2020-01-09 09:11:02 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- BORAL ROOF TILE NOA 18-0509.16 SUBMITTED DOESN'T |
| LIST THE 3M FOAM NOA 15-1201.04 SUBMITTED. THERE IS NO |
| WAY TO FIND THE UPLIFT RESISTANCE OF THE FOAM ADHESIVE |
| SUBMITTED BECAUSE NEITHER THE ROOF TILE NOA NOR THE |
| FOAM ADHESIVE NOA SUBMITTED SHOW THE UPLIFT RESISTANCE. |
| . NEED THIS TO TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED OR |
| PROVIDE COMPLETE INFORMATION FROM 3M ADHESIVE |
| MANUFACTURER FOR BUILDING OFFICIAL APPROVAL. |
| SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20.3001. |
| |
| 2- ROOF TILE NOA AND ROOF TILE ADHESIVE NOA SUBMITTED: |
| CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 3- POLYGLASS UNDERPAYMENT NOA 17-0614.22 SUBMITTED. |
| CLEARLY SPECIFY WHICH OF THE UNDERLAYMENTS LISTED IN |
| THE NOA IS GOING TO BE USED AS REQUIRED BY CITY POLICY |
| FOR ALL ROOFING PERMITS TO VERIFY THAT PROPOSED |
| UNDERLAYMENT IS OK TO BE USED ON FOAM ADHESIVE |
| INSTALLATIONS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |