Plan Review Details - Permit 19120756
Plan Review Stops For Permit 19120756
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 08:46 Rev Time 0.00
Received By jgomez Date 2020-02-12 Time 08:08 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By jgomez Date 2020-01-08 Time 14:12 Rev Time 0.00
Received By jgomez Date 2020-01-08 Time 14:04 Sent To E
Notes
2020-01-08 14:14:03BUILDING IS OK BUT NEED ZONING APPROVAL BEFORE
 APPROVING THE BUILDING REVIEW.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-02-13 Cont ID  
Sent By jleahy Date 2020-02-13 Time 11:30 Rev Time 0.00
Received By jleahy Date 2020-02-13 Time 11:30 Sent To  
Notes
2020-02-13 11:31:37PLANS CALL FOR NON ELECTRIC SIGN JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By fgiaquin Date 2020-01-09 Time 06:49 Rev Time 0.00
Received By fgiaquin Date 2020-01-09 Time 06:36 Sent To I
Notes
2020-01-09 06:49:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ENGINEER'S SEAL IS REQUIRED TO BE SIGNED WITH A WET
 SIGNATURE, NOT A STAMP. PLEASE SEE REQUIREMENTS BELOW
 FOR SIGNATURES AND SEALS
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 2. NEED APPROVAL FROM ZONING DEPARTMENT.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-13 Cont ID  
Sent By jleahy Date 2020-02-13 Time 11:31 Rev Time 0.00
Received By jleahy Date 2020-01-24 Time 13:52 Sent To  
Notes
2020-02-12 07:16:47ROUTED TO JGOMEZ
2020-02-11 16:12:27ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/11/20 EL
2020-01-27 13:52:31RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-09 Cont ID  
Sent By fgiaquin Date 2020-01-09 Time 06:49 Rev Time 0.00
Received By fgiaquin Date 2019-12-17 Time 13:53 Sent To  
Notes
2020-01-06 13:16:00ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/6/20 EL
2019-12-18 13:53:11ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-11 Cont ID  
Sent By elevesqu Date 2020-02-11 Time 16:12 Rev Time 0.00
Received By elevesqu Date 2020-02-11 Time 16:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By elevesqu Date 2020-01-06 Time 13:15 Rev Time 0.00
Received By elevesqu Date 2020-01-06 Time 13:15 Sent To B
Notes
2020-01-06 13:15:31NO INTERNAL ILLUMINATION PERMITTED, EXTERNAL ONLY
  
 PROVIDE VERTICAL CLEARANCE DIMENSION FROM SIDEWALK TO
 BOTTOM OF SIGN
  
 PROVIDE DIMENSION FROM WALL FACADE TO FURTHEST END OF
 SIGN- CANNOT EXCEED FOUR FEET
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
  
  