Plan Review Details - Permit 20010093
Plan Review Stops For Permit 20010093
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-21 Cont ID  
Sent By fgiaquin Date 2020-08-21 Time 22:04 Rev Time 0.00
Received By fgiaquin Date 2020-08-21 Time 21:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 11:50 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-08 Cont ID  
Sent By fgiaquin Date 2020-02-08 Time 12:48 Rev Time 0.00
Received By fgiaquin Date 2020-02-06 Time 06:04 Sent To  
Notes
2020-02-08 12:48:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. DESIGNS OVER $125,000 MUST BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL. F.S.
 471.003(2)(H)(1)
  
 2. PROVIDE UL OR OTHER NRTL (NATIONALLY RECOGNIZED
 TESTING LABORATORY) LISTINGS FOR ALL
 DEVICES/MATERIALS/AND EQUIPMENT. LIGHT FIXTURES, LIGHT
 POLES, ETC. NEC 90.7, 110.2, 110.3 FBC 107.2.1
  
 3. FBC-107.1 GENERAL - FAC 61G15-23.002 - PROVIDE A
 TITLE BLOCK FOR THE ENGINEER OF RECORD CONSISTENT WITH
 THE REQUIREMENTS OF THIS SECTION, E.G.: FIRM NAME,
 LICENSE NUMBER, PHONE NUMBER...ETC.
  
 4. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.5 (A NOTE ON PLAN WILL SUFFICE).
  
 5.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 6.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24. LABELS OUTDOORS MUST BE
 SUFFICIENT TO WITHSTAND THE WEATHER AND ELEMENTS.
  
 7.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-21 Cont ID  
Sent By fgiaquin Date 2020-08-21 Time 22:05 Rev Time 0.00
Received By fgiaquin Date 2020-08-06 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-06 Cont ID  
Sent By lmarchan Date 2020-07-06 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2020-06-03 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By shill Date 2020-04-10 Time 06:03 Rev Time 0.00
Received By shill Date 2020-01-27 Time 08:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-09-05 Cont ID  
Sent By fgiaquin Date 2020-09-05 Time 20:32 Rev Time 0.00
Received By fgiaquin Date 2020-09-05 Time 20:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-21 Cont ID  
Sent By fgiaquin Date 2020-08-21 Time 22:05 Rev Time 0.00
Received By fgiaquin Date 2020-08-21 Time 22:04 Sent To  
Notes
2020-08-21 22:05:07PLEASE SEE "SIGNATURE" REVIEW COMMENTS FROM LAST REVIEW
 ON 7/6 AND SIGN PAGES THAT NEED TO BE SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-06 Cont ID  
Sent By medwards Date 2020-07-06 Time 07:34 Rev Time 0.00
Received By medwards Date 2020-07-06 Time 07:34 Sent To  
Notes
2020-07-06 07:37:21DESIGNER MUST SIGN AND SEAL SHEETS- L-22; L-23; L-24
 FS-471
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By medwards Date 2020-03-03 Time 11:12 Rev Time 0.00
Received By medwards Date 2020-03-03 Time   Sent To  
Notes
2020-03-03 11:15:02BOTH ENGINEERS MUST ATTACH THEIR SEALS AND SIGN EACH
 SHEET OF THESE DRAWINGS. ENGINEERS MUST ALSO ATTACH A
 DIGITAL SEAL AND SIGNATURE TO EACH SHEET OF THESE
 DRAWINGS.
  
 MICHAEL EDWARDS
 561-805-6728
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By aaponte Date 2020-08-27 Time 16:42 Rev Time 0.00
Received By aaponte Date 2020-08-27 Time 16:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By aaponte Date 2020-06-25 Time 14:47 Rev Time 0.00
Received By aaponte Date 2020-06-25 Time 14:47 Sent To  
Notes
2020-06-25 14:47:41PROVISO: CITY STANDARD FIXTURE AND POLE SHALL BE BLACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By aaponte Date 2020-04-09 Time 14:04 Rev Time 0.00
Received By aaponte Date 2020-04-09 Time 14:04 Sent To  
Notes
2020-04-09 14:04:401. PLEASE PROVIDE A DETAIL SPEC DRAWING FOR THE ACORN
 LIGHT FIXTURE PROPOSED EAST OF DIXIE HWAY. IT SHOULD
 FOLLOW CITY STANDARDS FOR DOWNTOWN.
 2. DO WE NEED POLE 26? IT IS RIGHT NEXT TO AN EXISTING
 COUNTY LIGHT (POLE 133). COULD WE MAKE THE LAMP ON THE
 EXISTING COUNTY A TRIPLE HEAD AND REMOVE 26? THERE ARE
 SEVERAL POLES IN THAT AREA.
 3. ARE POLES 84 AND 85 MOUNTED ON THE MAST ARM? IF NOT,
 HOW ARE THEY LOCATED NEXT TO THE EXISTING MAST AMS?
 4. PLEASE INDICATE THE LOCATION OF THE RAILROAD
 CROSSINGS SIGNAL POLES.
 5. PLEASE CONFIRM LOCATION OF POLES ON NORTH SIDE OF
 BANYAN FROM DIXIE TO OLIVE ARE COORDINATED WITH THE
 PROPOSED 303 BANYAN PROJECT. DEPENDING ON THE SCHEDULE
 OF THE PRIVATE PROJECT, THESE FIXTURES COULD BE
 EXCLUDED FROM THE SCOPE OF WORK.
 6. POLES 111-113 AND,117 - 114 ARE ALREADY INSTALLED
 (OLD ICTY HALL PROJECT).
 7. WHERE IS POLE 130?
 8. PLEASE CONFIRM PROPOSED LIGHT FIXTURE INCLUDES THE
 7-PIN RECEPTACLE REQUIRED BY CITY STANDARDS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.