2019-12-05 10:10:58 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC B 107.2.1. PLEASE IDENTIFY ON PLANS ALL TENET |
| SEPARATION WALLS AND CORRIDOR SEPARATION WALLS. THE |
| INTEGRITY OF ALL FIRE RATED CEILINGS, FLOORS AND WALLS |
| MUST BE MAINTAINED. |
| 2. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING |
| CONSTRUCTION METHOD OF PROPOSED NEW SHOWER WALLS/FLOORS |
| AND SHOWING COMPLIANCE WITH 2509.2 AND 1210.2 FBC B. |
| 3. FBC B 107.2.1. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| 4. PROVIDE THE FOLLOWING TEST REPORTS FOR PROFLEX |
| RCU-250. MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE. |
| 5. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| 6. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| 7. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |