Plan Review Details - Permit 19120545
Plan Review Stops For Permit 19120545 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-01-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-01-23 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-01-23 |
Time |
12:53 |
Sent To |
|
|
Notes |
2020-01-23 12:55:37 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PLAN THAT WAS SUBMITTED E-1 DID NOT HAVE ELECTRICAL | | INFORMATION ON IT. BUT THE PLAN EMAILED TO ME WAS THE | | ELECTRICAL PAGE. A HARD COPY OF THIS PLAN SHOULD BE | | SIGNED AND SEALED AND FORWARDED TO THE CITY FOR ITS | | RECORDS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-12-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-12-23 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-12-23 |
Time |
11:13 |
Sent To |
FIRE |
|
Notes |
2019-12-23 11:15:08 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | NO ELECTRICAL LAYOUT SHOWN ACS, OULETS, LIGHTS, EXIT | | LIGHTS, EMERGENCY LIGHTS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-01-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-01-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-01-24 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-01-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-01-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-01-07 |
Time |
13:46 |
Sent To |
Z |
|
Notes |
2020-01-07 13:51:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO DIMENSIONS INDICATED BETWEEN THE | | GENERATORS AND THE A/C INTAKES. | | | | THE LOCATION OF EXHAUST SHALL BE A MINIMUM OF 10' AND | | MUST NOT BE DOWNWIND WITHIN THE 10'(SEPARATION MUST BE | | EXTENDED IF DOWNWIND) | | | | PLEASE REIVIEW AND PROVIDE DETAILS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-01-24 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-01-24 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-01-24 |
Time |
14:50 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-01-17 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-01-17 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-01-17 |
Time |
09:11 |
Sent To |
I |
|
Notes |
2020-01-17 09:11:59 | 1/17/20 FAILED. | | | | PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE | | LOCATION OF THE PROPOSED GENERATORS AND THE SETBACKS | | FROM THE PROPERTY LINES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | DEVELOPMENT SERVICES DEPARTMENT | | E-MAIL: [email protected] | | TEL: (561) 822-1442 | | |
|
|
|