Plan Review Details - Permit 19120033
Plan Review Stops For Permit 19120033
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By jwitmer Date 2019-12-16 Time 07:14 Rev Time 0.00
Received By jwitmer Date 2019-12-16 Time 06:06 Sent To  
Notes
2019-12-16 07:14:50, ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By jwitmer Date 2019-12-16 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2019-12-16 Time 06:06 Sent To  
Notes
2019-12-16 07:07:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120033
 ADD: 710 10TH STREET
 CONT: CILAS CONCRETE
 TEL: 561-689-3429
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 16TH/ 2019
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THIS PERMIT IS FOR
 INTERIOR DEMO OF DRYWALL FOR NEW ELECTRICAL, INSIDE
 ONLY. THE SCOPE OF WORK SHOWN ON THE PLANS SHEET A-1 IS
 FOR MORE THAN INTERIOR OF DEMO. THE VALUE OF THE WORK
 IS FOR $2,300.00 DOLLARS, WHICH IS INLINE BUT LOW FOR
 THE REMOVAL OF INTERIOR DRYWALL FOR AN 8 UNIT APARTMENT
 BUILDING. PLEASE ALSO NOTE THE INDEX OF DRAWINGS
 INDICATES SHEET A2 TO BE THE DEMO PLAN. THERE IS NO
 SHEET A-2 BUT THERE IS A D-1 WHICH DOES SHOW INTERIOR
 DEMO. PLEASE NOTE THERE IS MORE WORK JUST INTERIOR DEMO
 OF DRYWALL, THE REMOVAL OF THE ENTIRE SERVICE ENCLOSURE
 AND ALL FLOORING IN THE KITCHEN AND BATHROOMS TO EXPOSE
 THE PLUMBING PIPES. IS THIS WORK TO ALSO BE INCLUDED IN
 THE INTERIOR DEMO PERMIT AND THE ASSOCIATED VALUE OF
 WORK FOR 8 APARTMENTS? IF THIS IS PERMIT IS FOR
 INTERIOR DEMO DO NOT ICLUDE SHEET A-1!!!!!!
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By jleahy Date 2019-12-18 Time 15:19 Rev Time 0.00
Received By jleahy Date 2019-12-18 Time 15:19 Sent To  
Notes
2019-12-18 15:21:26FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED AN ELECTRICAL PERMIT FOR THE DEMO BEFORE PERMIT
 CAN BE ISSUED
  
 ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] AND [email protected] SO WE RECEIVE IT
 ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS
 WILL APPROVE THE PLAN REVIEW. THE ORIGINAL PERMIT
 APPLICATION MUST BE SUBMITTED WHEN THE PERMIT IS PICKED
 UP.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-04 Cont ID  
Sent By pleduc Date 2019-12-04 Time   Rev Time 0.00
Received By pleduc Date 2019-12-04 Time 14:59 Sent To  
Notes
2019-12-04 15:02:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS AN INDICATION OF INSTALLING NEW SMOKE
 DETECTORS IN THE BEDROOMS/SLEEPING AREAS.
  
 SMOKE ALARMS ARE TO INSTALLED OUTSIDE SLEEPING AREAS
 PER NFPA 101, CH 31, EXISTING APARTMENT OCCUPANCIES'
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL
 NOT BE REQUIRED TO
 BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE.
  
 PLEASE PROVIDE SMOKE ALARMS IN THE HALL AREAS OF EACH
 UNIT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-18 Cont ID  
Sent By jleahy Date 2019-12-18 Time 15:21 Rev Time 0.00
Received By jleahy Date 2019-11-26 Time 13:49 Sent To  
Notes
2019-12-02 13:49:47B05

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By jesmith Date 2019-12-17 Time 16:00 Rev Time 0.00
Received By jesmith Date 2019-12-17 Time 15:58 Sent To  
Notes
2019-12-17 16:00:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3 PROVIDE THE
 FOLLOWING INFORMATION
 DRAWING INDEX NOTES PLUMBING DRAWINGS PLAN SHEETS P-1
 AND P-2. PROVIDE THESE DRAWINGS FOR COMPREHENSIVE
 REVIEW.
 BASED UPON THE THE SCOPE OF WORK NOTES AND THE
 RECONFIGURATIONS NOTED BELOW, THE CLASSIFICATION OF
 WORK IS LEVEL 2, NOT LEVEL 1.
 ADDITIONAL COMMENTS AFTER REVIEW OF PLAN SHEETS A-1 AND
 D-1
 1. PLAN SHEET D-1 (DRAWING INDEX NOTES A-2 AS
 DEMOLITION PLAN; PLEASE CLARIFY): DEMOLITION PLAN.
 EXISTING WATER HEATERS; SHOW LOCATION OF EXISTING WATER
 HEATERS IN END APARTMENTS. PROVIDE EXISTING WATER
 HEATER SCHEDULE INDICATING STORAGE CAPACITY AND
 ELECTRICAL CHARACTERISTICS.
 2. PLAN SHEET A-1; SHOW LOCATION OF ALL WATER HEATERS
 ON FINISH FLOOR PLAN. KITCHENS ARE RECONFIGURED.
 3. PLAN SHEET A-1; SCOPE OF WORK. KITCHENS ARE
 RECONFIGURED. EXISTING WATER HEATERS SHALL BE REPLACED
 WITH NEW WATER HEATERS. PROVIDE DETAIL AND WATER HEATER
 SCHEDULE INDICATING MANUFACTURER, MODEL, STORAGE
 CAPACITY AND ELECTRICAL CHARACTERISTICS. COMPLY WITH
 FBC PL SECTION 504 AND FBC PL 607.3.
 4. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A
 SANITARY RISER DIAGRAM AND PLAN VIEW LAYOUT TO SHOW
 CHANGES. COMPLY WITH FBC PL CHAPTER 7 AND CHAPTER 9
 5. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A
 WATER DISTRIBUTION RISER DIAGRAM AND PLAN VIEW LAYOUT
 TO SHOW CHANGES. COMPLY WITH FBC PL CHAPTER 6.
 6. PROVIDE SHOWER DETAIL (ELEVATION VIEW). SHOW
 COMPLIANCE WITH FBC PL SECTION 417.
 7. PROVIDE MATERIAL TYPE FOR SANITARY DRAINS AND VENTS.
 8. PROVIDE MATERIAL TYPE FOR WATER DISTRIBUTION
 9. PROVIDE UL RATED ASSEMBLIES FOR THROUGH THE FLOOR
 PIPING PENETRATIONS IN THE ELEVATED FLOOR. COMPLY WITH
 FBC CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120033 710 10TH ST
  