Plan Review Details - Permit 19120548
Plan Review Stops For Permit 19120548
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2019-12-13 Cont ID  
Sent By cthroop Date 2019-12-13 Time 07:39 Rev Time 0.00
Received By cthroop Date 2019-12-13 Time 07:39 Sent To  
Notes
2019-12-13 07:40:36SEE NFIP REVIEW. CT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-14 Cont ID  
Sent By cthroop Date 2020-02-14 Time 10:24 Rev Time 0.00
Received By cthroop Date 2020-01-30 Time 13:31 Sent To  
Notes
2020-01-31 13:31:49RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-13 Cont ID  
Sent By cthroop Date 2019-12-13 Time 09:15 Rev Time 0.00
Received By cthroop Date 2019-12-13 Time 07:39 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By cthroop Date 2020-02-14 Time 10:22 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 10:16 Sent To  
Notes
2020-02-14 10:24:32PROVISO:
 1. B8 - PROPERTY IS LOCATED IN ZONE AE. REMOVE ZONE A
 FROM SECTION B8 AT FINISHED CONSTRCTION EC.
 2. C2(E) - SHOW LOWEST ELEVATION OF EQUIPT. AT FINISHED
 CONSTRCUTION EC.
 3. PROVIDE ICC EVALUATION REPORT FOR ENGINEERED FLOOD
 VENTS TO CITY BUILDING INSPECTOR.
 CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-12-13 Cont ID  
Sent By cthroop Date 2019-12-13 Time 08:21 Rev Time 0.00
Received By cthroop Date 2019-12-13 Time 07:39 Sent To  
Notes
2019-12-13 08:27:14PLAN REVIEW - NFIP - ELEVATION CERTIFICATE
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF. LINE A5 - LATITUDE AND LONGITUDE APPEAR TO BE
 INCORRECT. IT IS RECOMMENDED THAT THE FRONT CENTER OF
 THE STRUCTURE BE USED AS A REFENCE POINT.
  
 2. REF. LINE A9 B) - STATE NUMBER OF FLOOD OPENINGS IN
 ATTACHED GARAGE.
  
 3. REF. LINE A9 C) - STATE NET AREA OF FLOOD OPENINGS.
  
 4. REF. LINE A9 D) - PROPOSED FLOOD OPENINGS ARE
 NON-ENGINEERED. PROVIDE DETAIL OF OPENINGS SIGNED AND
 SEALED BY DESIGNER.
  
 5. REF. LINE B8 - PROPERTY IS LOCATED IN FLOOD ZONES -
 2% FLOOD HAZARD; AE.
  
 6. REF. LINE B9 - BASE FLOOD ELEVATIONS ARE 6 & 7.
  
 7. REF. LINE C2 E) - DOCUMENT BOTTOM OF EQIPTMENT IS AT
 OR ABOVE DFE AT FINISHED CONSTRUCTION ELEVATION
 CERTIFICATE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  