Plan Review Details - Permit 19120499
Plan Review Stops For Permit 19120499
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-02-13 Cont ID  
Sent By cpuell Date 2020-02-13 Time 16:17 Rev Time 0.00
Received By cpuell Date 2020-02-13 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2020-08-19 Time 07:53 Sent To  
Notes
2020-08-19 07:54:55PROVISO =
 1) WILL NEED TO PROVIDE SIGNED AND SEALED LOUVER SYSTEM
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609
 2) WILL NEED TO PROVIDE SIGNED AND SEALED METAL CANOPY
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609
 3) WILL NEED TO PROVIDE A SIGNED AND SEALED SOIL REPORT
 (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL
 BEARING CAPACITY PER NOTES ON THE DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 13:16 Sent To  
Notes
2020-06-22 14:05:53NEW BUILDING SHELL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL (18-0129.06 AND 17-1218.09) LISTED
 ON DRAWING A-6.0 FOR THE STOREFRONT GLAZING AND SGD
 DOES NOT MEET THE LARGE MISSILE IMPACT REQUIREMENTS PER
 FBC 1609.1.2 (1) - PLEASE PROVIDE PRODUCT APPROVAL FOR
 THE REQUIRED SHUTTERS.
  
  
 ITEMS TO PROVISO =
 1) WILL NEED TO PROVIDE SIGNED AND SEALED LOUVER SYSTEM
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609
 2) WILL NEED TO PROVIDE SIGNED AND SEALED METAL CANOPY
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609
 3) WILL NEED TO PROVIDE A SIGNED AND SEALED SOIL REPORT
 (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL
 BEARING CAPACITY PER NOTES ON THE DRAWINGS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-28 Cont ID  
Sent By rmcphers Date 2020-04-28 Time 14:19 Rev Time 0.00
Received By rmcphers Date 2020-04-27 Time 15:57 Sent To  
Notes
2020-04-28 14:19:56NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL (14-1204.10) LISTED ON DRAWING
 A-6.0 FOR THE STOREFRONT GLAZING DOES NOT MEET IMPACT
 REQUIREMENTS FBC 1609.1.2 - PLEASE PROVIDE PRODUCT
 APPROVAL NUMBER FOR THE REQUIRED SHUTTERS.
 2) PLEASE PROVIDE PRODUCT APPROVAL FOR THE METAL
 ROOFING.
 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT
 (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL
 BEARING CAPACITY PER DRAWINGS.
 4) PLEASE PROVIDE SIGNED AND SEALED SIDING ATTACHMENT
 DETAILS OR PRODUCT APPROVAL TO COMPLY WITH WIND DESIGN
 PRESSURES SHOWN ON THE DRAWINGS.
 5) PLEASE PROVIDE SIGNED AND SEALED LOUVER SYSTEM
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS.
 6) PLEASE PROVIDE SIGNED AND SEALED METAL CANOPY
 DETAILS TO COMPLY WITH THE DESIGN WIND LOADS.
 7) COVER SHEET SHOWS CODE USED "RESIDENTIAL" SHOULD BE
 "BUILDING".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 11:29 Rev Time 0.00
Received By dbattles Date 2020-02-04 Time 14:46 Sent To  
Notes
2020-02-07 11:30:16BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120499
 REVIEWED: FEBRUARY 6, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 DUE TO THE FACT THAT THESE STRUCTURES MAY BE
 RESIDENTIAL AND COMMERCIAL IN NATURE SOME CROSSOVER IN
 BUILDING CODE REVIEW WILL OCCUR. THE MOST STRINGENT OF
 THE CODES WILL APPLY.
 - PLEASE USE CODE REFERENCE IN BRACKETS AT EACH COMMENT
 AND REFER TO CODE INDEX AT THE TOP OF PAGE FOR THE CODE
 BOOK WHERE THAT THE COMMENT REFERENCES.
 419.1 FBC[B]GENERAL. A LIVE/WORK UNIT SHALL COMPLY WITH
 SECTIONS 419.1 THROUGH 419.9.
 - WHILE NOT CLARIFIED FOR THIS PERMIT IF LIVE WORK IS
 SPECIFIED FOR BUILD OUT PLEASE APPLY CHAPTER 4 SPECIAL
 REQUIREMENTS.
  
