Plan Review Details - Permit 20010087
Plan Review Stops For Permit 20010087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By rmcphers Date 2020-01-31 Time 11:42 Rev Time 0.00
Received By rmcphers Date 2020-01-31 Time 11:42 Sent To  
Notes
2020-01-31 11:53:07ATM SURROUND
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE ALL FRAMING ATTACHMENT DETAILS
 (WELDING, BOLTING - TYPES, SIZES, ETC.) FBC WPB
 AMENDMENTS107.2
 2) PLEASE PROVIDE A LOCATION PLAN FBC WPB AMENDMENTS
 107.2
 3) PLEASE PROVIDE A PERMIT APPLICATION FROM A
 CONTRACTOR LICENSED TO BUILD AND INSTALL THE STRUCTURE
 AND FOUNDATION, FBC WPB AMENDMENTS 105.1
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By fgiaquin Date 2020-01-29 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2020-01-29 Time 06:20 Sent To I
Notes
2020-01-29 06:36:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 FIRST PLEASE REVIEW THE SCOPE OF WORK FOR AND (ES) SIGN
 SPECIALTY LICENSE IN THE STATE OF FLORIDA:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 1. PROVIDE 120V DISCONNECT PER 600.6A1 NEC
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 (120V DISCONNECT MUST BE INSTALLED BY LICENSED
 ELECTRICIAN WITH SEPARATE ELECTRICAL PERMIT. FBC 105.1)
  
 2. SIGN COMPANY WITH ES LICENSE IS ONLY PERMITTED TO
 CONNECT FROM LAST DISCONNECTING MEANS TO SIGN.
  
 3. PALM BEACH OUTLET APPROVAL MALL STAMP IS REQUIRED
  
 4. PROVIDE UL OR OTHER NRTL LISTING FOR ATM SIGN
 SURROUND. FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 5. PROVIDE ELECTRICAL PLANS/WIRING DIAGRAM FOR SIGN
 SURROUND FBC 107.2.1
  
 6. PROVIDE COMPLIANCE WITH ENERGY CODE,
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.5
  
 7. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 8. VALUE LOW FOR AMOUNT OF WORK SHOWN. RAISE VALUE. FBC
 109.3
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-31 Cont ID  
Sent By rmcphers Date 2020-01-31 Time 13:58 Rev Time 0.00
Received By rmcphers Date 2020-01-03 Time 13:04 Sent To  
Notes
2020-01-31 13:59:25PLANS TAKEN TO PERMIT LIBRARY
2020-01-30 07:51:37ROUTED TO MISC 2
2020-01-28 11:14:48ROUTED TO ELECTRICAL
2020-01-06 13:04:28ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By eschneid Date 2020-01-27 Time 11:39 Rev Time 0.25
Received By eschneid Date 2020-01-27 Time 11:17 Sent To PC
Notes
2020-01-27 13:07:59FAILED
  
 1) THE PERMIT PLANS ARE REQUIRED TO BE APPROVED BY THE
 PALM BEACH OUTLETS MANAGEMENT. EITHER PROVIDE THE
 MANAGEMENT STAMP ON THE PLANS OR A SEPARATE LETTER FROM
 THE MANAGEMENT THAT LISTS THE APPROVED PLANS.
  
 2) PROVIDE TWO COPIES OF A SURVEY/SITE PLAN SHOWING THE
 LOCATION OF THE PROPOSED ATM SURROUND STRUCTURE.
  
 3) THE TD SIGN(S) REQUIRES A SEPARATE SIGN PERMIT WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  