2019-12-23 16:35:33 | RESIDENTIAL (R3) PROVISO SUBMITAL BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE; |
| BELOW IS THE COPY OF THE ORIGINAL PROVISO. COMPLIED |
| ITEMS ARE MARKED AS OK. SEE RESPONSE COMMENTS FOR ITEMS |
| NOT COMPLIED. |
| |
| BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS |
| AND SEC. 110.9 CITY AMENDMENTS. |
| RESPONSE: |
| DRAINAGE PLAN WAS NOT SUBMITTED YET. NEED TO PROVIDE |
| THE REQUESTED PLAN. |
| |
| 2- OK |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) |
| |
| B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| RECORD. AND CLEARLY MARK PADDY SIZE. |
| RESPONSE: |
| CLEARLY MARK PADDY SIZE ON THE PRODUCT APPROVAL |
| SUBMITTED. |
| |
| |
| C) DOUBLE DOORS AS SHOWN FOR NEW STORAGE. |
| RESPONSE: FLORIDA PRODUCT APPROVAL FL11136-R7 IS FOR |
| SINGLE DOORS ONLY. NEED TO PROVIDE PRODUCT APPROVAL FOR |
| DOUBLE DOORS AS SHOWN ON PLANS. |
| |
| D) RIDGE VENT SPECIFIED BY THE ENGINEER OF RECORD ON |
| PAGE 9.0 OF DRAWINGS SUBMITTED. |
| RESPONSE: |
| RIDGE VENT FLORIDA PRODUCT APPROVAL FL6267-R15 |
| SUBMITTED IS FOR SHINGLES APPLICATIONS. NEED PRODUCT |
| APPROVAL FOR ROOF TILE APPLICATION AS SHOWN ON PLANS. |
| |
| E) NEW COMMENT: |
| ROOF TILE NOA WAS REVISED. CLEARLY MARK ON NEW NOA THE |
| PROPOSED FOAM PADDY SIZE TO VERIFY COMPLIANCE WITH THE |
| UPLIFT CALCULATIONS. SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| CITY AMENDMENTS. |
| |
| |
| 5- ENGINEER OF RECORD SPECIFIES RIDGE VENT. SEE ATTIC |
| SPACE VENTILATION CALCULATIONS ON PAGE 9.0. ENGINEER TO |
| PROVIDE DETAILS/SPECIFICATIONS SHOWING LOCATION OF THE |
| RIDGE VENT VENTILATION. SEC. 107.2.1 CITY AMENDMENTS. |
| RESPONSE: |
| INFORMATION WAS NOT PROVIDED. NOTE: COORDINATE WITH |
| RIDGE VENT PRODUCT APPROVAL. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |