Plan Review Details - Permit 19120807
Plan Review Stops For Permit 19120807
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-24 Cont ID  
Sent By rmcphers Date 2020-06-24 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2020-06-24 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 16:36 Rev Time 0.00
Received By rmcphers Date 2020-04-24 Time 16:36 Sent To  
Notes
2020-04-24 16:33:41GENERATOR ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) BOTTOM HAND RAIL EXTENSION ON DRAWING 5.3 NEEDS TO
 COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. "CONTINUE
 TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER".
 2) GENERATOR HOUSING TIE DOWN (ATTACHMENT TO SLAB)
 NEEDS TO BE A SITE SPECIFIC SIGNED AND SEALED DETAIL
 SHOWING ATTACHMENT TYPE, SIZE, AMOUNT ETC. AND THE WIND
 DESIGN CRITERIA USED FOR DESIGN - FROM AN ARCHITECT OR
 ENGINEER TO COMPLY WITH WIND PRESSURES PER FBC 1609
 (180MPH)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2020-02-18 Time 09:51 Sent To  
Notes
2020-02-18 10:59:28GENERATOR ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW STAIRWAY HANDRAIL EXTENSIONS AT TOP AND
 BOTTOM OF STAIRS TO COMPLY WITH FBC 1014.6
 2) PLEASE PROVIDE STATE APPROVED PRE MANUFACTURED
 BUILDING DRAWINGS APPROVED BY A THIRD PARTY REVIEW OR
 SIGNED AND SEALED DRAWINGS FOR THE ON SITE CONSTRUCTION
 OF THE ENCLOSURE FBC WPB AMENDMENTS 107.3 EXCEPTION (1)
 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT FBC
 1803.1
 4) PLEASE PROVIDE SIGNED AND SEALED ANCHORING DETAILS
 FOR THE PRE FAB BUILDING AND STAIR - SHOW TYPE, SIZE
 AND LOCATION OF ANCHORS. FBC WPB AMENDMENTS 107
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-30 Cont ID  
Sent By jleahy Date 2020-06-30 Time 14:33 Rev Time 0.00
Received By jleahy Date 2020-06-30 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By jleahy Date 2020-04-28 Time 14:46 Rev Time 0.00
Received By jleahy Date 2020-04-28 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-26 Cont ID  
Sent By jleahy Date 2020-02-26 Time 16:49 Rev Time 0.00
Received By jleahy Date 2020-02-24 Time 15:31 Sent To  
Notes
2020-02-26 07:49:43FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE WORK SHOWN DOES NOT INCLUDE THE
 GENSETS. PLEASE SUBMIT A VALUE WHICH INCLUDES THE
 GENERATORS AND OTHER CUSTOMER SUPPLIED EQUIPMENT.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) NEED AN ELECTRICAL PERMIT FOR THE ELECTRICAL WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-21 Cont ID  
Sent By pleduc Date 2020-04-21 Time   Rev Time 0.00
Received By pleduc Date 2020-04-20 Time 09:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-13 Cont ID  
Sent By pleduc Date 2020-02-13 Time   Rev Time 0.00
Received By pleduc Date 2020-02-11 Time 09:38 Sent To  
Notes
2020-02-13 11:39:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THE REMOVAL OF THE GENERATOR REQUIRES AN EVALUATION OF
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
  
 1) MODIFICATIONS TO THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEM MAY BE REQUIRED DUE TO CHANGES.
  
  
  
 2) ANY WORK ON THE FS AND FA SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-22 Cont ID  
Sent By ccole Date 2020-06-22 Time 16:43 Rev Time 0.00
Received By ccole Date 2020-06-19 Time 16:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 11:56 Rev Time 0.00
Received By ccole Date 2020-04-30 Time 08:34 Sent To  
Notes
2020-04-30 11:56:21 
 2ND REVIEW FBC-2017 PLUMBING/GAS
 PERMIT #19120807
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4, UNDERGROUND GAS PIPING: SHOW THE WHERE
 GENERATOR BRANCH LINE CONNECTS TO THE MAIN LINE-
 SECTION 107.2.1 WPB.
  
 2) P1.1: MODIFY THE ISOMETRIC DRAWING TO INDICATE THE
 LENGTH OF THE UNDERGROUND PIPING RUN FROM THE POINT OF
 CONNECTION AT THE MAIN UNDERGROUND LINE TO THE NEW GAS
 METER AT THE ENCLOSURE. IDENTIFY THE TYPE AND SIZE OF
 UNDERGROUND GAS PIPING, BURIAL DEPTH AND HOW THE PIPE
 WILL BE PROTECTED FROM DAMAGE- SECTIONS 402.4 AND 404.1
 FBC FG.
  
 3) P1.1: I HAVE REVIEWED THE SUBMITTED SHOP DRAWINGS
 AND PRODUCT APPROVAL FOR THE GENERATOR ENCLOSURE, AND
 THE CLARKE GENERATOR SPECIFICATIONS SUBMITTAL WHICH
 INCLUDES THE OPTIBLEND DUEL FUEL SYSTEM SPECS. I DO NOT
 SEE IN ANY OF THESE DOCUMENTS AN INTERNAL GAS PIPING
 ISOMETRIC OR LAYOUT DRAWING FOR CONNECTING THE
 GENERATORS TO THE NEW EXTERIOR GAS LINE AND SERVICE.
 PAGE 29 OF THE GENERATOR SPECS INDICATES THE OPTIBLEND
 KITS ARE SHIPPED WITH EACH ASSEMBLY PACKAGE TOGETHER,
 BUT NO CONNECTION DETAILS PROVIDED TO THE GAS SUPPLY
 SYSTEM. PLEASE MODIFY THE EXISTING ISOMETRIC DRAWING
 ACCORDINGLY AND ALSO PROVIDE A GAS PIPING LAYOUT FOR
 INSIDE THE ENCLOSURE. SHOW LOCATIONS OF REGULATORS,
 SHUT OFF VALVES, UNIONS AND INLET PRESSURE REQUIRED AT
 THE OPTIBLEND KIT AND GENERATOR. PLEASE SEE GAS
 PRESSURE INFO ON PAGE 23 AND 29 OF THE SPEC- SECTIONS
 107.2.1 WPB. A) PLEASE CLARIFY HOW THE 18,000 SCFH
 TOTAL GAS LOAD WAS DETERMINED. WHICH CONVERSION OR
 CALULATION METHOD WAS USED?- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By shill Date 2020-02-21 Time 09:11 Rev Time 0.00
Received By shill Date 2020-02-17 Time 17:16 Sent To  
Notes
2020-02-21 09:11:50 
 GAS 1ST REVIEW**DENIED**19120807
  
  
 1)ON SHT. P1 YOU SO A NEW GAS METER BUT ALSO A GAS LINE
 TO CONNECT INTO THE BUILDINGS EXISTING. PLEASE CLARIFY.
 FBC 107.2.1. THE PLANS INDICATE AN EXISTING GAS METER.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3
  
  
 2)SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2 SHOW THE TYPE OF PIPE
 MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE
  
  
  
  
  
 3)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
  
  
  
  
  
 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIMES
  
  
  
  
  
 5)SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37)E OF INSPECTION. FGC SEC.305.1
  
  
  
  
  
 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
  
 7) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1
  
  
 8) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
  
  
  
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
  
  
 TIM HUNT
  
  
 PLUMBING PLAN REVIEW
  
  
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
  
  
 561-248-2703
  
  
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-17 Cont ID  
Sent By lmarchan Date 2020-07-17 Time 16:27 Rev Time 0.00
Received By lmarchan Date 2020-07-07 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-30 Cont ID  
Sent By jleahy Date 2020-06-30 Time 14:33 Rev Time 0.00
Received By jleahy Date 2020-06-15 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-01 Cont ID  
Sent By lmarchan Date 2020-05-01 Time 08:48 Rev Time 0.00
Received By lmarchan Date 2020-04-17 Time 10:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-26 Cont ID  
Sent By jleahy Date 2020-02-26 Time 16:49 Rev Time 0.00
Received By jleahy Date 2020-02-04 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-23 Cont ID  
Sent By ccole Date 2020-06-23 Time 10:21 Rev Time 0.00
Received By ccole Date 2020-06-19 Time 16:46 Sent To  
Notes
2020-06-23 10:26:21HOLDS ON CO PLACED FOR UL FIELD EVALUATION REPORT, AND
 ACCEPTANCE TESTING REPORT PER NFPA 110.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 13:47 Rev Time 0.00
Received By ccole Date 2020-04-30 Time 13:47 Sent To  
Notes
2020-04-30 13:47:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120807
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND
 STANDARDS USED IN THE DESIGN OF THE EPSS (EMERGENCY
 POWER SUPPLY SYSTEM)- SECTION 107.2.1 WPB.
  
 2) PLEASE INDICATE HOW COMPLIANCE IS BEING MET WITH
 RULE 58A-5.036, F.A.C., EMERGENCY ENVIRONMENTAL CONTROL
 FOR ASSISTED LIVING FACILITIES. PROVIDE A LIST OF HVAC
 SYSTEMS TO BE SUPPPORTED BY THE EPSS.
  
 3) REFER TO SECTION 4.1 NFPA 110 AND INDICATE THE LEVEL
 OF THE EPSS- 1 OR 2, AND SHOW COMPLIANCE WITH 4.4 ITEMS
 1, 2, & 3.
  
 4) REFER TO PAGE 6 OF THE SHOP DRAWINGS FOR THE
 GENERATOR ENCLOSURE WO#46720- 11/27/2019. IT APPEARS
 THE LOUVER/DAMPER LIST OF PRODUCTS AT THE BOTTOM LEFT
 OF THE PAGE IS CUT OFF. VERIFY THAT ALL AIR INTAKE AND
 EXHAUST LOUVERS ARE AMCA 550 RATED IN ACCORDANCE WITH
 SECTION 401.5 AND 501.3.2 FBC M.
  
 5) MOTORIZED DAMPERS ARE INDICATED IN THE SPECIAL
 INSTRUCTIONS LIST. PLEASE PROVIDE THE SEQUENCE OF
 OPERATION FOR THE EXHAUST VENTILATION SYSTEM- SECTION
 510.3 AND 510.6.5 FBC M. VERIFY THE DAMPERS ARE IN
 COMPLIANCE WITH SECTION 7.7.5 NFPA 110.
  
 6) REFER TO SECTION 7.7.4.1 NFPA 110 AND PROVIDE THE
 STATIC RESTRICTION AT THE RADIATOR DISCHARGE
 OUTLET.VERIFY THE LOUVERS WILL NOT RESTRICT AIRFLOW.
  
 7) PROVIDE ENGINE EXHAUST PIPING SPECIFICATIONS AND
 BACKPRESSURE CALCULATIONS- SECTION 7.10.1 NFPA 110 AND
 SECTION 107.2.1 WPB.
  
 8) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND
 THE FUEL TANK- SECTIONS 304.1 AND 915.1 FBC M.
  
 9) REFER TO SECTIONS 7.13.1 THROUGH 17.13.4.1.6 NFPA
 110 AND PROVIDE AN ACCEPTANCE TESTING PROCEDURE
 OUTLINE. PLEASE NOTE ITEMS #1-4 SECTION 7.13.4.6 SHALL
 BE MADE AVAILABLE TO THE WPB BUILDING DEPARTMENT FOR
 FINAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-06-24 Cont ID  
Sent By ccole Date 2020-06-22 Time 16:44 Rev Time 0.00
Received By ccole Date 2020-06-19 Time 16:27 Sent To  
Notes
2020-06-22 16:50:34PER THE EOR, CONDENSATION FROM EXHAUST SYSTEMS IS A
 SELF-CONTAINED SEALED SYSTEM THAT IS OPENED ONLY FOR
 INSPECTION AND REPAIRS, AND THEN DRAINED BY HAND IS
 NECESSARY.
 MECHNAICAL INSPECTOR WILL VERIFY IN FIELD.
 CCOLE- 6/24/2020
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By ccole Date 2020-04-30 Time 12:03 Rev Time 0.00
Received By ccole Date 2020-04-30 Time 12:03 Sent To  
Notes
2020-04-30 12:08:541ST REVIEW FBC-2017 PLUMBING
 PERMIT #19120807
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 7.10.3.1 NFPA 110 AND VERIFY THE
 GENERATOR EXHAUST PIPES ARE SELF-DRAINING, OR PROVIDE A
 CONDENSATE TRAP AND DRAIN VALVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By shill Date 2020-02-21 Time 09:11 Rev Time 0.00
Received By shill Date 2020-02-17 Time 17:16 Sent To  
Notes
2020-02-21 09:12:15SEE GAS REVIEW
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-24 Cont ID  
Sent By rmcphers Date 2020-06-24 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2020-06-24 Time 09:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 16:36 Rev Time 0.00
Received By rmcphers Date 2020-04-24 Time 16:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2020-02-18 Time 12:50 Sent To  
Notes
2020-02-18 12:51:47ALL DRAWINGS OK - - ADDED DRAWINGS WILL NEED TO BE
 VERIFIED.

Review Stop Z ZONING
Rev No 4 Status P Date 2020-07-17 Cont ID  
Sent By eschneid Date 2020-07-17 Time 16:22 Rev Time 0.25
Received By eschneid Date 2020-07-17 Time 15:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-06-25 Cont ID  
Sent By eschneid Date 2020-06-25 Time 13:24 Rev Time 0.25
Received By eschneid Date 2020-06-25 Time 11:16 Sent To  
Notes
2020-06-25 13:20:06FAILED
  
 1) REPEAT COMMENT: THE PROPOSED DUCK BANK, WHERE IT
 MEETS THE NORTH SIDE OF THE COOLING TOWER ENCLOSURE,
 APPEARS TO DIRECTLY CONFLICT WITH AN EXISTING SABAL
 PALM TREE. PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK
 TO AVOID THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT
 IT DOES NOT INTERFERE WITH THE EXISTING TREE. ---- NO
 RESPONSE PROVIDED OR CHANGES MADE.
  
 2) REPEAT COMMENT: ZONING WILL NOT APPROVE THIS PERMIT
 UNTIL A TREE ALTERATION PERMIT HAS BEEN SUBMITTED TO
 THE PLANNING DIVISION AND APPROVED BY THE CITY'S
 LANDSCAPE PLANNER. THIS IS REQUIRED SINCE THE PLANS
 CALL FOR TREES TO BE REMOVED AT THE GENERATOR LOCATION.
 NOTE: THE LATEST PROPOSAL IS TO DESTROY THE TREES.
 PLANNING STAFF IS NOT APPROVING THIS OPTION. THE TREES
 WILL NEED TO BE RELOCATED OR THE GENERATOR INSTALLED IN
 A LOCATION THAT DOES NOT IMPACT THE TREES.
  
 3) THE FENCE RELOCATION IS APPROVED AS PART OF THIS
 PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By eschneid Date 2020-04-30 Time 16:05 Rev Time 0.50
Received By eschneid Date 2020-04-30 Time 15:46 Sent To  
Notes
2020-04-30 16:50:49FAILED
  
 1) THE CIVIL PLAN NEEDS TO SHOW THE FULL EXTENT OF THE
 GENERATOR PAD, INCLUDING DIMENSIONS, IN ITS CORRECT
 LOCATION.
  
 2) THE PROPOSED DUCK BANK, WHERE IT MEETS THE NORTH
 SIDE OF THE COOLING TOWER ENCLOSURE, APPEARS TO
 DIRECTLY CONFLICT WITH AN EXISTING SABAL PALM TREE.
 PLEASE REVIEW THE PLACEMENT OF THE DUCT BANK TO AVOID
 THE TREE AND PROVIDE DRAWINGS TO VERIFY THAT IT DOES
 NOT INTERFERE WITH THE EXISTING TREE.
  
 3) ZONING WILL NOT APPROVE THIS PERMIT UNTIL A TREE
 ALTERATION PERMIT HAS BEEN SUBMITTED TO THE PLANNING
 DIVISION AND APPROVED BY THE CITY'S LANDSCAPE PLANNER.
 THIS IS REQUIRED SINCE THE PLANS CALL FOR TREES TO BE
 REMOVED AT THE GENERATOR LOCATION.
  
 4) THE FENCE RELOCATION IS APPROVED AS PART OF THIS
 PERMIT AND DOES NOT REQUIRE A SEPARATE FENCE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-14 Cont ID  
Sent By eschneid Date 2020-02-14 Time 14:09 Rev Time 0.25
Received By eschneid Date 2020-02-14 Time 14:09 Sent To  
Notes
2020-02-14 14:10:25FAILED
  
 THE GENERATOR LOCATION DOES NOT HAVE SITE PLAN
 APPROVAL. ZONING WILL NOT REVIEW THE PERMIT UNTIL THE
 SITE PLAN APPROVAL HAS BEEN GRANTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]