Plan Review Details - Permit 19120545
Plan Review Stops For Permit 19120545
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-23 Cont ID  
Sent By jleahy Date 2020-01-23 Time 12:53 Rev Time 0.00
Received By jleahy Date 2020-01-23 Time 12:53 Sent To  
Notes
2020-01-23 12:55:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN THAT WAS SUBMITTED E-1 DID NOT HAVE ELECTRICAL
 INFORMATION ON IT. BUT THE PLAN EMAILED TO ME WAS THE
 ELECTRICAL PAGE. A HARD COPY OF THIS PLAN SHOULD BE
 SIGNED AND SEALED AND FORWARDED TO THE CITY FOR ITS
 RECORDS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-23 Cont ID  
Sent By jleahy Date 2019-12-23 Time 11:15 Rev Time 0.00
Received By jleahy Date 2019-12-23 Time 11:13 Sent To FIRE
Notes
2019-12-23 11:15:08FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NO ELECTRICAL LAYOUT SHOWN ACS, OULETS, LIGHTS, EXIT
 LIGHTS, EMERGENCY LIGHTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-24 Cont ID  
Sent By pleduc Date 2020-01-24 Time   Rev Time 0.00
Received By pleduc Date 2020-01-24 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By pleduc Date 2020-01-07 Time   Rev Time 0.00
Received By pleduc Date 2020-01-07 Time 13:46 Sent To Z
Notes
2020-01-07 13:51:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO DIMENSIONS INDICATED BETWEEN THE
 GENERATORS AND THE A/C INTAKES.
  
 THE LOCATION OF EXHAUST SHALL BE A MINIMUM OF 10' AND
 MUST NOT BE DOWNWIND WITHIN THE 10'(SEPARATION MUST BE
 EXTENDED IF DOWNWIND)
  
 PLEASE REIVIEW AND PROVIDE DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-24 Cont ID  
Sent By rfalcone Date 2020-01-24 Time 14:50 Rev Time 0.00
Received By rfalcone Date 2020-01-24 Time 14:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-17 Cont ID  
Sent By rfalcone Date 2020-01-17 Time 09:11 Rev Time 0.00
Received By rfalcone Date 2020-01-17 Time 09:11 Sent To I
Notes
2020-01-17 09:11:591/17/20 FAILED.
  
 PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE
 LOCATION OF THE PROPOSED GENERATORS AND THE SETBACKS
 FROM THE PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  