Plan Review Details - Permit 20010255
Plan Review Stops For Permit 20010255
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By rmcdouga Date 2020-02-26 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2020-02-26 Time 07:19 Sent To FIRE
Notes
2020-02-26 07:42:48PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS MEMBRANE STRUCTURE WILL BE ATTACHED TO AND A
 PART OF A BUILDING THAT IS OF TYPE IIB CONSTRUCTION AND
 IS FULLY SPRINKLERED. ACCORDING TO FBC 3102.3,
 NON-COMBUSTIBLE FRAME STRUCTURES COVERED BY AN APPROVED
 MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1 SHALL BE
 CLASSIFIED AS TYPE IIB CONSTRUCTION. THERE IS AN EXIT
 PATH OF TRAVEL PASSES THROUGH THIS MEMBRANE STRUCTURE
 WHICH CONTAINS TABLES AND CHAIRS AND IS A PART OF THE
 RESTAURANT. FBC SECTION 903.2.1.2 REQUIRES THIS PORTION
 OF THE BUILDING TO BE FIRE SPRINKLERED. SUBMIT PLANS
 THAT SHOW COMPLIANCE.
  
 2) THE PLANS INDICATE THAT THE STEEL TRUSSES WILL BE
 ATTACHED TO WOOD BACKING OR OTHER. IF WOOD BACKING IS
 USED IT IS REQUIRED TO BE FIRE-RETARDANT-TREATED PER
 FBC 603.1.
  
 3) THE PLANS STATE THAT THE FABRIC COVERS ARE REQUIRED
 TO BE REMOVED WHEN WINDSPEEDS ARE EXPECTED TO EXCEED 75
 MPH. SPECIFY WHO WILL BE RESPONSIBLE FOR REMOVING THE
 FABRIC COVERS. SUBMIT TWO SETS OF DETAILED AWNING
 REMOVAL INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT
 SHOW HOW THIS IS DONE IN TERMS THAT A LAYMAN WILL
 UNDERSTAND. THESE INSTRUCTIONS ARE TO BE PROVIDED TO
 THE PROPERTY OWNER, OWNER'S REPRESENTATIVE OR LESSEE.
 FBC 107.2.1
  
 4) THE PLANS SHOW FABRIC ROLL UP SIDE PANELS. WILL
 THESE PANELS BE ROLLED UP AND REMAIN IN PLAN ON THE
 STRUCTURAL FRAME DURING PERIODS OF HIGH WINDS? IF SO
 WAS THIS CONSIDERED BY THE ENGINEER WHEN THE WINDLOAD
 ANALYSIS WAS PREFORMED? FBC 107.2.1
  
 5) SEPARATE PERMITS WILL BE REQUIRED FOR THE FIRE
 SPRINKLERS AND THE ELECTRICAL WORK. FBC 105
  
 6) THE PLANS FOR THE RESTAURANT BUILD OUT, PERMIT #
 19110659, STATE THAT THE EXTERIOR CANOPY WILL BE
 DESIGNED BY A DELEGATE ENGINEER. THE PLANS ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
 A SHOP DRAWING REVIEW STAMP IS REQUIRED ON THE PLANS.
 FAC 61G15-31.001
  
 7) SINCE THE MEMBRANE STRUCTURE IS STRUCTURALLY
 ATTACHED TO THE EXISTING BUILDING. THE EXISTING
 STRUCTURE NEEDS TO BE EVALUATED TO DETERMINE IF THE
 ADDITIONAL LOADS ( WINDLOADS, ETC.) FROM THE MEMBRANE
 STRUCTURE WILL HAVE A NEGATIVE AFFECT ON IT. FBC 1604
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By cthroop Date 2020-01-22 Time 13:25 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:01 Sent To  
Notes
2020-01-22 13:28:54PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STRUCTURAL DESIGN SHALL BE SIGNED AND SEALED BY A
 REGISTERED DESIGN PROFESSIONAL.
  
