THE EQUAL DISTANCE ON THE TOP AND SIDE
 HARDWARE ATTACHMENTS.
  
 6) THE ROSEMARY SQUARE SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE
 THE LINEAR FEET OF STORE FRONTAGE.
  
 7) CITY CELLAR HAS EXISTING SIGNAGE ON THE FACADE OF
 THE BUILDING. THE ROSEMARY SQUARE TENANT SIGN CRITERIA
 PERMIT ONLY ONE PRIMARY IDENTITY SIGN PER STOREFRONT.
 IF CITYPLACE RETAIL GRANTS A WAIVER AND PERMITS MORE
 THAN ONE SIGN AND THE EXISTING SIGNAGE IS TO REMAIN
 THEN THE SQUARE FOOTAGE OF THE EXISTING SIGNAGE (AND A
 ELEVATION DRAWING SHOWING THE SIGNAGE) IS TO BE
 PROVIDED AND SUBTRACTED FROM THE SIGNAGE ALLOWANCE. IF
 THE EXISTING SIGNAGE IS TO BE REMOVED THEN A PERMIT FOR
 THE REMOVAL NEEDS TO BE SUBMITTED.
  
 8) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 MAXIMUM LETTER HEIGHT OF 18 INCHES FOR AN ARCADE
 IDENTITY SIGN. PROVIDE THE HEIGHT OF THE LETTERS ON THE
 PLANS.
  
 9) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT ARCADE IDENTITY SIGNS HAVE A MINIMUM CLEARANCE OF
 NINE (9) FEET FROM FINISHED GRADE. THE DRAWINGS SHOW
 THAT THE SIGN DOES NOT MEET THIS MINIMUM CLEARANCE (8
 FEET 9 INCHES).
  
 10) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 ALL LIGHTING CONDUIT, WIRING, BALLAST BOXES,
 TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR SIGN
 CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO THE
 PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED BELL
 BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD WITHIN
 FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED. ADDITIONALLY,
 NO INFORMATION IS PROVIDED AS TO HOW THE ELECTRIC
 SERVICE IS PROVIDED TO THE BELL BOX.
  
 11) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. THE BOLT HEADS, BOLT ENDS AND
 NUTS THAT EXTEND PAST THE MOUNTING HARDWARE DO NOT MEET
 THIS STANDARD. IF THE BOLT HEADS MUST EXTEND PAST THE
 MOUNTING HARDWARE, THEY NEED TO BE CONCEALED BY CAPS
 MATCHING THE COLOR OF THE MOUNTING HARDWARE.
  
 12) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT ALL BOLTS, FASTENINGS AND CLIPS CONSIST OF
 ENAMELING IRON WITH PORCELAIN ENAMEL FINISH; STAINLESS
 STEEL, ANODIZED ALUMINUM, BRASS OR BRONZE; OR
 CARBON-BEARING STEEL WITH PAINTED FINISH. PROVIDE
 VERIFICATION ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  