Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By tklarge Date 2020-01-08 Time 14:43 Rev Time 0.00
Received By tklarge Date 2020-01-08 Time 14:12 Sent To  
Notes
2020-01-08 14:27:561) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED IS FROM
 AN OUTDATED GAS CODE EDITION. SUBMIT THE CORRECT SIZING
 FROM THE 2017 FBC-GAS CODE.
 2) SHOW THE DISTANCE FROM THE GAS METER TO THE POOL
 HEATER.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GAS REGULATOR TO BE INSTALLED AT
 THE POOL HEATER.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC. 409.4.
 5) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2(7).
 6) THE GAS PLAN ON FILE WITH THE CITY SHOWS THE BTU
 LOAD OF THE EXISTING GAS RANGE AS 125,000 BTU'S AND THE
 WATER HEATER AT 255,000 BTU'S. CLARIFY.
 7) THE GAS PLANS REFERENCE NFPA 58. THIS STANDARD IS
 FOR LP GAS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  