 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN.
 - PLEASE PUT FOR REFERENCE ONLY ON DEMO SHEET A1.0D.
 REMOVAL OF STRUCTURES REQUIRES A SEPARATE DEMOLITION
 PERMIT THAT HANDLES ALL ASSPECTS OF UTILITY
 DISCONNECTS.
  
 2) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND
 EPL CARD. EVEN THOUGH THE PLANS ARE FOR SHELL ONLY, THE
 THERMAL ENVELOPE NEEDS TO BE COMPLETED BY CHOSEN METHOD
 AND DOCUMENTS PROVIDED TO SHOW COMPLIANCE.
  
 3) 107.5.3 FBC[AMENDED]ADD SQUARE FOOTAGE OF SPACE
 UNDER AIR, OUTDOOR DECK SPACE AND TOTAL SPACE FOR THIS
 BUIL;DING.
 - SINCE THIS IS SHARED DECK SPLIT THE SQ. FOOTAGE
 BETWEEN THE BUILDINGS.
  
 4) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 5) [FBC 107.5][FBC 110.9][FBC R401.3]SHEET C503 FOR
 DRAINAGE SHOWS THE STUCTURES TO BE PLACED ON PADS.
 PLEASE ADJUST DRIANAGE PLAN TO ACCOUNT FOR STRUCTURES
 TO BE BUILT ON RAISED PIERS. SHOW HOW WATER WILL BE
 KEPT AWAY FROM THE CRAWL SPACE AND HOW DRAINAGE WORK
 BETWEEN STRUCTURES AS WATER DRAINS THROUGH THE DECK.
  
 6) 408.1 FBC[R] VENTILATION. THE UNDER-FLOOR SPACE
 BETWEEN THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH
 UNDER ANY BUILDING (EXCEPT SPACE OCCUPIED BY A
 BASEMENT) SHALL HAVE VENTILATION OPENINGS THROUGH
 FOUNDATION WALLS OR EXTERIOR WALLS.
 - THERE IS PLENTY OF VENTILATION, BUT TYPICALLY THE
 OPENINGS FOLLOW R408.1 WHERE IT STATES THAT OPENINGS
 ARE TO BE COVERED WITH MATERIAL PROVIDED THAT THE LEAST
 DIMENSION SHALL NOT EXCEED 1/4 INCH.
  
 7) 408.4 FBC[R] ACCESS TO UNDER FLOOR SPACE. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES. OPENINGS THROUGH A PERIMETER WALL
 SHALL BE NOT LESS THAN 16 INCHES BY 24 INCHES.
 - PLEASE INDICATE WHERE ACCESS WILL BE PROVIDED.
  
 8) PROVIDE DOCUMENTATION OF UNDER FLOOR INSULATION.
 DOES IT PROVIDE VAPOR BARRIER?
  
 9) F101.6 FBC[B]APPENDIX F. PIER AND WOOD CONSTRUCTION.
 F101.6.1 SILL LESS THAN 12 INCHES ABOVE GROUND.
 BUILDINGS NOT PROVIDED WITH A CONTINUOUS FOUNDATION
 SHALL BE PROVIDED WITH PROTECTION AGAINST RODENTS AT
 GRADE BY PROVIDING EITHER AN APRON IN ACCORDANCE WITH
 SECTION F101.6.1.1 OR A FLOOR SLAB IN ACCORDANCE WITH
 SECTION F101.6.1.2. F101.6.1.1 APRON. WHERE AN APRON IS
 PROVIDED, THE APRON SHALL BE NOT LESS THAN 8 INCHES
 (203 MM) ABOVE, NOR LESS THAN 24 INCHES (610 MM) BELOW,
 GRADE. THE APRON SHALL NOT TERMINATE BELOW THE LOWER
 EDGE OF THE SIDING MATERIAL. THE APRON SHALL BE
 CONSTRUCTED OF AN APPROVED NONDECAYABLE,
 WATER-RESISTANT RODENTPROOFING MATERIAL OF REQUIRED
 STRENGTH AND SHALL BE INSTALLED AROUND THE ENTIRE
 PERIMETER OF THE BUILDING. WHERE CONSTRUCTED OF MASONRY
 OR CONCRETE MATERIALS, THE APRON SHALL BE NOT LESS THAN
 4 INCHES (102 MM) IN THICKNESS.
 - THE PROPOSED LATTICE AT THE UNDER FLOOR AREAS WOULD
 CREATE ACCESS FOR CRITTERS TO THE UNDERSIDE OF
 STRUCTURE AND EXPOSED INSULATION. PLEASE REVIEW
 REQUIRMENTS FOR VENTILATION AND APPENDIX F FOR RODENT
 PROOFING.
  
 10) 105.10 FBC[B]CERTIFICATE OF PROTECTIVE TREATMENT
 FOR PREVENTION OF TERMITES. A WEATHER-RESISTANT
 JOB-SITE POSTING BOARD SHALL BE PROVIDED TO RECEIVE
 DUPLICATE TREATMENT CERTIFICATES AS EACH REQUIRED
 PROTECTIVE TREATMENT IS COMPLETED, PROVIDING A COPY FOR
 THE PERSON THE PERMIT IS ISSUED TO AND ANOTHER COPY FOR
 THE BUILDING PERMIT FILES. THE TREATMENT CERTIFICATE
 SHALL PROVIDE THE PRODUCT USED, IDENTITY OF THE
 APPLICATOR, TIME AND DATE OF THE TREATMENT, SITE
 LOCATION, AREA TREATED, CHEMICAL USED, PERCENT
 CONCENTRATION AND NUMBER OF GALLONS USED, TO ESTABLISH
 A VERIFIABLE RECORD OF PROTECTIVE TREATMENT. IF THE
 SOIL CHEMICAL BARRIER METHOD FOR TERMITE PREVENTION IS
 USED, FINAL EXTERIOR TREATMENT SHALL BE COMPLETED PRIOR
 TO FINAL BUILDING APPROVAL.
 - NO NOTES FOUND ON PLAN ABOUT TERMITE TREATMENT.
 PLEASE ADD OR LET ME KNOW WHAT SHEET THEY ARE LOCATED
 ON.
  
 105.11 FBC[B]NOTICE OF TERMITE PROTECTION. A PERMANENT
 SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
 AND NEED FOR REINSPECTION AND TREATMENT CONTRACT
 RENEWAL SHALL BE PROVIDED. THE SIGN SHALL BE POSTED
 NEAR THE WATER HEATER OR ELECTRIC PANEL.
 - NO NOTES FOUND ON PLAN ABOUT TERMITE TREATMENT.
 PLEASE ADD OR LET ME KNOW WHAT SHEET THEY ARE LOCATED
 ON.
  
 1816.1 FBC[B]TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 11) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
 - PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK FOR CONDENSATION CONTROL. ALSO,
 PROVIDE R-VALUE OF ALL INSULATION IN ENERGY CALCULATION
 DOCUMENTS.
  
 12) 905.1.1 FBC[R] ASPHALT SHINGLES SHALL BE USED ONLY
 ON ROOF SLOPES OF TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (2:12) OR GREATER
  
 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 - PLEASE ADD NOTE FOR DOUBLE UNDERLAYMENT.
  
 13) 1507.1.1 FBC[B]UNDERLAYMENT. UNLESS OTHERWISE
 NOTED, UNDERLAYMENT FOR ASPHALT SHINGLES, METAL ROOF
 PANELS, METAL ROOF SHINGLES, MINERAL SURFACED ROLL
 ROOFING, SLATE SHINGLES, WOOD SHINGLES, AND WOOD SHAKES
 SHALL CONFORM TO THE APPLICABLE STANDARDS LISTED IN
 THIS CHAPTER. UNDERLAYMENT MATERIALS REQUIRED TO COMPLY
 WITH ASTM D226, D1970, D4869 AND D6757 SHALL BEAR A
 LABEL INDICATING COMPLIANCE TO THE STANDARD DESIGNATION
 AND, IF APPLICABLE, TYPE CLASSIFICATION INDICATED IN
 TABLE 1507.1.1. UNDERLAYMENT SHALL BE APPLIED AND
 ATTACHED IN ACCORDANCE WITH TABLE 1507.1.1.
 - SHEET A4.0 CALLS FOR 15# FELT. PLEASE PROVIDE
 DOCUMENTATION THAT 15# COMPLIES WITH 1507.1.1. OR
 REMOVE NOTE AND SUPPLY UNDERLAYMENT PRODUCT APPROVAL
 WITH ROOFING SUB PERMIT.
  
 14) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERRED.
  
 15) PLEASE ADJUST ROOFING WIND DIAGRAMS ON SHEET S-1 TO
 MEET ASCE 7-10 TABLE 30.7.2. TYPICAL ROOF ZONE FOR
 GABLE END WOULD INCLUDE ZONE 2 AT RIDGE. ALSO, TWO ROOF
 TYPES ARE BEING UTILIZED SO ADD SHED ROOF DIAGRAM SINCE
 ZONE 3 HAS UNIQUE REQUIREMENTS.
 - THIS PERMIT IS FOR THE SHED TYPE ROOF, BUT SINCE BOTH
 BUILDING TYPES ARE SHOWN ON PLANS YOU SHOULD SHOW BOTH.
  
 16) 107.5.3 FBC[AMENDED]I FOUND ROOF PITCH ON THE ROOF
 PLAN, BUT IT WOULD BE GOOD TO HAVE THE PITCH SHOWN IN
 ELEVATION OR SECTION AS WELL.
  
 PROVISOS:
 A) DEMOLITION OF STRUCTURES TO BE DONE UNDER SEPARATE
 DEMOLITION PERMIT. IF NOT AVAILABLE AT WEBSITE HTTPS://
 WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FORMS
 PLEASE REQUEST VIA E-MAIL [email protected]
 B) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR: SIGNAGE, LIGHT POLES/SITE LIGHTING ,
 LANDSCAPING, IRRIGATION, FENCING AND PAVERS.
 C) SUBMIT TRUSS SHOP DRAWINGS TO THE BUILDING INSPECTOR
 PRIOR TO INSTALLATION. 107.3.4.1 FBC[AMENDED]
 D) DEFERRED SUBMITTALS: PROVIDE PRODUCT APPROVALS FOR
 WNDOWS, DOORS.
 ENGINEERING FOR HANDRAILS AND GUARDRAILS.
 E) NO CERTIFICATE OF OCCUPANCY CAN BE ISSUED FOR THIS
 STRUCTURE UNTIL OCCUPANCY IS DETERMINED AND INTERIOR
 BUILD OUT IS COMPLETE.
 F) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-23 Cont ID  
Sent By jleahy Date 2020-06-23 Time 15:39 Rev Time 0.00
Received By jleahy Date 2020-06-23 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By jleahy Date 2020-04-30 Time 12:42 Rev Time 0.00
Received By jleahy Date 2020-04-30 Time 08:02 Sent To  
Notes
2020-04-30 12:42:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO ADD AN OUTLET AT THE SERVICE LOCATION PER
 210.64
  
 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED WITH IN 15 M (50 FT) OF THE
 ELECTRICAL SERVICE EQUIPMENT.
  
 2) NEED AIC CALCULATION AND LABLES FOR SERVICE
 EQUIPMENT. 110.24
  
 110.24 AVAILABLE FAULT CURRENT ( A) FIELD MARKING.
 SERVICE EQUIPMENT IN OTHER THAN DWELLING UNITS SHALL BE
 LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE
 FAULT CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE
 DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE
 OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
 INVOLVED
  
 3) INTERSYSTEM BONDING CONNECTION TO BE INSTALLED AT
 SERVICE. 250.94
  
 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM BONDING
 TERMINATION FOR CONNECTING INTERSYSTEM BONDING
 CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING
 MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-16 Cont ID  
Sent By jleahy Date 2020-02-16 Time 07:48 Rev Time 0.00
Received By jleahy Date 2020-02-13 Time 09:03 Sent To  
Notes
2020-02-16 07:57:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E.1.1 IN THE SCOPE OF WORK FOR LOTS NOTE #3 HAS
 2017 NEC
  
 2) PAGE E.2.1 IN NOTE #2 YOU QUOTE NFPA-72-2010 SHOULD
 BE 2013, AND NFPA-101-2012 SHOULD BE 2015
  
 3) NOT SURE HOW TO REVIEW THESE PLANS IF FOR
 RESIDENTIAL THERE ARE MANY ITEMS MISSING. I WILL CHECK
 WITH MY SUPERVISOR FOR RECOMMENDATIONS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By rrossano Date 2020-05-01 Time   Rev Time 0.00
Received By rrossano Date 2020-05-01 Time   Sent To I
Notes
2020-05-01 14:55:11UNDER ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By rrossano Date 2020-03-16 Time   Rev Time  
Received By rrossano Date 2020-03-16 Time   Sent To I
Notes
2020-03-16 10:34:52PLEASE SUBMIT PLANS TO CITY OF WPB ENGINEERING SERVICES
 FOR FORMAL ENGINEERING REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-06-02 Cont ID  
Sent By pleduc Date 2020-06-02 Time   Rev Time 0.00
Received By pleduc Date 2020-06-02 Time 12:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By pleduc Date 2020-04-13 Time   Rev Time 0.00
Received By pleduc Date 2020-04-13 Time 13:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-02-03 Cont ID  
Sent By pleduc Date 2020-02-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-31 Time 16:33 Sent To  
Notes
2020-02-03 12:30:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 2.0 - THERE ARE TWO EXIT DOORS, ONE FROM EACH
 BUILDING, INDICATED AS SWINGING OUT ONTO TO A COVERED
 CORRIDOR.
  
 THE DOOSR OPEN INTO A PATH OF EGRESS AND NOT IN
 COMPLIANCE WITH NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-06-05 Cont ID  
Sent By fmittner Date 2020-06-05 Time 09:33 Rev Time 0.00
Received By fmittner Date 2020-06-05 Time 09:33 Sent To  
Notes
2020-06-05 09:34:01SEE NOTES FROM FIRST REVIEW

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-04-15 Cont ID  
Sent By fmittner Date 2020-04-15 Time 11:59 Rev Time 0.00
Received By fmittner Date 2020-04-15 Time 11:59 Sent To  
Notes
2020-04-15 11:59:501. WOOD SIDING DETAIL FOR ALL STRUCTURES WITH PROFILE,
 MATERIAL AND SIZE SHALL BE INCLUDED.
  
 2. ALL LATTICEWORK SHALL BE MADE OF WOOD AND NOTATIONS
 FOR VINYL SHALL BE REMOVED.
  
 3. ALL RAILINGS SHALL BE ALUMINUM OR WOOD.
  
 4. A WINDOW AND DOOR SCHEDULE SHALL BE PROVIDED FOR ALL
 STRUCTURES.
  
 5. A MUNTIN DETAIL SHALL BE PROVIDED DURING THE
 PERMITTING PROCESS (LAWSON MAY NO LONGER
 MANUFACTURE AN OGEE MUNTIN PROFILE).
 6. ALL PLANS SHALL BE CONSISTENT AND UNIFORM FOR ALL
 STRUCTURES.
  
 7. THE FAR DIAGRAM SHALL BE UPDATED TO INCLUDE THE
 PORTION OF COVERED WALKWAYS AND PATIOS IN THE
 AMOUNT AS DEFINED BY THE FAR DEFINITION FOR HISTORIC
 STRUCTURES. APPLICANT SHALL UPDATE LOT
 COVERAGE PERCENTAGE DATA TO WHOLE PERCENTAGES (E.G. 33%
 NOT .33%).
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2020-07-16 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-30 Cont ID  
Sent By lmarchan Date 2020-06-30 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-01 Cont ID  
Sent By cpuell Date 2020-05-01 Time 15:29 Rev Time 0.00
Received By cpuell Date 2020-04-10 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-19 Cont ID  
Sent By shill Date 2020-03-19 Time 13:57 Rev Time 0.00
Received By shill Date 2020-01-29 Time 11:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By lmarchan Date 2021-08-20 Time 08:59 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 13:26 Sent To  
Notes
2021-08-20 08:59:32RECEIPT MU-2020-37099 - NO IMPACT FEES DUE. LEM
2020-09-18 14:53:119/18/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 11:29 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 11:29 Sent To  
Notes
2020-02-07 11:30:31FYI WITHOUT PROVIDING OCCUPACY PBC IMPACT MAY REVIEW
 WITH MORE STRINGENT OCCUPANCY THAN IF YOU PROVIDE
 UPFRONT.
  
 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-02-26 Cont ID  
Sent By ccole Date 2020-02-26 Time 10:57 Rev Time 0.00
Received By ccole Date 2020-02-26 Time 10:57 Sent To  
Notes
2020-02-26 10:59:57SEPARATE PERMITS AND PLANS REQUIRED FOR MECHANICAL- SEE
 NOTE ON SHEET M1.1
 CCOLE-2/26/20

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-08-10 Cont ID  
Sent By jesmith Date 2020-08-10 Time 09:55 Rev Time 0.00
Received By jesmith Date 2020-08-10 Time 08:32 Sent To  
Notes
2020-08-10 09:55:41PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER AND MUST BE TESTED AND CERTIFIED BY THE CITY
 OF WEST PALM BEACH UTILITIES DEPT PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL
  
 PROVISO
 PER FBC PL 904.1, 904.1.1 AND 904.1.2, PROVIDE A 2 INCH
 VENT EXTENDING FROM THE BUILDING DRAIN TO THE OUTDOORS
 BY WAY OF A VENT THROUGH THE ROOF
 PER WPB FBC 107.2.1, PROVIDE REVISION REFLECTING THE
 REQUIREMENT FOR THE VENT TO THE OUTDOORS INCLUSIVE OF A
 RISER DIAGRAM. REVISION SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FIRST INSPECTION.
 SEE REDLINED COMMENTS APPROVED PLAN SHEET P1.1
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
  
 19120499 642 7TH ST

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-06-30 Cont ID  
Sent By rmcdouga Date 2020-06-30 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2020-06-30 Time 12:20 Sent To  
Notes
2020-06-30 16:10:57REVIEWED BY JERALD SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19120499 642 7TH ST
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 THERE WAS NO RESPONSE TO ITEM 1 OF THE SECOND REVIEW
 DATED 4/30/20
  
 THIRD REQUEST
 1. RE: PLAN SHEET P1.1; PLAN SHOWS SANITARY AND WATER
 INTO UNIT AND PROVIDES NOTE, FIXTURES SHALL BE PROVIDED
 UNDER A SEPARATE CONTRACT. PROVIDE SANITARY ROUGH- IN
 FOR FUTURE TENANT ONLY.
  
 SCOPE OF WORK IS UNCLEAR. IF IT IS THE INTENT TO STUB
 IN WATER AND SANITARY SERVICES ONLY THEN PER WPB FBC
 107.2.1, INDICATE CLEARLY ON THE PLAN BY SHOWING THE
 SERVICES TERMINATED AND CAPPED FOR FUTURE INSIDE THE
 BUILDING. AFORE MENTIONED NOTE SHOULD STATE, FIXTURES,
 SANITARY AND WATER ROUGH IN TO THE SAME SHALL BE
 PROVIDED UNDER A SEPARATE CONTRACT. PROVIDE SANITARY
 AND WATER STUB IN, TERMINATE AND CAP FOR FUTURE TENANT
 ONLY.
  
 PLEASE REFER TO RED LINED PLANS FROM SECOND REVIEW
 DATED 4/30/20 FOR ADDITIONAL CLARIFICATION
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ALL PLANS TO BE DIGITALLY SIGNED BY THE DESIGNER IN
 ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
 19120499 642 7TH ST
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 13:53 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 08:13 Sent To  
Notes
2020-04-30 08:13:44REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19120499 642 7TH ST
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 THERE WAS NO RESPONSE TO ITEM 1 OF THE FIRST REVIEW
 DATED 3/19/20
  
 SECOND REQUEST
 1. RE: PLAN SHEET P1.1; PLAN SHOWS SANITARY AND WATER
 INTO UNIT AND PROVIDES NOTE, FIXTURES SHALL BE PROVIDED
 UNDER A SEPARATE CONTRACT. PROVIDE SANITARY ROUGH- IN
 FOR FUTURE TENANT ONLY.
  
 SCOPE OF WORK IS UNCLEAR. IF IT IS THE INTENT TO STUB
 IN WATER AND SANITARY SERVICES ONLY THEN PER WPB FBC
 107.2.1, INDICATE CLEARLY ON THE PLAN BY SHOWING THE
 SERVICES TERMINATED AND CAPPED FOR FUTURE INSIDE THE
 BUILDING. AFORE MENTIONED NOTE SHOULD STATE, FIXTURES,
 SANITARY AND WATER ROUGH IN TO THE SAME SHALL BE
 PROVIDED UNDER A SEPARATE CONTRACT. PROVIDE SANITARY
 AND WATER STUB IN, TERMINATE AND CAP FOR FUTURE TENANT
 ONLY.
  
 PLEASE REFER TO RED LINED PLANS FOR ADDITIONAL
 CLARIFICATION
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ALL PLANS TO BE DIGITALLY SIGNED BY THE DESIGNER IN
 ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
 19120499 642 7TH ST
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By shill Date 2020-03-19 Time 13:57 Rev Time 0.00
Received By shill Date 2020-03-19 Time 11:06 Sent To  
Notes
2020-03-19 13:57:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19120499 642 7TH ST
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: PLAN SHEET P1.1; PLAN SHOWS SANITARY AND WATER
 INTO UNIT AND PROVIDES NOTE , FIXTURES SHALL BE
 PROVIDED UNDER A SEPARATE CONTRACT. PROVIDE SANITARY
 ROUGH- IN FOR FUTURE TENANT ONLY.
 SCOPE OF WORK IS UNCLEAR. IF IT IS THE INTENT TO STUB
 IN WATER AND SANITARY SERVICES ONLY THEN PER WPB FBC
 107.2.1, INDICATE CLEARLY ON THE PLAN BY SHOWING THE
 SERVICES TERMINATED AND CAPPED FOR FUTURE INSIDE THE
 BUILDING. AFORE MENTIONED NOTE SHOULD STATE, FIXTURES,
 SANITARY AND WATER ROUGH IN TO THE SAME SHALL BE
 PROVIDED UNDER A SEPARATE CONTRACT. PROVIDE SANITARY
 AND WATER STUB IN, TERMINATE AND CAP FOR FUTURE TENANT
 ONLY.
 2. DIGITAL SIGNATURE ON P1.1 IS NOT ACCEPTABLE. PER FS
 471 AND FAC 61G15-23.003, A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. THIS APPLIES TO ANY PLAN PAGES IN THESE
 DOCUMENTS WITH THIS DIGITAL SIGNATURE. PROVIDE
 CORRECTION PER WPB FBC 107.1.END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ALL PLANS TO BE DIGITALLY SIGNED BY THE DESIGNER IN
 ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
 19120499 642 7TH ST
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 14:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-04-28 Cont ID  
Sent By rmcphers Date 2020-04-28 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2020-04-28 Time 14:20 Sent To  
Notes
2020-04-28 14:20:32SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 11:29 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 11:29 Sent To  
Notes
2020-02-07 11:30:46SEE BUILDING COMMENTS 12-16
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2020-08-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 14:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By rmcphers Date 2020-04-28 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2020-04-28 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 11:29 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 11:29 Sent To  
Notes
2020-02-07 11:31:34ALL SHEETS OK FOR FIRST REVIEW.
 ALL ADDITIONAL SHEETS WILL NEED TO BE DIGITALLY SIGNED.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-06-05 Cont ID  
Sent By elevesqu Date 2020-06-05 Time 14:01 Rev Time 0.00
Received By elevesqu Date 2020-06-05 Time 14:01 Sent To  
Notes
2020-06-05 14:02:06PROVISOS:
 ? WITHIN 30 DAYS, PLEASE UPDATE COVER SHEET WITH
 FOLLOWING INFORMATION: RICHARD GREENE IS DEVELOPMENT
 SERVICES DIRECTOR,
 MOVED FROM ASSISTANT CITY ADMINISTRATOR AND UPDATE
 COMMISSION DISTRICT 3 ? COMMISSIONER CHRISTY FOX
 ? WITHIN 30 DAYS, PLEASE UPDATE FAR SHEET: FAR IN
 HISTORIC DISTRICT COUNTS 50% OF ROOFED BUT OPEN PORCHES
 THAT ARE ATTACHED
 TO A PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED
 BY SOLID WALLS ON MORE THAN TWO SIDES AND INCLUDES
 ROOFED BUT OPEN
 BREEZEWAYS THAT ARE ATTACHED TO A PRINCIPAL OR
 ACCESSORY STRUCTURE BUT NOT ENCLOSED BY SOLID WALLS ON
 MORE THAN TWO SIDES
 ? ELECTRICAL PANELS AND WALL MOUNTED EQUIPMENT SHALL BE
 PAINTED TO MATCH ADJACENT BUILDING COLOR
 ? ALL SIGNAGE, FENCE/GATE, AND PHOTOMETRICS SHALL BE
 REVIEWED THROUGH SEPARATE PERMIT
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By elevesqu Date 2020-04-15 Time 12:19 Rev Time 0.00
Received By elevesqu Date 2020-04-15 Time 12:19 Sent To  
Notes
2020-04-15 12:19:26COVER SHEET DOES NOT REFLECT MOST RECENT NUMBERS FOR
 NEW LOT AREA, ALLEY AREA, PERVIOUS AND IMPERIOUS AREA
 PER SITE PLAN APPROVAL - PLEASE CLARIFY
  
 RE-PLAT REQUIRES MINOR SUBDIVISION APPLICATION THROUGH
 ZONING DIVISION - NOT REVIEWED THROUGH BUIDLING PERMIT
  
 MASTER SITE PLAN DOES NOT MATCH LATEST APPROVAL -
 PLEASE REPLACE WITH CORRECT UPDATED SHEET
  
 PLEASE INDICATE ON MASTER PLAN LOCATION FOR BICYCLE
 RACKS THAT WERE REQUIRED AS CONDITION OF APPROVAL
 THROUGH THE SITE PLAN APPROVAL LETTER- TWO ADDITIONAL
 NEEDED WITHIN THE PRIVATE PROPERTY - CAN BE ON MULTIPLE
 LOTS. STAFF ALSO RECOMMENDS ADDITIONAL BICYCLE RACKS
 ALONG 7TH STREET AND ALLEY ADJACENT TO PROJECTS (CAN BE
 COORDINATED WITH HDR)
  
 PLEASE HASH OUT OR REMOVE NON APPLICABLE ENLARGED SITE
 PLANS THAT ARE NOT RELEVANT FOR SPECIFIC PERMIT - FOR
 EXAMPLE, LOT 7 IN THIS PERMIT ON SHEET A1.1
 SHEET A1.1 NOT LATEST PLAN FROM SITE PLAN SUBMITTAL
  
 DIMENSIONS ON SHEET A2.0 DO NOT MATCH LATEST SITE PLAN
 SUBMITTAL - PLEASE CLARIFY
  
 THERE ARE TWO DIFFERENT FOUNDATION PLANS AND ROOFING
 PLANS - PLEASE REMOVE WHAT IS DUPLICATIVE
  
 DUPLICATIVE SECTION SHEETS - REMOVE WHAT IS DUPLICATIVE
  
 IS PAVER AREA IN YARD THROUGH SEPARATE PERMIT? PLEASE
 CLARIFY WITH BUILDING DIVISION
  
 INDICATE LOCATION OF PROPOSE ABOVE GROUND UTILITIES
  
 INCLUDE FAR DIAGRAM - UPDATED PER CONIDTION OF APPROVAL
 FROM SITE PLAN APPROVAL LETTER
  
 SEPARATE PERMIT REQUIRED FOR LANDSCAPE, LIGHTING,
 FENCE, SIGNAGE (IF NOT ALLREADY SUBMITTED)
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By eleveque Date 2020-02-11 Time 16:39 Rev Time 0.00
Received By elevesqu Date 2020-02-11 Time 16:39 Sent To  
Notes
2020-02-11 16:39:33APPLICATION Z18070021 HAS NOT RECEIVED SITE PLAN
 APPROVAL - REQUIRED PRIOR TO PERMIT APPROVAL
  
 ONCE SITE PLAN APPROVAL HAS BEEN GRANTED, PLEASE ENSURE
 ALL SUBMITTED PLANS MATCH THE SITE PLAN APPROVAL PLANS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426