Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By jgomez Date 2020-01-07 Time 18:55 Rev Time 0.00
Received By jgomez Date 2020-01-08 Time 08:43 Sent To  
Notes
2020-01-08 09:49:37RE STRIPPING BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- SCOPE OF WORK IS NOT CLEAR. THIS IS A MULTI LEVEL
 BUILDING. ONLY ONE FLOOR LEVEL WAS SUBMITTED. IF THE
 SCOPE OF WORK IS FOR MORE THAN ONE LEVEL, THEN PROVIDE
 FLOOR PLAN FOR EACH LEVEL WHERE WORK IS GOING TO TAKE
 PLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CLEARLY IDENTIFY HOW MANY PARKING SPACES ARE
 PROVIDED ON EACH LEVEL TO VERIFY COMPLIANCE WITH THE
 MINIMUM ACCESSIBLE PARKING SPACES. NOTE: 1 TO 25
 PARKING SPACES REQUIRE AT LEAST 1 ACCESSIBLE SPACE.
 AND, 26 TO 50 PARKING SPACES REQUIRE AT EAST 2
 ACCESSIBLE PARKING SPACES. SEC. 801.3 FBC-EXISTING
 BUILDING AND TABLE 208.2 FBC-ACCESSIBILITY.
  
 3- PLANS SUBMITTED NEED TO HAVE THE SEAL AND SIGNATURE
 OF THE ENGINEER SHOWN ON THE TITLE BLOCK AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 4- PLANS SUBMITTED ARE TOO SMALL. THEY ARE NOT LEGIBLE.
 PROVIDE LARGER DRAWINGS THAT HAVE THE ACTUAL SCALE
 SHOWN ON PLANS. SEC. 107.2.1 AND SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-01-07 Cont ID  
Sent By rrossano Date 2020-01-07 Time   Rev Time  
Received By rrossano Date 2020-01-07 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-08 Cont ID  
Sent By jgomez Date 2020-01-08 Time 09:49 Rev Time 0.00
Received By jgomez Date 2019-12-13 Time 12:51 Sent To I
Notes
2020-01-06 10:30:43TO LMARCHAN
2019-12-16 12:52:04ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By aaponte Date 2020-01-06 Time 10:30 Rev Time 0.00
Received By aaponte Date 2020-01-06 Time 10:30 Sent To ENG
Notes
***NONE***