Plan Review Details - Permit 19120832
Plan Review Stops For Permit 19120832
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 14:14 Sent To  
Notes
2020-01-06 14:15:43BUILDING BUILT IN 2006 NO ASBESTOS. JWL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-22 Cont ID  
Sent By jwitmer Date 2020-01-22 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2020-01-22 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 14:15 Sent To  
Notes
2020-01-06 14:32:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120832
 ADD: 801 N OLIVE SUITE: 1209
 CONT: J D ROOFING AND CONTRACTING
 TEL: 561-719-0725
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN. 06/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A HIGHRISE CONDO AND THE
 REQUIREMENTS FOR FLOORING ARE VERY STRINGENT. THE ONLY
 REFERENCE TO THE TYPE OF FLOORING BEING INSTALLED IS
 THE PERMIT APPLICATION, THE PERMIT APPLICATION
 INDICATES THE NEW FLOORING BEING INSTALLED IS WALNUT.
 THERE IS NO OTHER INFORMATION PROVIDED. IS THE WALNUT
 FLOORING A LAMINATE, ENGINEERED WOOD OR A ? INCH THICK
 PLANK FLOORING? THE SECOND ISSUE IS THE FLOORING
 INSULATION APPROVALS ARE FOR SOUND LVT VINYL ON
 SILENCER LVT UNDERLAYMENT. PLEASE PROVIDE THE TYPE OF
 WALNUT FLOORING AND UNDERLAYMENT THAT IS TO BE
 INSTALLED AND TESTED TO THE 3 TEST LISTED BELOW. WE
 WANT THE ACTUAL TEST NOT SALES BROCHURES. IF THE WALNUT
 FLOORING IS ? INCH PLANK FLOORING AND SUBFLOOR AND OR
 SLEEPERS ARE TO BE INSTALLED THEN COMPLIANCE NEEDS TO
 FOLLOW 805.1 OF THE FBC-B 2017 CODE FOR TYPE I TYPE II
 BUILDINGS.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-22 Cont ID  
Sent By jpearson Date 2019-12-22 Time 11:51 Rev Time 0.00
Received By jpearson Date 2019-12-22 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-01-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-14 Time 13:47 Sent To  
Notes
2020-01-15 13:47:25RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-19 Time 13:35 Sent To  
Notes
2019-12-20 13:36:03B02


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved