Plan Review Details - Permit 20010341
Plan Review Stops For Permit 20010341
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-04-09 Cont ID  
Sent By jpearson Date 2020-04-09 Time 12:38 Rev Time 0.00
Received By jpearson Date 2020-04-09 Time 11:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 09:46 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 09:46 Sent To I
Notes
2020-03-24 09:46:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL SIGNATURE ON
 PAPER PLANS IS NOT ACCEPTABLE. PROVIDE CORRECTION. WPB
 FBC 107.1; FS 471/481
  
 FOR RESUBMITTAL:
  
 PLEASE PAY YOUR BALANCE DUE ONLINE SO YOUR PERMIT CAN
 BE EMAILED TO YOU.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), OR IF THE DESIGN
 PROFESSIONAL HAS A DIGITAL SIGNATURE, AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By fgiaquin Date 2020-01-30 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2020-01-30 Time 06:21 Sent To I
Notes
2020-01-30 06:47:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.5. PROVIDE CORRECTION.
  
 2. PROVIDE ELECTRICAL DRAWING SHOWING CONDUIT, WIRE
 SIZE, CIRCUIT NUMBER AND PANEL WHERE CIRCUIT IS FED
 FROM. FBC 107.2.1
  
 3. THE VALUE FOR SITE LIGHTING IS NOT TO BE INCLUDED IN
 THE MAIN PERMIT REVIEW. PLEASE CONTACT SAMANTHA HILL
 (CHIEF PLANS EXAMINER) @ [email protected] WITH A COPY OF
 THE ELECTRICIAN'S CONTRACT AND THE GENERAL CONTRACTOR'S
 CONTRACT TO VERIFY THE PROPER FEES HAVE BEEN COLLECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-10 Cont ID  
Sent By lmarchan Date 2020-04-10 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2020-04-09 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-13 Time 16:23 Sent To  
Notes
2020-03-21 14:57:53TO JP DESK
  
2020-03-13 16:23:20RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By fgiaquin Date 2020-01-30 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2020-01-09 Time 13:11 Sent To  
Notes
2020-01-28 09:00:41ROUTED TO ELEC BOX
2020-01-10 13:11:56ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-09 Cont ID  
Sent By shill Date 2020-04-09 Time 12:39 Rev Time 0.00
Received By jpearson Date 2020-04-09 Time 10:37 Sent To  
Notes
2020-04-09 10:38:16PAPER ORIGINALS RECEIVED
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-10 Cont ID  
Sent By eschneid Date 2020-04-10 Time 08:50 Rev Time 0.00
Received By eschneid Date 2020-04-10 Time 08:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By eschneid Date 2020-03-19 Time 16:47 Rev Time 0.25
Received By eschneid Date 2020-03-19 Time 16:47 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By eschneid Date 2020-01-27 Time 14:49 Rev Time 0.50
Received By eschneid Date 2020-01-27 Time 14:36 Sent To PC
Notes
2020-01-27 14:49:00FAILED
  
 1) THE LIGHT POLE LOCATIONS DO NOT FULLY MATCH THE
 LOCATIONS SHOWN ON EITHER THE ORIGINALLY APPROVED SITE
 PLAN OR THE RECENTLY SUBMITTED "AS BUILT" SITE PLAN.
  
 2) THE LIGHT POLES ARE REQUIRED TO MEET THE FIVE (5)
 FOOT SETBACK. THIS NEEDS TO BE CLEARLY SHOWN ON THE
 NORTH PROPERTY LINE. IT APPEARS THAT ALL OF THE LIGHT
 POLES ENCROACH INTO THE SETBACK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]