 2. PLAN INDICATES THERE IS A PAGE 2 OF 2 FOR CURTAIN
 WALLS. PROVIDE PAGE 2 OF 2 IF CURTAIN WALLS ARE PART OF
 THIS SUBMITTAL.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-22 Cont ID  
Sent By pleduc Date 2020-06-22 Time   Rev Time 0.00
Received By pleduc Date 2020-06-22 Time 09:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-02 Cont ID  
Sent By pleduc Date 2020-03-02 Time   Rev Time 0.00
Received By pleduc Date 2020-03-02 Time 15:06 Sent To I
Notes
2020-03-02 15:30:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE EXISTING BUILDING IS PROTECTED BY FIRE
 SPRINKLERS. ANY OVERHANG OR CANOPY IS REQUIRED TO HAVE
 THE FIRE SPRINKLER SYSTEM EXTENDED TO PROTECT IT.
  
 ADDITIONALLY, A CURTAIN IS PROPOSED THAT ENCLOSES THE
 CANOPY.
  
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703.
  
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE
 THAT THE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
  
 2) PLEASE PROVIDE A DETAILE DNARRATIVE OF HOW THIS
 CREATED SPACE IS PROPOSED TO FUNCTION.
  
  
 3) A CURTAIN IS INDICATED, WAS THE MATERIAL OF THE
 CURTAIN PROVIDED.
  
 IT IS NOT CLEAR WHAT THE CURTAIN IS COMPOSED OF.
  
 PLEASE PROVIDE A SAMPLE AND OR MANUFACTURES SPECS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-06 Cont ID  
Sent By shill Date 2020-07-06 Time 13:43 Rev Time 0.00
Received By shill Date 2020-06-17 Time 16:57 Sent To  
Notes
2020-06-19 17:00:0506/17/2020 CONTRACTOR UPLOADED PLANS/DOCUMENTS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-02 Cont ID  
Sent By spalmer Date 2020-03-02 Time 18:02 Rev Time 0.00
Received By spalmer Date 2020-01-23 Time 13:44 Sent To  
Notes
2020-02-19 18:25:26RESUB ROUTED TO CTHROOP
2020-01-27 13:44:27RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-22 Cont ID  
Sent By cthroop Date 2020-01-22 Time 13:29 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 13:51 Sent To  
Notes
2020-01-15 15:35:59MISC 2
2020-01-15 09:11:55TO LMARCHAN
2020-01-09 13:51:28ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By shill Date 2020-07-16 Time 11:06 Rev Time 0.00
Received By shill Date 2020-07-16 Time 11:06 Sent To  
Notes
2020-07-29 13:19:37RECEIVED ORIGINALS ON 7/29, ROUTED TO STORAGE SH
2020-07-16 11:07:03MIKE WILL MAIL DIRECTLY TO ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 12:46 Sent To  
Notes
2020-06-25 12:51:29THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 ELECTRONICALLY SUBMITTED CANOPY DRAWINGS. FS 471 & FAC
 61G15
2020-06-19 16:59:4306/17/2020 CONTRACTOR UPLOADED PLANS/DOCUMENTS. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-06-29 Cont ID  
Sent By aaponte Date 2020-06-29 Time 15:12 Rev Time 0.00
Received By aaponte Date 2020-06-29 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-02-19 Cont ID  
Sent By aaponte Date 2020-02-19 Time 11:47 Rev Time 0.00
Received By aaponte Date 2020-02-19 Time 11:47 Sent To  
Notes
2020-02-19 12:03:15REPEAT COMMENT- PROPOSED CANOPY CONFLICTS WTIHT THE
 LANDSCAPE PROPOSED ON THE EDGE PLANTERS. PLEASE
 COORDINATE WITH PROJECT LANDSCAPE AND SUBMIT COPY OF
 THE APPROVED LANDSCAPE ALONG WITH THE CANOPY PERMITI TO
 DEMONSTRATE THERE WILL BE NO CONFLICT.
 FOR ADDITIONAL INFORMATION PLEAS CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By aaponte Date 2020-01-15 Time 09:10 Rev Time 0.00
Received By aaponte Date 2020-01-15 Time 09:10 Sent To  
Notes
2020-01-15 09:11:38PROPOSED CANOPY CONFLICTS WTIHT THE LANDSCAPE PROPOSED
 ON THE EDGE PLANTERS. PLEASE COORDINATE WITH PROJECT
 LANDSCAPE AND SUBMIT COPY OF THE APPROVED LANDSCAPE
 ALONG WITH THE CANOPY PERMTI TO DEMONSTRATE THERE WILL
 BE NO CONFLICT.
 FOR ADDITIONAL INFORMATION PLEAS CONTACT ANA MARIA
 APONTE AT 561-822-1439.