Plan Review Details - Permit 19110900
Plan Review Stops For Permit 19110900
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-06 Cont ID  
Sent By rmcdouga Date 2020-03-06 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2020-03-06 Time 08:37 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-07 Cont ID  
Sent By rmcdouga Date 2020-02-07 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2020-02-07 Time 17:50 Sent To I
Notes
2020-02-07 18:28:12PERMIT VALUE CHANGED FROM $12,000.00 TO $15,000.00
 BASED ON CONTRACT SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-22 Cont ID  
Sent By rmcdouga Date 2019-11-22 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2019-11-22 Time 15:38 Sent To I
Notes
2019-11-22 16:16:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. (PROVIDE A
 COMPLETE SCOPE OF WORK ON THE PLANS.) SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) PROVIDE A COPY OF THE SIGNED CONTRACT TO VERIFY THE
 VALUE OF THE WORK. FBC 109.3 BUILDING PERMIT VALUATION.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 5) RE-SUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-05 Cont ID  
Sent By jpearson Date 2020-03-05 Time 10:39 Rev Time 0.00
Received By jpearson Date 2020-03-05 Time 10:39 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-02-07 Cont ID  
Sent By jpearson Date 2020-02-07 Time 13:32 Rev Time 0.00
Received By jpearson Date 2020-02-07 Time 13:32 Sent To  
Notes
2020-02-07 13:32:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED(AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481 (PLAN
 NOT SIGNED AND SEALED BY DESIGNER. PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 09:34 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 09:34 Sent To  
Notes
2019-11-21 09:34:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED(AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-06 Cont ID  
Sent By lcrespo Date 2020-03-06 Time 16:54 Rev Time 0.00
Received By lcrespo Date 2020-02-27 Time 13:05 Sent To  
Notes
2020-02-28 13:05:21RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-07 Cont ID  
Sent By rmcdouga Date 2020-02-07 Time 18:28 Rev Time 0.00
Received By rmcdouga Date 2020-02-05 Time 16:29 Sent To  
Notes
2020-02-06 16:29:30R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-22 Cont ID  
Sent By rmcdouga Date 2019-11-22 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2019-11-19 Time 14:28 Sent To  
Notes
2019-11-20 14:29:06R25

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-06 Cont ID  
Sent By lcrespo Date 2020-03-06 Time 16:53 Rev Time 0.00
Received By lcrespo Date 2020-03-06 Time 16:53 Sent To  
Notes
2020-03-06 16:54:4803/06/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-02-07 Cont ID  
Sent By lcrespo Date 2020-02-07 Time 16:34 Rev Time 0.00
Received By lcrespo Date 2020-02-07 Time 08:04 Sent To  
Notes
2020-02-07 16:34:4802/07/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 2. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS PER THE 2017 FBC SEC
 R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-22 Cont ID  
Sent By lcrespo Date 2019-11-22 Time 15:30 Rev Time 0.00
Received By lcrespo Date 2019-11-22 Time 15:30 Sent To  
Notes
2019-11-22 15:30:5911/22/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  